MACX MCR-SL-2NAM-RO-SP
-
Isolation switch amplifier
2924294
NAMUR 2-channel signal conditioner for operating proximity sensors and switches. The signals are transferred to the control level using relay outputs (N/O contact). Line fault detection, 3-way electrical isolation, SIL 2, Push-in connection.
Free download available.
Downloads
Product details
Product type | Isolating switch amplifier |
Product family | MACX Analog |
Application | Digital IN |
No. of channels | 2 |
Type | Signal conditioners with SIL functional safety |
Configuration | DIP switches |
Functionality | |
Configuration | DIP switches |
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Maximum power dissipation for nominal condition | < 1 W |
Electrical isolation Input/output IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VPP |
Overvoltage category | III |
Pollution degree | 2 |
Electrical isolation Input/supply, DIN rail connector IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VPP |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/supply, DIN rail connector IEC/EN 61010-1 | |
Standards/regulations | IEC/EN 61010-1 |
Rated insulation voltage | 300 Vrms |
Overvoltage category | II |
Pollution degree | 2 |
Insulation | Safe isolation |
Electrical isolation Output 1/output 2/input, power supply, DIN rail connector IEC/EN 61010-1 | |
Standards/regulations | IEC/EN 61010-1 |
Rated insulation voltage | 300 Vrms |
Overvoltage category | III |
Pollution degree | 2 |
Insulation | Safe isolation |
Electrical isolation Output 1/output 2/input/power supply, DIN rail connector | |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Overvoltage category | III |
Pollution degree | 2 |
Supply | |
Nominal supply voltage | 24 V DC -20 % ... +25 % |
Supply voltage range | 19.2 V DC ... 30 V DC |
Max. current consumption | 35 mA (24 V DC) |
Power dissipation | < 1 W |
Power consumption | < 1 W |
Signal: NAMUR | |
Number of inputs | 2 |
Available input sources | NAMUR proximity sensors (IEC/EN 60947-5-6) |
floating switch contacts | |
Switch contacts with resistance circuit | |
Switching threshold "0" signal current | < 1.2 mA (blocking) |
Switching threshold "1" signal, current | > 2.1 mA (conductive) |
Short-circuit current | 8 mA |
Switching hysteresis | < 0.2 mA |
Line fault detection | < 0.05 mA ... 0.35 mA (Line break) |
< 100 Ω ... 360 Ω (Short circuit) | |
Activated /deactivated via DIP switch | |
Non-load voltage | 8 V DC |
Switching: Relay | |
Contact switching type | 1 N/O contact per channel |
Contact material | AgSnO2, hard gold-plated |
Maximum switching voltage | 250 V AC (2 A) |
120 V DC (0.2 A) | |
30 V DC (2 A) | |
Maximum switching capacity | 500 VA |
Recommended minimum load | 5 V / 10 mA |
Switching frequency | ≤ 20 Hz (without load) |
Signal | |
Number of outputs | 2 |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) |
0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) | |
Conductor cross section AWG | 24 ... 14 |
24 ... 22 (TWIN ferrule without plastic sleeve) | |
20 ... 16 (TWIN ferrule with plastic sleeve) |
Ex installation (EPL) | Gc |
Div. 2 |
Data | |
No. of channels | 0 |
Status display | Green LED (supply voltage) |
LED yellow (switching state) | |
Red LED (line errors) |
Dimensional drawing |
|
Width | 12.5 mm |
Height | 107.9 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing material | PA 6.6-FR |
Safety data | |
Safety Integrity Level (SIL) | 2 |
Safety data: IEC 61508 - Low demand | |
Safety Integrity Level (SIL) | 2 |
Safety data: IEC 61508 - Low demand | |
Safety Integrity Level (SIL) | 2 |
Ambient conditions | |
Degree of protection | IP20 (not assessed by UL) |
Ambient temperature (operation) | -40 °C ... 60 °C (Any mounting position) |
-40 °C ... 70 °C (Derating) | |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m) | |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient temperature (operation) | -40 °C ... 60 °C |
-40 °C ... 70 °C (Derating) | |
Rated insulation voltage | 253 V AC (Power supply, input / output) |
125 V DC (Power supply, input / output) | |
Altitude range (≤ 3000 m) | |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -40 °C ... 54 °C |
-40 °C ... 63 °C (Derating) | |
Rated insulation voltage | 190 V AC (Power supply, input / output) |
110 V DC (Power supply, input / output) | |
Altitude range (≤ 4000 m) | |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -40 °C ... 48 °C |
