Controller - RFC 4072R
1136419

High-availability PLCnext controller with redundancy functionality


Product Details


High-availability PLCnext controller for PROFINET networks with S2 system redundancy functionality.
When it comes to high-availability, distributed, and modular automation, PLCnext controllers with IEC 61131 control intelligence, redundancy technology, and network connection are the ideal solution. Thanks to the integrated FO-based redundancy function, you can reduce system downtimes, work cost-effectively, and also avoid potential hazards. Virtual IP technology enables the easy and convenient connection of SCADA systems. The integrated OPC UA server/client function enables a cascaded topology of redundancy levels.



Type Stand-alone
Product type Controller
Insulation characteristics
Protection class III (IEC 61140, EN 61140, VDE 0140-1)
Display
Diagnostics display yes

Power consumption typ. 25 W (Without fan module)
max. 35 W (With fan module)
Transmission medium Copper
FO
Supply
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including ripple (3.6 VPP))
Power supply connection Via COMBICON, max. conductor cross section 2.5 mm²
Real-time clock
Realtime clock integrated (capacitive buffering)
Description realtime clock 1.73 s/day = 20 ppm at 25 °C
Potentials
Protective circuit Surge protection of the supply voltage; electronic
Polarity reversal protection of the supply voltage; electronic

COMBICON connector
Conductor cross section, rigid 0.2 mm² ... 2.5 mm²
Conductor cross section, flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 12

Web server yes
USB
Number of interfaces 1
Connection method USB type A, socket
Ethernet
Bus system RJ45
Number of interfaces 4
Connection method RJ45 jack
Note on the connection method Auto negotiation and auto crossing, auto polarity exchange
Transmission speed 10/100/1000 Mbps (LAN 1/LAN 2, half duplex or full duplex)
10/100 Mbps (LAN3.1/LAN3.2 (internally switched), half duplex or full duplex)

Processor Intel® Core™ i5-6300U 2x 2.4 GHz (Standard)
Flash memory 100 Mbyte (internal flash memory)
SD card from Phoenix Contact (for external flash memory, see accessories)
Retentive data storage 2 Mbyte
IEC 61131 runtime system
Program memory 16 Mbyte
Data storage 32 Mbyte
PROFINET
Device function PROFINET-Controller
Number of supported devices max. 256
Function
Diagnostics display yes
Controller redundancy yes
Safety function No

Functionality
Programming languages supported Instruction list (IL)
Symbolic flowchart (SFC)
Ladder diagram (LD)
Function block diagram (FBD)
Structured text (ST)
C++
C#
Java
Python
Simulink
System requirements
Engineering tool PLCnext Engineer
Eclipse
Visual Studio
MATLAB® Simulink®
Application interface OPC UA
OPC UA Pub/Sub

External dimensions
Width / Height / Depth 122 mm / 182 mm / 173 mm (without fan module)
122 mm / 220 mm / 173 mm (With fan module)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) 0 °C ... 60 °C up to 2000 m above mean sea level (recommended: above 50°C with fan module)
0 °C ... 55 °C 2000 m to 3000 m above mean sea level (With fan module only)
0 °C ... 50 °C 3000 m to 4000 m above mean sea level (With fan module only)
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Shock (operation) 20g (according to EN 60068-2-27/IEC 60068-2-27)
Vibration (operation) 1g (according to EN 60068-2-6/IEC 60068-2-6)
Air pressure (operation) 60 kPa ... 108 kPa (up to 4000 m above mean sea level)
Air pressure (storage/transport) 58 kPa ... 108 kPa (up to 4500 m above mean sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 Use of the device in these ambient conditions is prohibited.

Conformance with EMC directives Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B; Supply lines: 2 kV; Signal/data lines: 2 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines: 0.5 kV, signal/data cables: 1 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU

Mounting type DIN rail mounting

Item number 1136419
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Product Key DRADBA
GTIN 4063151072230
Weight per Piece (including packing) 3,062 g
Weight per Piece (excluding packing) 2,000 g
Customs tariff number 85371091
Country of origin DE


ECLASS

ECLASS-9.0 27242207
ECLASS-10.0.1 27242207
ECLASS-11.0 27242207

ETIM

ETIM 8.0 EC000236

UNSPSC

UNSPSC 21.0 32151700

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Fast startup and automatic configuration of all redundancy functions, thanks to AutoSync technology
Uninterrupted process in the event of failure or when a controller is replaced
Integrated PROFINET controller and PROFINET device
System networking M2M with OPC UA
A distance of up to 10 km between the controllers via fiber optics; cost-optimized thanks to plug-in SFP modules
Automatic switch-over of the visualization by using virtual IP technology
High-resolution display for displaying status and error messages in plain text
PROFINET standards ensure optimum device integration and S2 redundancy for your future-proof Ethernet network