With the Inline Control CPU, the Inline station is transformed into a modular compact controller. The Inline controller is installed instead of the standard Inline bus terminal module. Thwe Inline Control connects the station to the higher-level network, just like a bus terminal module.
The integrated control functions can be programmed according to IEC 61131-3. These functions permit distributed and independent control of the Inline installation system. Fast inputs and outputs ensure short response times.
Use of the Inline controller or other Remote Field Controllers permits to set up pre-tested mechanical and electrical units that can be combined as desired to form a complete solution. By combining tested mechanical, electrical, I/O device and control program functional units, planning, installation and startup times are considerably reduced. Systems can also be expanded in a flexible manner by following this principle.
Programming with PC WORX
The Inline controller is programmed with PC WORX automation software. The programs are created using the international IEC 61131-3 standard. They are downloaded either over the INTERBUS interface or over the local RS-232 interface. Programs and configuration data are stored in the integrated flash memory in a non-volatile way. 8 Kbytes of non-volatile (NV)RAM is available for the remanent storage of variables and flags.
ILC 200 IB
-
Controller
2729800
Inline controller, without connecting plug and labeling field. The controller is installed instead of a standard Inline bus coupler. It connects the station to the higher-level INTERBUS network in the same way as a bus coupler.
Product details
Product type | Controller |
Product family | Inline |
Type | modular |
Display | |
Diagnostics display | no |
Retentive data storage | 8 kByte (NVRAM) |
IEC 61131 runtime system | |
Program memory | typ. 384 kByte (32 K instructions (IL)) |
Data storage system | 330 kByte |
Number of control tasks | 8 |
INTERBUS-Master | |
Amount of process data | max. 4096 bit (INTERBUS-Master) |
Number of parameter data | max. 8 Byte (configurable) |
Number of supported devices | max. 512 (of which 254 are remote bus devices/bus segments) |
Number of local bus devices that can be connected | max. 63 (observe current consumption) |
Number of devices with parameter channel | max. 62 |
Number of supported branch terminals with remote bus branch | max. 15 |
Function | |
Diagnostics display | no |
Redundancy function | no |
Local diagnostics | |
Designation | BA, RC, RD, TR |
Monitored function | Higher-level network |
Optical representation | LED |
Module | |
ID code (dec.) | 3 |
232 | |
233 | |
235 | |
ID code (hex) | 3 |
E8 | |
E9 | |
EB | |
System requirements | |
Engineering tool | PC Worx |
Diagnostics tool | DIAG+ from version 1.14 |
Local diagnostics | BA, RC, RD, TR Higher-level network LED |
FC RUN, SYSFAIL IEC 61131 runtime system LED | |
RDY/RUN, BSA, FAIL, PF INTERBUS master LED | |
Transmission medium | Copper |
Maximum power dissipation for nominal condition | max. 3.25 W |
Supply | |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC |
Power supply connection | 8-pos. Inline connector |
Max. total permissible current consumption of all I/O terminal blocks | Communications power (7,5 V DC) ≤ 2 A DC |
Analog supply (24 V DC) ≤ 0.5 A | |
Residual ripple | ± 5 % |
Typical current consumption | 153 mA (no local bus device connected during idling, bus inactive) |
Potentials | |
Supply voltage | 7.5 V DC ±5 % |
Potentials | |
Supply voltage | 24 V DC -15 % / +20 % |
Potentials | |
Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
Potentials | |
Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
Current draw | max. 2 A |
Digital: | |
Input name | Digital inputs |
Description of the input | Interrupt input, fast counter, pulse generator |
Number of inputs | 4 |
Connection method | Inline potential distributor |
Connection technology | 2-, 3-, 4-conductor |
Input voltage | 2 x 24 V DC + 2 x 5/24 V DC |
Typical input current per channel | 40 mA |
Typical response time | < 1 ms |
Counter: | |
Number of inputs | 4 |
Input frequency | 40 kHz |
Digital: | |
Output name | Digital outputs |
Connection method | Spring-cage connection |
Connection technology | 2-, 3-, 4-conductor |
Number of outputs | 2 |
Output voltage | 24 V DC |
Maximum output current per channel | 500 mA |
Pulse direction | |
Number of pulse direction outputs | 2 |
Limit frequency | 20 kHz |
Inline connector | |
Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
INTERBUS local bus (master) | |
Number of interfaces | 1 |
Connection method | Inline data jumper |
Transmission speed | 500 kBaud / 2 MBaud (can be switched) |
Higher-level INTERBUS remote bus (slave) | |
Connection method | Inline shield connector |
Transmission speed | 500 kBaud |
No. of channels | 1 |
Parameterization/operation/diagnostics | |
Bus system | RS-232 |
Number of interfaces | 1 |
Connection method | 6-pos. MINI DIN socket (PS/2) |
Transmission speed | 19200 Baud |
Transmission physics | Copper |
Dimensional drawing |
|
Width | 109.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Color | green (RAL 6021) |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 75 °C |
Permissible humidity (operation) | 5 % ... 85 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 85 % (non-condensing) |
Shock | 25g, Criterion 1, according to IEC 60068-2-27 |
Vibration (operation) | 2g, criterion 1 according to IEC 60068-2-6 |
Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Mounting type | DIN rail mounting |
Item number | 2729800 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product key | DRAAAB |
GTIN | 4017918185992 |
Weight per piece (including packing) | 387 g |
Weight per piece (excluding packing) | 342.4 g |
Country of origin | DE |
ETIM
ETIM 8.0 | EC000236 |
UNSPSC
UNSPSC 21.0 | 32151700 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
Compatible products
-
-
COM CAB MINI DIN - Connecting cable 2400127
-
IBS OPC SERVER - Programming software 2729127
-
PC WORX BASIC LIC - Programming software 2985275
-
PC WORX PRO LIC - Programming software 2985385
-
ILC IB-PLSET - Connector set 2729622
-
IB IL FIELD 2 - Marking field 2727501
-
AX+ BASIC - Software 2985068
-
AX DTM LIB - Programming software 2988065
Your advantages
Fast inputs for interrupt processing, event counting, and period measurement
24 V high-speed outputs for pulse width modulation