EM-CPS-PS/3AC/24DC/5 - Power supply unit
1064922

Primary-switched power supply unit TRIO POWER, Snap-on connection, Cross Power System - installation, input: 3-phase, output: 24 V DC / 5 A


Product Details


The TRIO CROSS POWER power supply for the CrossPowerSystem power distribution board is perfectly adapted for use in machine building. All of the functions and space-saving design are tailored to the high requirements in this area. The push-in connection enables quick and easy connection of a 24 V DC control voltage.



AC operation
Network type Star network
Nominal input voltage range 3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC
Input voltage range 3x 400 V AC ... 500 V AC -20 % ... +15 %
2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range AC 3x 320 V AC ... 575 V AC
Typical national grid voltage 3x 400 V AC
3x 480 V AC
Voltage type of supply voltage AC
Inrush current integral (I2t) ≤ 0.25 A2s
Inrush current limitation ≤ 22 A
AC frequency range 50 Hz ... 60 Hz
Mains buffering time typ. 20 ms (400 V AC)
typ. 20 ms (500 V AC)
Current consumption 3x 0.4 A (400 V AC)
3x 0.3 A (500 V AC)
2x 0.6 A (400 V AC)
2x 0.5 A (500 V AC)
Nominal power consumption 243.6 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.55
Typical response time < 1 s
Input fuse 3.15 A (internal (device protection), slow-blow)
Discharge current to PE < 0.25 mA
< (550 V AC, 60 Hz)

Efficiency typ. 91 % (400 V AC)
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A
Dynamic Boost (IDyn.Boost) 7.5 A (5 s)
Derating > 60 °C ... 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple ≤ 20 mVPP
Short-circuit-proof yes
No-load proof yes
Output power 120 W
180 W
Maximum no-load power dissipation < 1 W (400 V AC)
Power loss nominal load max. < 12 W (480 V AC)
Rise time ≤ 120 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK
Continuous load current 100 mA
Signal relay 13/14
Default closed
Digital 30 V AC 30 V DC 100 mA

Input
Connection method Snap-on connection
Output
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Signal
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min. 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

Types of signaling LED
Floating signal contact
Signal output: LED status indicator
Signalization designation DC OK
Status display LED
Color green
DC OK UOUT > 0.9 x UN (UN = 24 V DC)
UOUT > 0.9 x UN (UN = 24 V DC)

Number of phases 3.00
Insulation voltage input/output 3 kV AC (type test)
1.5 kV AC (routine test)

Product type Power supply
Product family TRIO POWER
MTBF (IEC 61709, SN 29500) > 2300000 h (25 °C)
> 1300000 h (40 °C)
> 620000 h (60 °C)
Insulation characteristics
Protection class II (in closed control cabinet)
Degree of pollution 2

Width 36 mm
Height 160 mm
Depth 159 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance right/left (active) 14 mm / 14 mm
Installation distance top/bottom 50 mm / 50 mm
Installation distance top/bottom (active) 50 mm / 50 mm

Mounting type Cross Power System - installation
Assembly instructions Cross Power System
With protective coating No

Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Plastic
Type of housing Polycarbonate
Hood version Polycarbonate

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) 10 ... 150 Hz, amplitude ±0.35 mm, 5g, 90 min. (in accordance with IEC 60068-2-6)
2 Hz ... 15 Hz, amplitude ±1 mm, > 15 Hz, 0.7g (in accordance with DNV GL Class A)

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety IEC 61010-1 (SELV)
Standard – Safety extra-low voltage IEC 61010 (SELV) / (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Overvoltage category
EN 61010-1 II

UL approvals UL Listed UL 61010-2-201
Conformity/Approvals
SIL in accordance with IEC 61508 0

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise immunity EN 61000-6-2
Conducted noise emission EN 55016
EN 61000-6-4 (Class A)
Interference emission Interference emission in accordance with EN 61000-6-2 (industrial)
Noise emission EN 55011 (EN 55022)
Noise emission EN 55016
EN 61000-6-4 (Class A)
Noise immunity Immunity in accordance with EN 61000-6-2 (industrial)
Harmonic currents
Frequency range Class A, B
Flicker
Frequency range 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 6 kV (Test Level 4)
Discharge in air 8 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Input 3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Signal 1 kV (Test Level 1 - symmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-6-2
Voltage dips
Standards/regulations EN 61000-4-11
Voltage 230 V AC
Frequency 50 Hz
Voltage dip 70 %
Number of periods 25 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 40 %
Number of periods 10 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 0 %
Number of periods 1 period
Additional text Test Level 2
Comments Criterion A
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Item number 1064922
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key 00
Product Key CMPO33
Catalog Page Page 262 (C-4-2019)
GTIN 4055626725222
Weight per Piece (including packing) 781.6 g
Weight per Piece (excluding packing) 510 g
Customs tariff number 85044083
Country of origin CN


ECLASS

ECLASS-9.0 27040701
ECLASS-10.0.1 27040701
ECLASS-11.0 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0 39121000

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

EAC

Approval ID: RU S-DE.BL08.W.00764

EAC

Approval ID: RU S-DE.BL08.W.00764

cUL Listed

Approval ID: FILE E 123528

UL Listed

Approval ID: FILE E 123528

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products



Your advantages

Push-in connections for easy 24 V DC control voltage connection
Fast startup: Tool-free mounting and automatic contacting in just one step (CrossPowerSystem)
Reliable startup of high loads, thanks to the dynamic boost
Electrically robust, thanks to high electric strength
Maximum flexibility, thanks to the temperature range of -25°C … +70°C and device startup at -40°C