You can connect this Axioline E device to an IO-Link master via an IO-Link A port. It is used to acquire analog voltage and current signals. Use within different networks is possible via the IO-Link master.
AXL E IOL AI4 M12 3M
-
Analog module
1743420
Axioline E, Analog input device, Analog inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-, 3-, 4-conductor, IO-Link, degree of protection: IP65/IP67/IP69
Free download available.
Downloads
Product details
| Dimensional drawing |
|
| Width | 30 mm |
| Height | 184 mm |
| Depth | 30.3 mm |
| Note on application | |
| Note on application | Only for industrial use |
| Color (Housing) | zinc color |
| Housing material | Die-cast zinc |
| Analog: | |
| Input name | Analog inputs |
| Description of the input | Differential inputs, voltage or current can be chosen separately |
| Number of inputs | 4 |
| A/D conversion time | 31.25 µs |
| Connection method | M12 connector, A-coded |
| Connection technology | 2-, 3-, 4-conductor |
| Note regarding the connection technology | shielded |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| -20 mA ... 20 mA | |
| Input resistance current input | typ. 106 Ω |
| Voltage input signal | 0 V ... 5 V |
| -5 V ... 5 V | |
| 0 V ... 10 V | |
| -10 V ... 10 V | |
| Input resistance of voltage input | typ. 280 kΩ |
| A/D converter resolution | 16 bit |
| Data formats | Standardized representation |
| Input filter | 30 Hz and mean value generation (can be parameterized) |
| Measured value representation | 16 bits (15 bits + sign bit) |
| Protective circuit | Transient protection |
| Overload protection | |
| IO-Link | |
| Number of ports | 1 |
| Connection method | M12 connector, A-coded |
| Note on the connection method | Push-pull fast connection according to IEC 61076-2-010 or screw connection according to IEC 61076-2-101 |
| Connection technology | 3-conductor |
| Port type | Class A |
| Specification | V1.1.4 |
| Reverse polarity protection | yes |
| Transmission speed | 230.4 kbps (COM3) |
| Cycle Time | 2 ms |
| Amount of process data | 8 Byte (Input data) |
| 0 Byte (Output data) | |
| Product type | I/O component |
| Product family | Axioline E |
| Type | Stand-alone |
| Special properties | IO-Link |
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Supply: IO-Link | |
| Designation | IO-Link port supply (L+) |
| Nominal voltage for I/O supply | 24 V DC (Provided via the IO-Link interface of the IO-Link master.) |
| Supply voltage range | 18 V DC ... 30 V DC (including all tolerances, including ripple) |
| Nominal current per device | typ. 44 mA |
| Current consumption | max. 59 mA (IiS = 0 mA) |
| max. 139 mA (IiS = 4 x 20 mA (nominal load)) | |
| max. 859 mA (IiS = 4 x 200 mA (full load)) | |
| Observe the current of the IO-Link master that is made available via L+. | |
| Protective circuit | Reverse polarity protection; yes |
| Supply: Sensors | |
| Designation | Sensor supply UiS |
| Supply voltage | 24 V DC (from L+) |
| Current consumption | max. 200 mA (per channel) |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 24 V supply L+ (IO-Link)/functional ground | 500 V AC, 50 Hz, 1 min |
| Test voltage: 24 V supply L+ (IO-Link)/analog inputs | 500 V AC, 50 Hz, 1 min |
| Test voltage: Analog inputs / functional ground | 500 V AC, 50 Hz, 1 min |
| Connection method | M12 connector |
| Tightening torque | 0.4 Nm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 70 °C |
| Degree of protection | IP65/IP67/IP69 |
| IK08 (Impact resistance level) | |
| Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Permissible humidity (storage/transport) | 75 % (non-condensing) |
| Mechanical test | |
| Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6 | 5g |
| Shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 30g |
| Continuous shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 10g |
| Test (noxious gas) | |
| Test standard | IEC 60068-2-60:2015 Method 4 |
| Temperature | 25 °C ±1 K |
| Humidity (relative) | 75 % ±3 % |
| Test duration | 14 Days |
| Volume concentration H2S (Hydrogen sulfide) | 10 ppb ±5 ppb |
| Volume concentration NO2 (Nitrogen dioxide) | 200 ppb ±20 ppb |
| Volume concentration Cl2 (Chlorine) | 10 ppb ±5 ppb |
| Volume concentration SO2 (Sulfur dioxide) | 200 ppb ±20 ppb |
| Test (Salt spray) | |
| Test standard | DIN EN 60068-2-52 |
| Number of cycles | 4 |
| Test steps per cycle | 2 |
| Test duration (Total) | 168 h |
| Test step (Salt mist) | 2 h with 5 % ±0.5 % NaCl, pH value 6.5...7.2 for 35 °C ±2 K |
| Test step (Humidity) | 166 h with 93 % ±3 % Humidity for 40 °C ±2 K |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | Screw mounting |
| Item number | 1743420 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Product key | DRI7MF |
| GTIN | 4067923308459 |
| Weight per piece (including packing) | 299.2 g |
| Weight per piece (excluding packing) | 272 g |
| Country of origin | Information on the country of origin is provided with the delivery. |
ECLASS
| ECLASS-13.0 | 27242601 |
| ECLASS-15.0 | 27242601 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 7(a), 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
Compatible products
-
-
US-EMLP-HA (20X9) - Plastic label 0830989
-
US-EML (20X8) - Label 0800458
-
PROT-M12 - Screw plug 1680539
-
PROT-M12 SH - Screw plug 1503302
-
SAC-3P-Y/2XM 8FS SCO - Y distributor 1523984
-
SAC-3P-Y/2XFS PE SCO - Y distributor 1523971
-
SAC-3P-Y/2XFS B PE SCO - Y distributor 1523968
-
SAC-5P-P12MS/ 1,5-PUR/P12FS SH - Sensor/actuator cable 1224249
-
SAC-5P-P12MR/ 1,5-PUR/P12FS SH - Sensor/actuator cable 1224256
-
SAC-5P-P12MS/ 1,5-PUR/P12FR SH - Sensor/actuator cable 1224252
-
SAC-5P-P12MR/ 1,5-PUR SH - Sensor/actuator cable 1476899
-
SAC-5P-P12MS/ 1,5-PUR SH - Sensor/actuator cable 1476903
-
SAC-5P-M12MS/ 1,5-PUR SH - Sensor/actuator cable 1682728
-
SAC-5P-M12MS/ 1,5-PUR/M12FS SH - Sensor/actuator cable 1500907
-
SAC-5P-M12MS/ 1,5-PUR/M12FR SH - Sensor/actuator cable 1501045
-
SACC-P12MS-4PL-CM SH - Connector 1438165
-
SACC-P12MS-5PL-CM SH - Connector 1438175
-
SACC-P12MR-5PL-CM SH - Connector 1438179
-
SACC-P12MR-4PL-CM SH - Connector 1438168
-
SACC-M12MS-5PL SH - Connector 1424658
-
SACC-M12MS-4PL SH - Connector 1424666
-
SACC-P12FS-4PL-CM M - Connector 1438151
-
SACC-P12FR-4PL-CM M - Connector 1438155
-
SACC-P12FR-5PL-CM M - Connector 1438162
-
SACC-P12FS-5PL-CM M - Connector 1438159
-
SACC-M12FS-5PL M - Connector 1424652
-
SACC-M12FS-4PL M - Connector 1424655
-
SAC BIT M12-D15 - Tool 1208432
-
SACC BIT M12-D20 - Tool 1208445
-
TSD 04 SAC - Torque screwdriver 1208429
-
NF PD IOL R - Inductive coupler 1736165
-
NF PD IOL B - Inductive coupler 1736167
Your advantages
Connection to an IO-Link master with M12 connector (A-coded, 4-pos.)
Type A port
IO-Link specification V1.1.4
Connection of up to 4 inputs with M12 connectors (A-coded, 4-pos.)
Connection of sensors in 2-, 3-, and 4-conductor technology
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Diagnostic and status indicators
Device rating plate stored
IP65/IP67/IP69 degree of protection