-40 °C ... 56 °C (Derating) | |
Rated insulation voltage | 60 V AC/DC (Power supply, input / output) |
Altitude range (≤ 5000 m) | |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -40 °C ... 42 °C |
-40 °C ... 49 °C (Derating) | |
Rated insulation voltage | 60 V AC/DC (Power supply, input / output) |
CE | |
Certificate | CE-compliant |
Note | and EN 61326-1 |
ATEX | |
Identification | II 3G Ex ec nC IIC T4 Gc |
Certificate | IBExU 07 ATEX 1069 X |
IECEx | |
Identification | Ex ec nC IIC T4 Gc |
Certificate | IBE 08.0001 X |
CCC / China-Ex | |
Identification | Ex ec nC IIC T4 Gc |
Certificate | 2021122304114179 |
UL, USA/Canada | |
Identification | UL 508 Listed |
UL 61010 Listed | |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Group IIC T4 | |
Shipbuilding approval | |
Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | 2 |
Certificate | IN-AT-AS-MRL-24-00163 |
Systematic Capability | |
Identification | 3 |
INMETRO | |
Identification | Ex ec nC IIC T4 Gc |
Certificate | DNV 18.0114 X |
EAC Ex | |
Identification | 2Ex ec nC IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00078 |
Shipbuilding data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 |
EN 61326 | |
Noise emission | |
Standards/regulations | EN 61000-6-4 |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Evaluation criterion | A |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Evaluation criterion | A |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Evaluation criterion | A |
Electrical isolation | 3-way isolation |
GB Standard | |
Standards/regulations | GB/T 3836.1 |
GB/T 3836.3 | |
GB/T 3836.8 |
Mounting type | DIN rail mounting |
Item number | 2924294 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | CK1 |
Product key | DK1113 |
Catalog page | Page 136 (C-5-2019) |
GTIN | 4046356492096 |
Weight per piece (including packing) | 179 g |
Weight per piece (excluding packing) | 140 g |
Customs tariff number | 85365019 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27210121 |
ETIM
ETIM 9.0 | EC001485 |
UNSPSC
UNSPSC 21.0 | 39121000 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol (CAS: 79-94-7) | |
SCIP | d94a74ea-7c4d-4d0a-9120-9af75e6e640f |
Compatible products
-
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - DIN rail bus connector 2695439
-
ME 6,2 TBUS-PR-ADAPTER - DIN rail bus connector 1136500
-
MCR-DP - Separating plate 1430594
-
TC-2D37SUB-ADIO32-2EX-P-UNI - Module carrier 2904684
-
MPS-IH WH - Insulating sleeve 0201663
-
MPS-IH RD - Insulating sleeve 0201676
-
MPS-IH BU - Insulating sleeve 0201689
-
MPS-IH YE - Insulating sleeve 0201692
-
MPS-IH GN - Insulating sleeve 0201702
-
MPS-IH GY - Insulating sleeve 0201728
-
MPS-IH BK - Insulating sleeve 0201731
-
MPS-MT - Test plug 0201744
-
UC-EMLP (11X9) - Plastic label 0819291
-
UC-EMLP (11X9) YE - Plastic label 0822602
-
UC-EMLP (11X9) CUS - Plastic label 0824547
-
UC-EMLP (11X9) YE CUS - Plastic label 0824548
-
UC-EMLP (11X9) SR - Plastic label 0828094
-
UC-EMLP (11X9) SR CUS - Plastic label 0828098
-
US-EMLP (11X9) - Plastic label 0828789
-
US-EMLP (11X9) YE - Plastic label 0828871
-
US-EMLP (11X9) SR - Plastic label 0828872
-
LS-EMLP (11X9) WH - Device marker 0831678
-
LS-EMLP (11X9) SR - Device marker 0831705
-
LS-EMLP (11X9) YE - Device marker 0831732
-
MACX MCR-PTB - Power and error message module 2865625
-
MACX MCR-PTB-SP - Power and error message module 2924184
-
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
-
D-UKK 3/5 - End cover 2770024
-
D-UKK 3/5 BU - End cover 2770105
-
UKK 5-2R/NAMUR - Component terminal block 2941662
-
SZS 0,6X3,5 - Screwdriver 1205053
-
MACX SET-TVFKC 2-POLE - Connector set 1584383
Your advantages
Power supply and error indication possible via DIN rail connector
Up to SIL 2 in accordance with EN 61508
Installation in zone 2, protection type "n" (EN 60079-15) permitted
Line fault detection (LFD), can be activated/deactivated, error indicated by flashing red LED with de-excitation of output relay
LED indicators for supply voltage, switching state, and malfunction in accordance with NAMUR NE 44
Direction of operation can be selected (operating or closed circuit current behavior)
3-way electrical isolation
2-channel
Relay signal output (N/O contact)
Input for NAMUR proximity sensors (EN 60947-5-6), floating contacts or contacts with resistance circuit