DC/DC converter, protective coating - QUINT-PS/60-72DC/24DC/10/CO
2905011

Primary-switched QUINT DC/DC converter with wide range input for DIN rail mounting with SFB (Selective Fuse Breaking) technology, input: 60-72 V DC, output 24 V DC / 10 A


Product Details


QUINT DC/DC converter with maximum functionality.
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation. QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore cost-effective system protection. In addition, the high system availability is ensured by preventive function monitoring which reports critical operating states before errors can occur.



DC operation
Nominal input voltage range 60 V DC ... 72 V DC
Input voltage range 42 V DC ... 96 V DC
Wide-range input yes
Input voltage range DC 42 V DC ... 96 V DC
Inrush current < 9 A (typical)
Inrush current integral (I2t) 0.64 A2s
Mains buffering time typ. 10 ms (60 V DC)
Current consumption 5.6 A (60 V DC)
4.7 A (72 V DC)
Reverse polarity protection ≤ 30 V DC
Protective circuit Transient surge protection; Varistor
Input fuse 10 A 150 V DC (internal (device protection))

Efficiency > 91 % (UIN 60 V DC / UOUT 24 V DC)
> 91 % (UIN 72 V DC / UOUT 24 V DC)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-40 °C ... 60 °C)
POWER BOOST (IBoost) 12.5 A (-40°C ... 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6
Derating 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation 18 A
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Output power 240 W
Peak switching voltages nominal load < 10 mVPP (20 MHz)
Maximum no-load power dissipation 4 W (UIN 60 V DC)
Power loss nominal load max. 24 W (UIN 60 V DC)
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Switching voltage range 18 V DC ... 24 V DC
Maximum inrush current < 20 mA (short-circuit-proof)
Signal: POWER BOOST, active
Output description IOUT < IN: High signal
Switching voltage range 18 V DC ... 24 V DC
Maximum inrush current < 20 mA (short-circuit-proof)
Signal: UIN OK, active
Output description UIN > 19.2 V: High signal
Switching voltage range 18 V DC ... 24 V DC
Maximum inrush current ≤ 20 mA (short-circuit-proof)
Signal: DC OK floating
Output description Relay
Output voltage ≤ 30 V AC/DC
Maximum inrush current ≤ 100 mA

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Types of signaling LED
Active switching output
Relay contact
Signal output: DC OK active
Status display "DC OK" LED green
Color green
Signal output: POWER BOOST, active
Status display "BOOST" LED yellow/IOUT > IN : LED on
Color yellow
Note on status display LED on
Signal output: UIN OK, active
Status display LED "UIN < 0.8 x UN V" yellow/UIN < 0.8 x UN V DC: LED on
Color yellow
Note on status display LED on
Signal output: DC OK floating
Note on status display UOUT > 0.9 x UN: Contact closed

Number of phases 1.00
Insulation voltage input/output 1.5 kV (type test)
1 kV (routine test)
Insulation voltage input/output 1 kV (type test)

Product type DC/DC converters
MTBF (IEC 61709, SN 29500) > 1349000 h (25 °C)
> 765000 h (40 °C)
Insulation characteristics
Protection class I
Degree of pollution 2

Width 48 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm (≤ 70 °C)
Installation distance right/left (active) 15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom 50 mm / 50 mm (≤ 70 °C)
Installation distance top/bottom (active) 50 mm / 50 mm (≤ 70 °C)
Alternative assembly
Width 122 mm
Height 130 mm
Depth 51 mm

Mounting type DIN rail: 35 mm
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting position horizontal DIN rail NS 35, EN 60715
With protective coating yes

Housing material Metal
Type of housing Aluminum (AlMg3)
Hood version Galvanized sheet steel, free from chrome (VI)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) 100 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Rail applications EN 50121-4
EN 50155
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Noxious gas test ISA-S71.04-1985 G3 Harsh Group A

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz ... 2 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 9 kHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Item number 2905011
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C13
Product Key CMDQ43
Catalog Page Page 297 (C-4-2019)
GTIN 4046356908320
Weight per Piece (including packing) 1,166 g
Weight per Piece (excluding packing) 1,006.4 g
Customs tariff number 85044030
Country of origin CN


ECLASS

ECLASS-9.0 27210901
ECLASS-10.0.1 27210901
ECLASS-11.0 27040792

ETIM

ETIM 8.0 EC002046

UNSPSC

UNSPSC 21.0 39121000

cUL Recognized

Approval ID: FILE E 211944

UL Recognized

Approval ID: FILE E 211944

EAC

Approval ID: RU S-DE.BL08.W.00764

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

EAC

Approval ID: RU S-DE.BL08.W.00764

UL Recognized

Approval ID: FILE E 211944

cUL Recognized

Approval ID: FILE E 211944

cUL Listed

Approval ID: FILE E 123528

UL Listed

Approval ID: FILE E 123528

EAC

Approval ID: RU S-DE.BL08.W.00764

EAC

Approval ID: RU S-DE.BL08.W.00764

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cUL Listed

Approval ID: FILE E 199827

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Reliable starting of difficult loads, thanks to the static POWER BOOST power reserve with up to 125% nominal current permanently
Preventive function monitoring indicates critical operating states before errors occur
Constant voltage: output voltage regenerated even at the end of long cables
Support conversion to various voltage levels
Electrical isolation: for setting up independent supply systems
Optimum protection with dip coating for 100 % humidity