CAPAROC PM S-R - Feed-in module
1115661

Power module with status output and reset input for supplying the CAPAROC circuit breaker system with 12 or 24 V DC. For DIN rail installation via the CAPAROC current rails.

This product needs further products for operation. Mandatory accessories

Product details









Compatible products




Your advantages

The benchmark that you can customize by selecting single signals and resets all the way to PROFINET communication
Particularly easy operation for everyone with tool-free assembly, direct feed-in to the busbar, and clear operating states
Exceptionally easy design-in thanks to the comprehensive digital data packet and PROFINET function blocks

Frequently asked questions


What signals does the CAPAROC PM S-R power module provide?

The module has three different connection options for the signals:
 
S - Status output: Potential-bound collective signal, this indicates the status of the system. If there is at least one fault shutdown, this outputs a message.
High (24 V) ... View more

The module has three different connection options for the signals:
 
S - Status output: Potential-bound collective signal, this indicates the status of the system. If there is at least one fault shutdown, this outputs a message.
High (24 V) = there is no fault
Low (0 V) = there is at least one fault shutdown
Maximum current 20 mA
 
RST - Reset input: Channels that have been switched off by an error are switched on again via a falling edge.
 
I > 80%-signal output: Potential-bound collective signal, if the current flowing on a channel is greater than 80% of the set nominal current, a HIGH signal (24 V) is out

View less

Is there a hardware tutorial in which the CAPAROC functions are explained?

video thumbnail of faq answer

Yes, there is a hardware tutorial to make getting started with CAPAROC easier.... View more

Yes, there is a hardware tutorial to make getting started with CAPAROC easier.

View less

How many circuit breaker modules can I connect downstream of an infeed module?

CAPAROC PM S-R: 20 circuit breaker modules
CAPAROC PM IOL: 20 channels
CAPAROC PM PN: 16 circuit breaker modules
CAPAROC PM EIP: 16 circuit breaker modules
CAPAROC PM MB: 16 circuit breaker modules
CAPAROC PM EC: 16 circuit breaker modules


The channel LED flashes yellow twice every 4 seconds. What does this mean?

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the... View more

This means that the internal communication to the power module is interrupted or faulty.
Check that the modules are mounted correctly and that there is no gap between the modules. If communication is still disrupted, check the side contacts of the first module (left) that is flashing, if they are bent, either too far into the module, not centered in the housing opening or otherwise damaged, replace the module.

View less

Can I block the setting of the set currents?

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to fla... View more

The currents can be locked in different ways:
1. Programming lock: press the PWR button on the power module for > 3 seconds, the PWR LED flashes yellow 3 x, the settings are now locked. Pressing it again for > 3 seconds causes the LED to flash green 3 times and unlocks it again.
2. The lock can also be set and released via the communication interface; the operating lock can also be set here, which prevents operation and settings on the device. The lock can then only be released via the interface.

View less