General
Note LABS release – in accordance with test specification VW PV 3.10.7:2005-0
When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules.

Product type Device circuit breakers
Product family CAPAROC
Number of slots 1
Insulation characteristics
Protection class III
Pollution degree 2

General
Operating voltage 0 V DC ... 30 V DC
Rated voltage 12 V DC
24 V DC
Rated current IN 10 A DC (per output)
40 A DC (Total)
Rated surge voltage 0.5 kV
Efficiency > 99 %
Power dissipation < 0.4 W (in nominal operation at 24 V and 4 x 10 A)
MTBF (IEC 61709, SN 29500) 269532625 h (at 25 °C with 21 % load)
269532334.5 h (at 40°C with 34.25% load)
269530881.5 h (at 60°C with 100% load)
Voltage drop 9.7 mV (at 10 A)

Load circuit
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section flexible 0.2 mm² ... 4 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve 0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 4 mm²

Dimensional drawing
Width 6.2 mm
Height 132.4 mm
Depth 109.9 mm (incl. DIN rail 7.5 mm)

Color light grey RAL 7035
Material PA 6
PA 6
PA 6
Flammability rating according to UL 94 V-0

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -30 °C ... 65 °C (The temperature range of the power module must be taken into consideration)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Altitude ≤ 4000 m (amsl (above mean sea level))
Humidity test 96 h, 95 % RH, 40 °C
Shock (operation) 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27)
25g (6 ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock)
Vibration (operation) 5g (10 ... 150 Hz / 10 cycles / axis / X, Y, Z)

UL approval
Identification UL/C-UL Listed UL 508
UL 121201 Class I, Division 2, Groups A, B, C, D, T4A

Standards/specifications EN 61000-6-2
Standards/specifications EN 61000-6-3
Standards/specifications EN 60068-2-78
Standards/specifications EN 50178
Standards/specifications EN 60068-2-6
Standards/specifications EN 60068-2-27

Mounting type pluggable onto CAPAROC CR… current rail

Item number 1110987
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C34
Product Key CLA23Z
GTIN 4063151029395
Weight per Piece (including packing) 79.3 g
Weight per Piece (excluding packing) 79.3 g
Customs tariff number 85363010
Country of origin DE


ECLASS

ECLASS-9.0 27141116
ECLASS-10.0.1 27140401
ECLASS-11.0 27140401
ECLASS-12.0 27140401

ETIM

ETIM 8.0 EC003538

UNSPSC

UNSPSC 21.0 39121400

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 483407

UL Listed

Approval ID: FILE E 483407

cULus Listed

cULus Listed



Your advantages

The benchmark that you can tailor with direct pairwise integration into the system alongside the circuit breaker module
Particularly easy operation for everyone with tool-free insertion without additional wiring effort
Exceptionally easy design-in with color-coded pushers for clear identification of the potentials