Surge protection device - PT-IQ-2X2+F-24DC-UT
2800981

Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for two 2-wire floating signal circuits. Indirect grounding via gas discharge tube, HART-compatible.

This product needs further products for operation. Mandatory Accessories

Product Details




General
Note Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

IEC test classification C1
C2
C3
D1
Type DIN rail module, two-section, divisible
Product type Surge protection for MCR technology
Surge protection fault message Optical, multi-stage
Wire pairs per module 2
Insulation characteristics
Overvoltage category III
Pollution degree 2

Connection method Screw connection
Screw thread M3
Tightening torque 0.5 Nm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12

Dimensional drawing
Width 17.7 mm
Height 91 mm
Depth 77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch 1 Div.

Color jet black RAL 9005
Flammability rating according to UL 94 V-0
Housing material PA 6.6

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC 30 V DC
21 V AC
Rated current 700 mA (50 °C)
Operating effective current IC at UC ≤ 1 mA (in the signal circuit)
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line) 10 kA
Nominal discharge surge current In (8/20) µs (Core-Earth) 10 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 2.5 kA
Total discharge current Itotal (8/20) µs 20 kA
Voltage protection level Up (line-line) ≤ 80 V (C1 - 1 kV / 500 A)
≤ 130 V (C2 - 10 kV / 5 kA)
≤ 150 V (C2 - 10 kA)
≤ 55 V (C3 - 25 A)
≤ 60 V (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 900 V (C1 - 1 kV / 500 A)
≤ 1300 V (C2 - 10 kV / 5 kA)
≤ 1200 V (C2 - 10 kA)
≤ 1000 V (C3 - 25 A)
≤ 1300 V (C3 - 100 A)
Voltage protection level Up (line-signalground) ≤ 600 V (C1 - 1 kV / 500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 800 V (C2 - 10 kA)
≤ 700 V (C3 - 25 A)
≤ 800 V (C3 - 100 A)
Voltage protection level Up static (line-line) ≤ 65 V (C1 - 1 kV / 500 A)
≤ 65 V (C2 - 10 kA)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-earth) ≤ 100 ns
Response time tA (line-signalground) ≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 270 kHz/150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 1.1 MHz
Capacity (Core-Earth) typ. 2 nF
Resistance per path 1.2 Ω ±5 %
Surge protection fault message Optical, multi-stage
Max. required back-up fuse 800 mA (FF)
Impulse durability (line-line) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 100 A
Impulse durability (line-earth) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 100 A
D1 - 2.5 kA
Impulse durability (line-signalground) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 100 A
D1 - 2,5 kA
Pulse reset time (line-line) ≤ 4000 ms
Pulse reset time (line-earth) ≤ 30 ms
Pulse reset time (line-signalground) ≤ 2600 ms

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 4000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %

Standards/specifications IEC 61643-21
Standards/specifications EN 61643-21
Standards/specifications EN 61000-6-3
Standards/specifications EN 61000-6-2

Mounting type DIN rail: 35 mm

Item number 2800981
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Sales Key C07
Product Key CL2151
Catalog Page Page 121 (C-4-2019)
GTIN 4046356665810
Weight per Piece (including packing) 126.1 g
Weight per Piece (excluding packing) 121 g
Customs tariff number 85363010
Country of origin DE


ECLASS

ECLASS-9.0 27130807
ECLASS-10.0.1 27130807
ECLASS-11.0 27130807

ETIM

ETIM 8.0 EC000943

UNSPSC

UNSPSC 21.0 39121600

CSA

Approval ID: 2761632

EAC

Approval ID: RU C-DE.*09.B.00169

UL Listed

Approval ID: FILE E 138168

CSAus

Approval ID: 2761632

cCSAus


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Predictive monitoring with 3-stage LED display
Integration of the status message into the system controller via group remote signaling
Install quickly and error-free with DIN rail connectors
Maximum ease of maintenance, thanks to the 2-piece design
Maximum protection for MCR applications with high discharge capacity