Type 1/2 surge protection plug - VAL-EV-T1/T2 264/12.5-P
1180148

CHARX protect: replacement plug for surge protective devices from the VALVETRAB EV-T1/T2 product range for the L-N path.


Product Details




IEC test classification I / II
T1 / T2
EN type T1 / T2
IEC power supply system TN-S
TT
Type DIN rail module, two-section, divisible
Product type Replacement plug
Surge protection fault message optical
Insulation characteristics
Overvoltage category III
Pollution degree 2

Nominal frequency fN 50 Hz (60 Hz)

Connection method pluggable

Dimensional drawing
Width 17.5 mm
Height 47.2 mm
Depth 63.9 mm
Horizontal pitch 1 Div.

Color light grey RAL 7035
Flammability rating according to UL 94 V-0
CTI value of material 600
Insulating material PA 6.6/PBT
Material group I
Housing material PA 6.6
PBT

Mode of protection L-N
Direction of action L-N / L-PEN
Nominal voltage UN 240/415 V AC (TN-C, TN-S)
240/415 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous voltage UC 264 V AC
Residual current IPE ≤ 800 µA
Standby power consumption PC ≤ 270 mVA
Nominal discharge current In (8/20) µs 12.5 kA
Maximum discharge current Imax (8/20) µs 50 kA
Impulse discharge current (10/350) µs, charge 6.25 As
Impulse discharge current (10/350) µs, specific energy 39 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp 12.5 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up ≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20 µs)
Residual voltage Ures ≤ 1.2 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
TOV behavior at UT 415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
Response time tA ≤ 25 ns
Max. backup fuse with branch wiring 160 A (gG)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

Standards/specifications IEC 61643-11
Standards/specifications EN 61643-11

Mounting type on base element

Item number 1180148
Packing unit 10 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Product Key CL1151
GTIN 4063151215538
Weight per Piece (including packing) 112.7 g
Weight per Piece (excluding packing) 107.34 g
Customs tariff number 85363090
Country of origin DE


ECLASS

ECLASS-9.0 27130890
ECLASS-11.0 27130890

ETIM

ETIM 8.0 EC002496

UNSPSC

UNSPSC 21.0 39121600

KEMA-KEUR

Approval ID: 71-113415

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Your advantages

Uninterrupted continuation of the charging process with a protected power supply
Additional protection for the connected electric vehicle
High system availability, thanks to a high-performance protective circuit
Easy insulation measurement and simple replacement during servicing with consistently pluggable protective devices
No mismatching of plugs, thanks to mechanical coding