IB IL 24 FLM-PAC
-
Communication module
2736903
Inline, Branch terminal, for extending the Inline local bus, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connector and labeling field
Product details
Dimensional drawing |
|
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Note on application | |
Note on application | Only for industrial use |
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Utilization restriction | |
CCCex note | Use in potentially explosive areas is not permitted in China. |
Inline local bus | |
Number of interfaces | 1 (incoming local bus) |
Connection method | Inline data jumper |
Transmission speed | 500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds) |
Inline local bus | |
No. of channels | outgoing local bus |
Connection method | Inline shield connector |
Note on the connection method | Standard INTERBUS cable |
Transmission speed | 500 kbps / 2 Mbps |
Module | |
ID code (dec.) | none |
ID code (hex) | none |
Input address area | 0 Byte |
Output address area | 0 Byte |
Register length | 0 Byte |
Required parameter data | 0 Byte |
Required configuration data | 0 Byte |
Product type | I/O component |
Product family | Inline |
Type | modular |
Scope of supply | including Inline connector and labeling field |
Special properties | for extending the Inline local bus |
Maximum power dissipation for nominal condition | 0.85 W |
Potentials: Communications power (UL) | |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current draw | 110 mA |
Potentials | |
Supply voltage | 24 V DC |
Current draw | max. 6 A (Fieldline Modular M8 local bus, with both-side supply; maximum 3 A for go and return line each) |
max. 55 mA (internal) |
Connection technology | |
Connection name | Inline connector |
Conductor connection | |
Connection method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector | |
Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 55 °C |
Degree of protection | IP20 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 75 % (On average, 85 % occasionally) |
Permissible humidity (storage/transport) | 75 % (On average, 85 % occasionally) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Item number | 2736903 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DRI |
Product key | DRI152 |
Catalog page | Page 147 (C-6-2019) |
GTIN | 4046356079204 |
Weight per piece (including packing) | 93 g |
Weight per piece (excluding packing) | 43 g |
Customs tariff number | 85389099 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27242608 |
ETIM
ETIM 9.0 | EC001604 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | d40353be-44b3-4e43-bd3b-e984f74d5bf8 |
Compatible products
-
IB IL SCN 6-SHIELD-TWIN - Inline shield connector 2740245
-
IL CP - Coding star 2742683
-
IB IL FIELD 2 - Marking field 2727501
-
EMT (62X10)R - Insert label 0800057
-
ZBF 6:UNBEDRUCKT - Zack Marker strip, flat 0808710
-
UCT-TMF 6 - Marker for terminal blocks 0828746
-
UC-TMF 6 - Marker for terminal blocks 0818140
-
ZBF 12:UNBEDRUCKT - Zack Marker strip, flat 0809735
-
UCT-TMF 12 - Marker for terminal blocks 0829214
-
UC-TMF 12 - Marker for terminal blocks 0819233
-
IB IL 24 SEG/F-D-PAC - Segmentation module 2861904
-
IBS RBC METER/F-T - Remote bus cable 2723123
-
IBS RBC METER-T - Remote bus cable 2806286
Your advantages
Connection of Fieldline Modular M8 to Fieldline Modular M12
Connection of Fieldline Modular M8 or M12 to Inline Modular