Industrial Ethernet Switch - FL SWITCH 2316
2702909

Managed Switch 2000, 16 RJ45 ports 10/100/1000 Mbps, PROFINET Conformance-Class B

Downloads

Product Details




Dimensional drawing
Width 85 mm
Height 130 mm
Depth 115 mm

General Support by phone or on-site (fee is charged)
Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area
Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.

Housing material Polycarbonate fiber reinforced

Mounting type DIN rail

Ethernet (RJ45)
Connection method RJ45
Note on the connection method Auto negotiation and autocrossing
Transmission speed 10/100/1000 Mbps
Transmission physics Copper
Transmission length 100 m (per segment)
Signal LEDs Data receive, link status
No. of channels 16 (RJ45 ports)

Digital
Output name Alarm output

Type Book type
Product type Switch
MTTF 379.84 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
199.41 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
27.52 Years (SN 29500 standard, temperature 55°C, operating cycle 100%)
Signal delay ≥ 1.9 µs (Store-and-Forward mode, 10/100/1000 Mbps, depending on the frame size)
Insulation characteristics
Protection class III (VDE 0106)
Degree of pollution 2
Switch functions
Diagnostic functions RMON History
LLDP (Link Layer Discovery Protocol)
SNMP-Traps
N:1-Portmirroring
ACD (Address Conflict Detection)
SysLog
CRC-Surveillance
Basic functions Store-and-forward switch, complies with IEEE 802.3
Signal contact control voltage typ. 24 V DC
PROFINET conformance class Conformance-Class B
PROFINET device function PROFINET device
Fast Startup
Filter functions Quality of Service (8 priority classes)
Class of Service
DiffServ/DSCP
Port-Priorisierung
VLAN (up to 32 VLANs)
IGMP Snooping/Querier (v1/v2)
Auto-Query-Port
Extended Multicast Filtering
IP parameterization DHCP-Client
DHCP Option 82 (Relay Agent)
DHCP server (pool-based, port-based)
BootP
DCP (Discovery and Configuration Protocol)
MAC address table 8k
Management Web-based management (HTTP/HTTPS)
Role-based user management (LDAP, RADIUS)
SNMPv1/v2/v3
Command-line interface (Telnet, SSH)
Redundancy MRP (Media Redundancy Protocol)
RSTP (Rapid Spanning Tree Protocol)
FRD (Fast Ring Detection)
Large Tree Support
LACP (Link Aggregation Control Protocol)
PROFINET S2 system redundancy
Status and diagnostic indicators LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed)
Additional functions Jumbo frames (max. 9,600 bytes)
Transmission of MMS and GOOSE (IEC 61850-8-1)
Transmission of Modbus/TCP
Time synchronization SNTP (Simple Network Time Protocol)
Security functions
Port security MAC-based, RADIUS (IEEE 802.1X), MAC Authentication Bypass
Basic functions Store-and-forward switch, complies with IEEE 802.3

Local diagnostics US1/2 Supply voltage US1, US2 Green LED
FAIL Div. LED red
LINK Link status Green LED
Maximum power dissipation for nominal condition 13.2 W (US = Min, Tamb = Max, DOI = Max)
Test voltage 500 V DC
Test section for one minute 500 V DC
Transmission medium Copper
Supply
Supply voltage 24 V DC (redundant)
Supply voltage range 12 V DC ... 57 V DC
Power supply connection via COMBICON, max. conductor cross section 1.5 mm²
Residual ripple 3.6 VPP (within the permitted voltage range)
Max. current consumption 1.8 A (US = Min, Tamb = Max, DOI = Max)
Typical current consumption 455 mA (at US = 24 V DC and 25 °C ambient temperature)
Current consumption 455 mA
Function
Signal contact control voltage typ. 24 V DC

Connection method Push-in spring connection
Note on the connection method Use only copper connecting cables providing the permitted temperature range (-40 °C ... 75 °C).
Conductor cross section, rigid 0.25 mm² ... 1.5 mm²
Conductor cross section, flexible 0.25 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 9 mm

Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Shock (operation) 30g (EN 60068-2-27)
Vibration (operation) in acc. with IEC 60068-2-6: 5g, 150 Hz
Air pressure (operation) 79 kPa ... 108 kPa up to 2000 m above mean sea level (Without derating)
Air pressure (storage/transport) 79 kPa ... 108 kPa up to 2000 m above mean sea level (Without derating)

Free from substances that could impair the application of coating Yes

Shipbuilding approval Tested in accordance with IEC 60945 and IACS E10
ATEX
Identification  II 3 G Ex ec IIC T4 Gc
Certificate DEMKO 16 ATEX 1709X
IECEx
Identification Ex ec IIC T4 Gc
Certificate IECEx ULD 16.0018 X
UL, USA / Canada
Identification cULus
UL Ex, USA / Canada
Identification Class I, Division 2, Groups A, B, C and D, T4
Class I, Zone 2, AEx ec IIC T4
Ex ec IIC T4 Gc X
Certificate E366272
Note UL 60079-0 Ed. 6 / UL 60079-7 Ed. 5, CSA 22.2 No. 60079-0 Ed. 3 / CSA C22.2 No. 60079-7 Ed. 2
EAC Ex
Identification 2Ex e IIC T4 Gc X
Certificate RU C-DE.HB49.B.00118/21
The following continue to apply for EAC Ex:
Identification При монтаже использовать походящий допущенный корпус со степенью защиты не ниже IP66.
На корпусе/шкафу управления должна быть размещена предупреждающаяя надпись, запрещающая открывать корпус или шкаф во взрывоопасной зоне.
Эксплуатация устройства допускается только при условии, что все оптические порты заняты подключенными устройствами или закрыты прилагаемыми заглушками.
CCC / China-Ex
Identification Ex nA IIC T4 Gc
Certificate 2022122310115629
Corrosive gas test
Identification ISA S71.04.2013 G3 Harsh Group A

Conformance with EMC directives EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B
EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion A
EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A
EN 61000-6-2 EN 61000-4-5 (surge) Criterion A
EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A
EN 61000-6-2 EN 61000-6-3 (noise emission) Class B
EN 61000-6-2 EN 61000-6-3 (conducted emissions) Class B
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2

Status display LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed)

Item number 2702909
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C23
Product Key DNN121
Catalog Page Page 307 (C-6-2019)
GTIN 4055626398723
Weight per Piece (including packing) 633.9 g
Weight per Piece (excluding packing) 435 g
Customs tariff number 85176200
Country of origin DE


ECLASS

ECLASS-9.0 19170106
ECLASS-10.0.1 19170401
ECLASS-11.0 19170401

ETIM

ETIM 8.0 EC000734

UNSPSC

UNSPSC 21.0

EAC

Approval ID: RU*-DE.*.B.00741/19

DNV GL

Approval ID: TAA00000YV

LR

Approval ID: LR2160176TA

NK

Approval ID: TA19464M

BV

Approval ID: 48146/A1 BV

UL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 238705

BSH

Approval ID: 1045

RINA

Approval ID: ELE162721XG

ABS

Approval ID: 21-2066186-PDA

CC-Link IE Field

Approval ID: Ref. No. 184

IECEx

Approval ID: IECEx ULD 16.0018X

cUL Listed

Approval ID: FILE E 366272

UL Listed

Approval ID: FILE E 366272

ATEX

Approval ID: DEMKO 16 ATEX 1709X

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Ambient temperature -40 °C ... 70 °C
MRP (client and manager)
RSTP
DHCP client, DHCP server (pool-based and port-based), DHCP option 82
VLANs
Configuration memory
Web-based management, SNMP
Easy and fast startup and commissioning with the FL NETWORK MANAGER software
Suitable for PROFINET and EtherNet/IP™ networks