Differential current monitoring - EV-RCM-6DC-WAT-X10
1309695

The residual current monitoring module is used for AC and DC residual current detection in AC charging points. The higher-level safety equipment (e.g., residual current device) is protected against potential DC residual currents.


Product Details




Product type Residual current monitoring module
Application Residual current monitoring module for detecting AC and DC residual voltages in 50/60 Hz AC installations
Type 1-channel
Manufacturer Western Automation
Manufacturer Designation RCM14-03
Charging standard Type 2
Charging mode Mode 3

Type of charging current AC
Power consumption min. 60 mW
Measuring current transducer
Diameter of measuring coil 14 mm
Measuring range: Residual current
Residual current IΔn 30 mA (AC)
6 mA (DC)
Rated current In 100 A (1-phase)
40 A (3-phase)
Supply
Supply voltage range 10.8 V DC ... 13.2 V DC (nominal voltage range)
Nominal power consumption 60 mW
Frequency range 50 Hz ... 60 Hz

Conductor connection
Connection method Pin strip 4-pos.
Conductor cross section AWG 26

Number of interfaces 2 (Error/Test)

Charging controllers
Number of charging points 1

Width 60.7 mm
Height 33.6 mm
Depth 32.50 mm

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C

Conformity/Approvals
Conformance CE-compliant

Standards
Standards/regulations IEC 62955

Mounting position any

Item number 1309695
Packing unit 1 pc
Minimum order quantity 10 pc
Sales Key A17
Product Key XWBBFK
GTIN 4063151560867
Weight per Piece (including packing) 22.22 g
Weight per Piece (excluding packing) 46.4 g
Customs tariff number 85437090
Country of origin CN


ECLASS

ECLASS-11.0 27144703

ETIM

ETIM 8.0 EC002889

UNSPSC

UNSPSC 21.0 39121800