PT 2X1VA- 60AC-ST
-
Surge protection plug
2839172
Protective plug PT with protective circuit for higher signal voltages, 2-channel, visual error display. Nominal voltage: 60 V AC
This product needs further products for operation.
Mandatory accessories
Product details
General | |
Note | Technical data is valid in association with the following specified base elements: |
PT -BE/ FM 2839282 |
Product type | Surge protection for MCR technology |
Product family | PLUGTRAB PT |
IEC test classification | C1 |
C2 | |
C3 | |
D1 | |
Type | Male |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Nominal voltage UN | 60 V AC |
Indicator/remote signaling | |
Switching function | N/C contact |
Connection method | Screw connection (in connection with the base element) |
Screw thread | M3 |
Tightening torque | 0.5 Nm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensional drawing |
|
Width | 17.5 mm |
Height | 44.8 mm |
Depth | 51.7 mm |
Horizontal pitch | 1 Div. |
Complete module width | 17.7 mm |
Complete module height | 90 mm |
Complete module depth | 65.5 mm |
Color | black (RAL 9005) |
copper color | |
Flammability rating according to UL 94 | V-0 |
Housing material | PA 6.6 |
Mechanical data | |
Open side panel | No |
Direction of action | Line-Line & Line-Earth Ground |
Maximum continuous voltage UC | 100 V DC |
75 V AC (50/60 Hz) | |
Rated current | 26 A AC (30 °C) |
3 A DC (78 °C) | |
Operating effective current IC at UC | ≤ 1.5 mA AC |
≤ 3 mA DC | |
Residual current IPE | ≤ 3 mA AC |
≤ 6 mA DC | |
Nominal discharge current In (8/20) µs (line-ground) | 2 kA |
Pulse discharge current Iimp (10/350) µs | 500 A |
Total discharge current ITotal (8/20) µs | 4 kA |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 200 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 200 V |
Voltage protection level Up (line-earth) | ≤ 250 V (C1 - 1.4 kV / 0.7 kA) |
≤ 300 V (C2 - 4 kV / 2 kA) | |
≤ 220 V (C3 - 100 A) | |
Response time tA (line-earth) | ≤ 25 ns |
Input attenuation aE, asym. | typ. 0.3 dB (≤ 150 kHz / 150 Ω) |
Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω system | typ. 600 kHz |
Capacity (Core-Earth) | typ. 4 nF |
Surge protection fault message | optical |
Max. required back-up fuse | 25 A AC (gL/gG) |
3 A DC (T) | |
Impulse durability (line-earth) | C1 - 1,4 kV / 0,7 kA |
C2 - 4 kV / 2 kA | |
C3 - 100 A | |
D1 - 500 A |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (amsl) |
Standards/specifications | IEC 61643 |
Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
Standards/specifications | EN 61643-21 |
Note | 2001 + A1:2009 + A2:2013 |
Mounting type | on base element |
Item number | 2839172 |
Packing unit | 10 pc |
Minimum order quantity | 1 pc |
Product key | CL2111 |
Catalog page | Page 138 (C-4-2019) |
GTIN | 4017918182830 |
Weight per piece (including packing) | 26.3 g |
Weight per piece (excluding packing) | 23.19 g |
Customs tariff number | 85363010 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27171501 |
ETIM
ETIM 9.0 | EC000943 |
UNSPSC
UNSPSC 21.0 | 39121600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | cf9c391a-a063-4d17-88e7-c8c271ee8d7a |
Compatible products
-
ZBF 5:UNBEDRUCKT - Zack Marker strip, flat 0808642
-
ZBF 5/WH-100:UNBEDRUCKT - Zack Marker strip, flat 0808668
-
ZBF 5,LGS:FORTL.ZAHLEN - Zack Marker strip, flat 0808671
-
ZBF 5,LGS:GERADE ZAHLEN - Zack Marker strip, flat 0810821
-
ZBF 5,LGS:UNGERADE ZAHLEN - Zack Marker strip, flat 0810863
-
ZBF 5,QR:FORTL.ZAHLEN - Zack Marker strip, flat 0808697
-
ZBN 18:UNBEDRUCKT - Zack marker strip 2809128
-
ZBN 18 CUS - Zack marker strip 0825059
-
SSA 3-6 - Shield connection 2839295
-
SSA 5-10 - Shield connection 2839512
-
X-PEN 0,35 - Marker pen 0811228
-
SZS 0,6X3,5 VDE - Screwdriver 1212602
Your advantages
Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
Maximum ease of maintenance, thanks to the 2-piece design
Easy selection for all possible demands in MCR applications with a complete product portfolio
The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
PHOENIX CONTACT Israel Ltd.
P.O.B. 1799 Industrial Park Hasharon
Kadima 60920