Voltage measuring transducers - MACX MCR-VAC
2906239

MACX MCR voltage transducer, for AC voltages from 0 V ... 20 V AC to 0 ... 660 V AC, output signal: 0 V ... 10 V/0(4) ... 20 mA


Product Details




Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Voltage transducer
Insulation characteristics
Pollution degree 2

Alignment span ± 20 %
Alignment zero ± 20 %
Frequency measuring range 45 Hz ... 405 Hz
Electrical isolation IEC 61010-2-30 (Measuring category II (1000 V)Measuring category III (600 V)Measuring category IV (300 V))
IEC 61010-1 (Overvoltage category III at 300 VOvervoltage category IV at 150 V)
Test voltage 5.3 kV AC (50 Hz, 60 s)
2.2 kV AC (50 Hz, 60 s)
Protective circuit Surge protection; 33 V suppressor diode
Step response (10-90%) < 180 ms
Maximum temperature coefficient < 0.015 %/K
Maximum transmission error < 1 % (from a measuring range final value, 45 ... 65 Hz)
< 1.3 % (from a measuring range final value, 65 ... 405 Hz)
Supply
Nominal supply voltage 24 V DC (-20 % ... +25 %)
Supply voltage range 19.2 V DC ... 30 V DC
Max. current consumption < 45 mA

Measurement
Configurable/programmable Yes
Input voltage range 0 V AC ... 550 V AC
Input resistance of voltage input 5500 kΩ
Maximum input voltage + 660 V AC
Impulse form AC voltage
Measurement
Input voltage range 0 V AC ... 370 V AC
Input resistance of voltage input 3700 kΩ
Measurement
Input voltage range 0 V AC ... 250 V AC
Input resistance of voltage input 2500 kΩ
Measurement
Input voltage range 0 V AC ... 170 V AC
Input resistance of voltage input 1700 kΩ
Measurement
Input voltage range 0 V AC ... 120 V AC
Input resistance of voltage input 1200 kΩ
Measurement
Input voltage range 0 V AC ... 80 V AC
Input resistance of voltage input 800 kΩ
Measurement
Input voltage range 0 V AC ... 54 V AC
Input resistance of voltage input 800 kΩ
Measurement
Input voltage range 0 V AC ... 36 V AC
Input resistance of voltage input 800 kΩ
Measurement
Input voltage range 0 V AC ... 24 V AC
Input resistance of voltage input 240 kΩ

Signal: Voltage
Output name Voltage output
Voltage output signal 0 V ... 10 V
2 V ... 10 V
Max. voltage output signal ≤ 11 V
Load/output load voltage output > 10 kΩ
Ripple 50 mV
Signal: Current
Output name Current output
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal ≤ 22 mA
Load/output load current output < 500 Ω
Max. capacitive load < 1000 pF
Max. inductive load < 1 mH

Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14

Width 22.5 mm
Height 113 mm
Depth 114 mm

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C (non-condensing)
Altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
UKCA
Certificate UKCA-compliant
UL, USA / Canada
Identification UL 61010 Listed

Low Voltage Directive Conformance with Low Voltage Directive
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Conducted interference
Frequency range 45 Hz ... 405 Hz

Standards/regulations IEC 61010-1
IEC 61010-2-030

Mounting type DIN rail mounting
Assembly instructions Can be aligned with spacing = 10 mm
Mounting position any

Item number 2906239
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C04
Product Key CK4B11
Catalog Page Page 238 (C-5-2019)
GTIN 4055626051000
Weight per Piece (including packing) 227.4 g
Weight per Piece (excluding packing) 211 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210125
ECLASS-10.0.1 27210125
ECLASS-11.0 27210125

ETIM

ETIM 8.0 EC002477

UNSPSC

UNSPSC 21.0 39121000

EAC

Approval ID: RU*DE.*08.B.01852-19

UL Listed

Approval ID: FILE E 330267

cUL Listed

Approval ID: FILE E 330267

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Adjustable voltage ranges
Bidirectional output signals
3-way isolation
ZERO/SPAN adjustment ±20%
Tool-free parameterization of measured values
Teach-in configuration of the measured value range