PLC-OPT- 24DC/ 24DC/10/R - Solid-state relay module
2900398

PLC-INTERFACE with confirmation contact, consisting of basic terminal block with push-in connection and integrated miniature solid-state relay, for mounting on DIN rail NS 35/7,5, 1 N/O contact, input: 24 V DC, output: 3 - 33 V DC/10 A


Product Details




Notes on operation The PLC-ATP partition plate must be installed for voltages greater than 250 V (L1, L2, L3) between identical terminal blocks on adjacent modules.
Notes on operation The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
Notes on operation Do not connect adjacent channels to SELV/ PELV and voltages dangerous to the touch.
Notes on operation The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Notes on operation At least one functional insulation against adjacent modules is complied with in the support rail direction.
If the application has higher requirements on the insulation (basic or reinforced insulation), then these must be realized through suitable measures (e. g., partition plates).
Notes on operation Do not use to separate SELV / PELV circuits from other circuits, because safe isolation is not guaranteed.

Product type Solid-state relay module
Product family PLC-INTERFACE
Application With integrated solid-state relay
Operating mode 100% operating factor
Insulation characteristics
Insulation Basic insulation
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation Basic insulation
Overvoltage category II
Pollution degree 2

Maximum power dissipation for nominal condition 0.07 W
Air clearances and creepage distances between the power circuits
Rated insulation voltage 50 V DC
Rated surge voltage 0.5 kV

Rated actuating voltage UC 24 V DC
Rated actuating current IC 3.5 mA
Switching threshold "0" signal in reference to UN < 0.4
Switching threshold "1" signal in reference to UN > 0.8
Typical response time 100 µs
Typical turn-off time 500 µs
Operating voltage display Yellow LED
Protective circuit Reverse polarity protection; Polarity protection diode
Surge protection
Surge voltage protection > 33 V
Transmission frequency 100 Hz

Designation DC voltage output
Contact type 1 N/O contact
Design of digital output electronic
Type of contact Power contact
Output voltage range 8 V DC ... 33 V DC
Limiting continuous current 10 A (see derating curve)
Quiescent current 5.2 mA
Voltage drop at max. limiting continuous current < 50 mV
Output circuit 3-conductor, ground-referenced
Protective circuit Inverse diode
Surge protection
Designation Alarm output
Output voltage range 3 V DC ... 33 V DC
Limiting continuous current 100 mA
Surge voltage protection > 33 V
Voltage drop at max. limiting continuous current < 1.2 V
Output circuit 2-conductor, floating
Error indication Red LED
Protective circuit Reverse polarity protection; Polarity protection diode
Surge protection; Suppressor diode

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG 26 ... 14

Width 6.2 mm
Height 80 mm
Depth 86 mm

Flammability rating according to UL 94 V0 (Housing)

Ambient conditions
Degree of protection IP20
Degree of protection (Installation location) IP54 (Installation location)
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m

Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN 60068-2-60

Air clearances and creepage distances between the power circuits
Standards/regulations IEC 60947-5-1

Mounting type DIN rail mounting
Assembly instructions in rows with zero spacing
Mounting position any

Item number 2900398
Packing unit 1 pc
Minimum order quantity 10 pc
Sales Key C05
Product Key CK6233
Catalog Page Page 409 (C-5-2019)
GTIN 4046356506960
Weight per Piece (including packing) 32.48 g
Weight per Piece (excluding packing) 32.4 g
Customs tariff number 85364190
Country of origin DE


ECLASS

ECLASS-9.0 27371604
ECLASS-10.0.1 27371604
ECLASS-11.0 27371604

ETIM

ETIM 8.0 EC001504

UNSPSC

UNSPSC 21.0 39122300

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

EAC

Approval ID: TR_TS_D_00573_c

UL Listed

Approval ID: FILE E 172140

cUL Listed

Approval ID: FILE E 172140

DNV GL

Approval ID: TAE0000196
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products



Your advantages

Resistant to vibrations and shocks
Wear-free switching with no contact bounce
Protective circuit in input and output
Status indicator
DC voltage outputs up to 24 V DC/10 A
Option of bridging adjacent modules