Power terminal block - MINI MCR-SL-PTB
2864134

MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw connection, maximum current consumption of up to 2 A


Product Details


The 6.2 mm wide MINI MCR-SL-PTB... power terminal is used for supplying the DIN rail connector with supply voltage.
Two separate voltage inputs allow a redundant voltage supply of 24 V DC and a maximum current of 2 A.
A green LED on the front panel lights up when there is supply voltage on the DIN rail connector. Red LEDs indicate supply voltages connected with reversed polarity. When the supply voltage has been connected correctly, the red LED extinguishes.



Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Power module

Input voltage range DC 20 V DC ... 30 V DC
Max. input current 2 A
Reverse polarity protection yes

Output voltage range Input voltage - 0.8 V

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Stripping length 12 mm
Screw thread M3

Status display Green LED (supply)
Indication Red LED

Dimensional drawing
Width 6.2 mm
Height 93.1 mm
Depth 102.5 mm

Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Designation CE
Certificate CE-compliant
CE
Designation UKCA
Certificate UKCA-compliant
CE
Designation UL, USA / Canada
Identification UL 508 Listed
CE
Designation Shipbuilding approval
Certificate DNV GL TAA000020N
DNV GL data
Temperature B
Humidity B
Vibration B
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Evaluation criterion A
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Evaluation criterion B
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Comments Criterion B
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Evaluation criterion A

Mounting type DIN rail mounting
Assembly instructions The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position any

Item number 2864134
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C01
Product Key CK12ZZ
Catalog Page Page 118 (C-7-2015)
GTIN 4017918974770
Weight per Piece (including packing) 86.8 g
Weight per Piece (excluding packing) 69.5 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27379201
ECLASS-10.0.1 27371392
ECLASS-11.0 27371392

ETIM

ETIM 8.0 EC002498

UNSPSC

UNSPSC 21.0 39121100

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

DNV GL

Approval ID: TAA00002R0

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

For supplying the supply voltage via the foot element (DIN rail connector) where DC voltages of up to 30 V are already available
Status and error indication via diagnostic LEDs