PLC-RPT- 24UC/21/MS - Relay Module
2909668

PLC-INTERFACE, consisting of PLC-BPT.../21 basic terminal block with Push-in connection and plug-in miniature relay with power contact and manual operation, 1 changeover contact, 24 V AC/DC input voltage


Product Details





Notes on operation Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500....
Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Relay Module
Product family PLC-INTERFACE
Application Palm switch
Operating mode 100% operating factor
Mechanical service life 1x 107 cycles
Insulation characteristics: Standards/regulations
Overvoltage category III
Pollution degree 3

Maximum power dissipation for nominal condition 0.26 W
Test voltage (Winding/contact) 4 kV AC (50 Hz, 1 min., winding/contact)

Coil side
Nominal input voltage UN 24 V AC/DC
Input voltage range 19.4 V AC/DC ... 33.6 V AC/DC (20 °C)
Typical input current at UN 11 mA (at UN = 24 V AC)
8.5 mA (at UN = 24 V DC)
Typical response time 6 ms
Typical release time 15 ms
Protective circuit Bridge rectifier; Bridge rectifier
Operating voltage display Yellow LED

Switching
Contact type 1 changeover contact
Type of switch contact Single contact
Drive and function monostable
Drive (polarity) bipolar
Contact material AgSnO
Maximum switching voltage 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage 5 V (at 100 mA)
Limiting continuous current 6 A
Maximum inrush current 10 A (4 s)
Min. switching current 10 mA (12 V)
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
20 W (at 48 V DC)
18 W (at 60 V DC)
23 W (at 110 V DC)
40 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.1 A (at 220 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15)

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG 26 ... 14

Width 6.2 mm
Height 80 mm
Depth 94 mm

Flammability rating according to UL 94 V0 (Housing)

Ambient conditions
Degree of protection Relay RT II (Relay)
IP20 (Relay base)
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C

CE
Certificate CE-compliant
Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN 60068-2-60

Standards/regulations
Standards/regulations IEC 60664
IEC 60664A
DIN VDE 0110
DIN EN 50178/VDE 0160 (in relevant parts)
DIN EN 50178/VDE 0160
IEC 60255/DIN VDE 0435 (in relevant parts)

Mounting type DIN rail mounting
Assembly instructions in rows with zero spacing
Mounting position any

Item number 2909668
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C05
Product Key CK623A
Catalog Page Page 365 (C-5-2019)
GTIN 4055626378015
Weight per Piece (including packing) 37.62 g
Weight per Piece (excluding packing) 31.27 g
Customs tariff number 85364190
Country of origin DE


ECLASS

ECLASS-9.0 27371601
ECLASS-10.0.1 27371601
ECLASS-11.0 27371601
ECLASS-12.0 27371601
ECLASS-13.0 27371601

ETIM

ETIM 8.0 EC001437

UNSPSC

UNSPSC 21.0 39122300

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

EAC

Approval ID: TR_TS_D_00573_c

DNV GL

Approval ID: TAE0000196
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

EAC

Approval ID: RU*C-DE.*08.B.00010

UL Listed

Approval ID: FILE E 172140

cUL Listed

Approval ID: FILE E 172140

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
Hexahydromethylphthalic anhydride
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products



Your advantages

Slim design
Efficient connection to system cabling using V8 adapter
RT III sealed relay
Safe isolation according to DIN EN 50178 between coil and contact
Functional plug-in bridges
Integrated input circuit and interference suppression circuit