Bus coupler - IL EIP BK DI8 DO4 2TX-PAC
2897758

Inline, Bus coupler, EtherNet/IP™, RJ45 jack, Digital inputs: 8, 24 V DC, connection technology: 3-conductor, Digital outputs: 4, 24 V DC, connection technology: 3-conductor, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields

Downloads

Product Details


The bus coupler with integrated I/Os is intended for use within an EtherNet/IP™ network and represents the link to the Inline I/O system. Up to 61 Inline devices can be connected to the bus coupler. The bus coupler supports a maximum of 8 PCP devices. A corresponding EDS file is available for integrating the Inline station into the programming system. This file can be downloaded via the product at phoenixcontact.net/products.



Dimensional drawing
Width 80 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Specfications with connectors

Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.

Color green

EtherNet/IP™
No. of channels 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Permissible conductor cross section 0.14 mm² ... 0.22 mm² (twisted pair)
Transmission speed 10/100 Mbps (half or full duplex (automatic detection))
Transmission physics Ethernet in RJ45 twisted pair
Inline local bus
Connection method Inline data jumper
Transmission speed 500 kbps / 2 Mbps (automatic detection, no combined system)
Fieldbus: Local bus gateway
Max. number of local bus devices 61 (The on-board I/Os are two devices)
EtherNet/IP™
No. of channels 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Permissible conductor cross section 0.14 mm² ... 0.22 mm² (twisted pair)
Transmission speed 10/100 Mbps (half or full duplex (automatic detection))
Transmission physics Ethernet in RJ45 twisted pair
Inline local bus
Connection method Inline data jumper
Transmission speed 500 kbps / 2 Mbps (automatic detection, no combined system)

System limits
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 61 (The on-board I/Os are two devices)
Number of devices with parameter channel max. 8
Number of supported branch terminals with remote bus branch 0
Module
ID code (hex) none

Digital
Input name Digital inputs
Description of the input EN 61131-2 type 1
Number of inputs 8
Connection method Inline connector
Connection technology 3-conductor
Input voltage 24 V DC
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Nominal input voltage UIN 24 V DC
Nominal input current at UIN typ. 3 mA
Typical input current per channel typ. 3 mA
Typical response time approx. 500 µs
Delay at signal change from 0 to 1 1.2 ms
Delay at signal change from 1 to 0 1.2 ms
Protective circuit Reverse polarity protection; Suppressor diode

Digital
Output name Digital outputs
Connection method Inline connector
Connection technology 3-conductor
Number of outputs 4
Protective circuit Short-circuit and overload protection; Free running circuit
Output voltage 24 V DC -1 V (At nominal current)
Maximum output current per module max. 2 A
Nominal output voltage 24 V DC
Output current when switched off max. 10 µA (When not loaded, a voltage can be measured even at an output that is not set.)
Nominal load, inductive 12 VA (1.2 H, 48 Ω)
Nominal load, lamp 12 W
Nominal load, ohmic 12 W
Reverse voltage resistance to short pulses Reverse voltage proof
Behavior with overload Auto restart
Behavior with inductive overload Output can be destroyed
Behavior at voltage switch-off The output follows the power supply without delay

Type modular
Product type I/O component
Scope of delivery including Inline connectors and marking fields
No. of channels 12
Diagnostics messages Short-circuit or overload of the digital outputs Yes
Sensor supply failure Yes
Failure of the actuator supply Yes

No. of channels 12
Maximum power dissipation for nominal condition 23.5 W
Power dissipation typ. 1.7 W (entire device)
Potentials
Power consumption typ. 3 W (entire device)
Protective circuit Short-circuit protection of the communications power; electronic
Short-circuit protection of the analog supply; electronic
Potentials: Bus coupler supply UBK; Communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from the bus coupler supply.
Supply voltage 24 V DC (via Inline connector)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 0.98 A (with max. number of connected I/O terminal blocks)
80 mA (without connected I/O terminal blocks)
Potentials: Communications power (UL)
Supply voltage 7.5 V DC
max. 0.8 A DC
Potentials: Supply of analog modules (UANA)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
max. 0.5 A DC
Potentials: Main circuit supply (UM)
Supply voltage 24 V DC (via Inline connector)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
max. 8 A DC (sum of UM + US)
Current draw max. 8 A DC
min. 3 mA (without connected peripherals)
Potentials: Segment circuit supply (US)
Supply voltage 24 V DC (via Inline connector)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
max. 8 A DC (sum of UM + US)
Current draw max. 8 A DC
min. 6 mA (without connected peripherals)

Connection technology
Connection name Inline connector
Conductor connection
Connection method Spring-cage connection
Conductor cross section solid 0.08 mm² ... 1.5 mm²
Conductor cross section flexible 0.08 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Stripping length 8 mm
Inline connector
Connection method Spring-cage connection
Conductor cross section, rigid 0.08 mm² ... 1.5 mm²
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail mounting

Item number 2897758
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C21
Product Key DRI11D
Catalog Page Page 103 (C-6-2019)
GTIN 4046356157926
Weight per Piece (including packing) 347.78 g
Weight per Piece (excluding packing) 320 g
Customs tariff number 85176200
Country of origin DE


ECLASS

ECLASS-9.0 27242608
ECLASS-10.0.1 27242608
ECLASS-11.0 27242608

ETIM

ETIM 8.0 EC001604

UNSPSC

UNSPSC 21.0 32151600

cUL Recognized

Approval ID: FILE E 140324

UL Recognized

Approval ID: FILE E 140324

UL Recognized

Approval ID: FILE E 140324

cUL Recognized

Approval ID: FILE E 140324

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cUL Listed

Approval ID: FILE E 199827

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Your advantages

8 digital inputs, 4 digital outputs (on-board)
EtherNet/IP™, Version 1.2
Web-based management
2 RJ45 connections
Automatic detection of the transmission speed in the local bus (500 kbps or 2 Mbps)