Surge protection plug - PT 2X1VA-120AC-ST
2839185

Protective plug PT with protective circuit for higher signal voltages, 2-channel, visual error warning. Nominal voltage: 120 V AC

This product needs further products for operation. Mandatory Accessories

Product Details




General
Note Technical data is valid in association with the following specified base elements:
PT -BE/ FM 2839282

IEC test classification C1
C2
C3
D1
Type Male
Product type Surge protection for MCR technology
Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.00
Insulation characteristics
Overvoltage category III
Pollution degree 2

Supply: Status indicator/remote signaling
Operating voltage 250 V AC
Rated current 3 A

Connection method Screw connection (in connection with the base element)
Screw thread M3
Tightening torque 0.5 Nm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12

Dimensional drawing
Width 17.5 mm
Width 17.5 mm
Height 44.8 mm
Height 44.8 mm
Depth 51.7 mm
Depth 51.7 mm
Horizontal pitch 1 Div.
Complete module width 17.7 mm
Complete module height 90 mm
Complete module depth 65.5 mm

Color jet black RAL 9005
Flammability rating according to UL 94 V-0
Housing material PA 6.6

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Earth Ground
Maximum continuous voltage UC 150 V DC
150 V AC (50/60 Hz)
Rated current 26 A AC (30 °C)
1 A DC (82 °C)
Operating effective current IC at UC ≤ 1.5 mA AC
≤ 2 mA DC
Residual current IPE ≤ 3 mA AC
≤ 4 mA DC
Nominal discharge surge current In (8/20) µs (Core-Earth) 2.5 kA
Pulse discharge current Iimp (10/350) µs 500 A
Total discharge current Itotal (8/20) µs 5 kA
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 380 V
Output voltage limitation at 1 kV/µs (line-earth) static ≤ 380 V
Voltage protection level Up (line-earth) ≤ 450 V (C1 - 1.4 kV / 0.7 kA)
≤ 550 V (C2 - 5 kV/2,5 kA)
≤ 400 V (C3 - 100 A)
Response time tA (line-earth) ≤ 25 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω system typ. 1 MHz
Capacity (Core-Earth) typ. 2.5 nF
Surge protection fault message optical
Max. required back-up fuse 25 A AC (gL/gG)
1 A DC (T)
Impulse durability (line-earth) C1 - 1,4 kV / 0,7 kA
C2 - 5 kV / 2.5 kA
C3 - 100 A
D1 - 500 A

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m (amsl (above mean sea level))

Standards/specifications IEC 61643
Standards/specifications EN 61643-21

Mounting type on base element

Item number 2839185
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C07
Product Key CL2111
Catalog Page Page 138 (C-4-2019)
GTIN 4017918182847
Weight per Piece (including packing) 27.48 g
Weight per Piece (excluding packing) 23.623 g
Customs tariff number 85363010
Country of origin DE


ECLASS

ECLASS-9.0 27130807
ECLASS-10.0.1 27130807
ECLASS-11.0 27130807

ETIM

ETIM 8.0 EC000943

UNSPSC

UNSPSC 21.0 39121600

EAC

Approval ID: EAC-Zulassung

EAC

Approval ID: RU C-DE.*09.B.00169

UL Listed

Approval ID: FILE E 138168

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
Maximum ease of maintenance, thanks to the 2-piece design
Easy selection for all possible demands in MCR applications with a complete product portfolio
The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs