The terminal is designed for use within an Inline station. This terminal can be used to acquire signals from standard thermocouples. The terminal supports type J thermocouples according to DIN EN 60584-1. The measured values are depicted in standardized representation format. Inline ECO terminals are approved for the temperature range from 0°C to +55°C. The electronics base and Inline connector are supplied as standard.
    
  
  IB IL UTH 4/J-ECO
   - 
  Temperature module
    
      2702502
      
      
    
  
      Inline, Temperature measurement terminal, Analog UTH inputs: 4 (Type J), connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector
      Free download available.
      Downloads
    
  Product details
| Dimensional drawing |  | 
| Width | 12.2 mm | 
| Height | 119.8 mm | 
| Depth | 71.5 mm | 
| Note on application | |
| Note on application | Only for industrial use | 
| Inline local bus | |
| Number of interfaces | 2 | 
| Connection method | Inline data jumper | 
| Transmission speed | 500 kbps | 
| Module | |
| ID code (dec.) | 126 | 
| ID code (hex) | 7E | 
| Length code (hex) | 04 | 
| Length code (dec) | 04 | 
| Process data channel | 64 bit | 
| Input address area | 8 Byte | 
| Output address area | 0 Byte | 
| Register length | 64 bit | 
| Required parameter data | 1 Byte | 
| Required configuration data | 4 Byte | 
| Analog | |
| Input name | Analog UTH inputs | 
| Description of the input | Differential inputs | 
| Number of inputs | 4 (Type J) | 
| Connection method | Inline connector | 
| Connection technology | 2-conductor | 
| Note regarding the connection technology | shielded | 
| A/D conversion time | typ. 120 ms | 
| A/D converter resolution | 24 bit | 
| Sensor types that can be used (TC) | J | 
| Measuring principle | Sigma/Delta process | 
| Measured value representation | 16 bits (15 bits + sign bit) | 
| Process data update | < 10 ms | 
| Protective circuit | Transient protection of inputs | 
| Product type | I/O component | 
| Product family | Inline | 
| Type | modular | 
| Installation location | Control cabinet | 
| Scope of supply | including Inline connector | 
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler | 
| Checksum error I/O error message sent to the bus coupler | 
| Maximum power dissipation for nominal condition | 1.35 W | 
| Potentials: Communications power (UL) | |
| Supply voltage | 7.5 V DC (via voltage jumper) | 
| Current draw | max. 55 mA | 
| typ. 38 mA | |
| Potentials: Supply of analog modules (UANA) | |
| Supply voltage | 24 V DC (via voltage jumper) | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Current draw | max. 39 mA | 
| typ. 32 mA | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Bus logic (local bus, communications power) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Analog I/O | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Functional ground | 500 V AC, 50 Hz, 1 min | 
| Connection technology | |
| Connection name | Inline connector | 
| Conductor connection | |
| Connection method | Spring-cage connection | 
| Conductor cross-section rigid | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section flexible | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 28 ... 16 | 
| Stripping length | 8 mm | 
| Inline connector | |
| Connection method | Spring-cage connection | 
| Conductor cross-section, rigid | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 28 ... 16 | 
| Stripping length | 8 mm | 
| Ambient conditions | |
| Ambient temperature (operation) | 0 °C ... 55 °C | 
| Degree of protection | IP20 | 
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Ambient temperature (storage/transport) | -25 °C ... 85 °C | 
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) | 
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) | 
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | 
| Mounting type | DIN rail mounting | 
| Item number | 2702502 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DRI | 
| Product key | DRI143 | 
| GTIN | 4055626206059 | 
| Weight per piece (including packing) | 87.9 g | 
| Weight per piece (excluding packing) | 69 g | 
| Customs tariff number | 85389099 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27242601 | 
| ECLASS-15.0 | 27242601 | 
ETIM
| ETIM 9.0 | EC001596 | 
UNSPSC
| UNSPSC 21.0 | 32151600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I, 7(c)-II | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | f1f342b6-9d43-4dfb-a780-31b384850f73 | 
Compatible products
- 
    
      IB IL SCN-8 - Inline connector 2726337
- 
    
      SKS 8 - Shield connection terminal block 3240210
- 
    
      SK 8 - Shield connection terminal block 3025163
- 
    
      SCC 15-NS35 - Shield connection terminal block 1019443
- 
    
      AB/SKS - Support bracket 3240224
- 
    
      AB-SK/E - Support bracket 3026476
- 
    
      NLS-CU 3/10 SN 1000MM - Neutral busbar 0402174
- 
    
      IL CP - Coding star 2742683
- 
    
      IB IL FIELD 2 - Marking field 2727501
- 
    
      EMT (62X10)R - Insert label 0800057
- 
    
      ZBF 6:UNBEDRUCKT - Zack Marker strip, flat 0808710
- 
    
      UCT-TMF 6 - Marker for terminal blocks 0828746
- 
    
      UC-TMF 6 - Marker for terminal blocks 0818140
- 
    
      ZBF 12:UNBEDRUCKT - Zack Marker strip, flat 0809735
- 
    
      UCT-TMF 12 - Marker for terminal blocks 0829214
- 
    
      UC-TMF 12 - Marker for terminal blocks 0819233
Your advantages
4 differential inputs for thermocouples
        Measuring range: -210 °C ... +1200 °C
        Connection of sensors in 2-conductor technology
        Diagnostic information in the process data word
        Diagnostic indicator