EMC: class A product, see manufacturer's declaration in the download area
Utilization restriction
CCCex note
Use in potentially explosive areas is not permitted in China.
Product type
Extension module
MTTF
889 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
391 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
151 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
Insulation characteristics
Overvoltage category
II
Degree of pollution
2
Electrical isolation
300 V (Rated insulation voltage (in each case between the digital inputs // digital outputs // TBUS supply, reinforced insulation according to EN 61010))
50 V (Rated insulation voltage (in each case between the analog inputs / analog outputs / TBUS supply, reinforced insulation according to EN 61010))
300 V (Rated insulation voltage (in each case between the digital inputs and outputs and between the analog inputs and outputs, reinforced insulation according to EN 61010))
300 V (Rated insulation voltage (to adjacent devices, basic insulation in accordance with EN 61010))
Test voltage for digital I/Os
2.5 kV AC (50 Hz, 1 min.)
Test voltage for analog I/Os
1.5 kV AC (50 Hz, 1 min.)
Maximum power dissipation for nominal condition
2.28 W
Transient surge protection
Yes
Supply voltage range
19.2 V DC ... 30.5 V DC (DIN rail connector)
Max. current consumption
≤ 95 mA (At 24 V DC, at 25°C)
Max. current consumption
< 1 mA
Analog
Description of the input
Analog input
Number of inputs
1
Current input signal
0 mA ... 20 mA (can be set via DIP switches)
4 mA ... 20 mA (can be set via DIP switches)
Max. current input signal
22 mA
Input resistance current input
< 70 Ω
Resolution
16 bit
Precision
≤ 0.02 % (at 25 °C)
Protective circuit
Short-circuit and overload protection
Temperature coefficient, typical
typ. 0.0025 %/K (at -40 °C ... +70 °C)
Supply voltage
≥ 12 V DC (For passive sensors (via terminal PWR1, +I1))
Digital
Description of the input
Digital input
Number of inputs
2
Min. voltage input signal
0 V AC/DC
Max. voltage input signal
250 V AC/DC
Switching level "0" signal
0 V AC/DC ... 4 V AC/DC (Low-voltage input)
0 V AC/DC ... 20 V AC/DC (High-voltage input)
Switching level "1" signal
10 V AC/DC ... 50 V AC/DC (Low-voltage input)
50 V AC/DC ... 250 V AC/DC (High-voltage input)
Input frequency
≤ 2 Hz
Output name
Relay output
Number of outputs
2
Contact type
Changeover contact
Contact material
AgSnO2
Maximum switching voltage
250 V AC/DC
Min. switching current
≥ 10 mA
Max. switching current
2 A (per channel)
Mechanical service life
1x 107 cycles
Electrical service life
2x 105 cycles (At 2 A, 250 V AC, cosφ 0.4)
2x 105 cycles (At 1 A, 24 V DC, L/R = 48 ms)
Maximum switching frequency
2 Hz
Switching capacity
120 W (24 V DC)
120 W (30 V DC)
20 W (48 V DC)
18 W (60 V DC)
22 W (110 V DC)
40 W (220 V DC)
42 W (250 V DC)
1250 VA
Behavior of the outputs (adjustable via DIP switch)
Hold / Reset
Output name
Analog output
Number of outputs
1
Voltage output signal
0 V ... 10 V
Max. voltage output signal
approx. 10.83 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal
approx. 21.67 mA
Load
≥ 10 kΩ
≤ 500 Ω
Resolution
16 bit
Precision
≤ 0.02 % (at 25 °C)
typ. 0.5 % (Voltage output)
Temperature coefficient, typical
typ. 0.0025 %/K (at -40 °C ... +70 °C)
Protective circuit
Transient protection of outputs
Connection method
Screw connection
Stripping length
7 mm
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Status display
Green LED (supply voltage, PWR)
Green LED (bus communication, DAT)
Red LED (periphery error, ERR)
Yellow LED (digital input, DI1)
Yellow LED (digital input, DI2)
Yellow LED (digital output, DO1)
Yellow LED (digital output, DO2)
Dimensional drawing
Width
17.5 mm
Height
113 mm
Depth
114.5 mm
Color
green
Flammability rating according to UL 94
V0
Housing material
PA 6.6-FR
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 70 °C (>55°C derating)
-40 °F ... 158 °F (>131°F derating)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
-40 °F ... 185 °F
Altitude
2000 m
Permissible humidity (operation)
20 % ... 85 %
Permissible humidity (storage/transport)
20 % ... 85 %
Shock
16g, 11 ms
Vibration (operation)
in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
CE
Designation
CE
Certificate
CE-compliant
CE
Designation
EAC
Identification
EAC
CE
Designation
ATEX
Identification
II 3 G Ex nA nC IIC T4 Gc
Certificate
IBExU 15 ATEX B008 X
Note
Please follow the special installation instructions in the documentation!
CE
Designation
IECEx
Identification
Ex nA nC IIC T4 Gc
Certificate
IECEx IBE 13.0019X
CE
Designation
EAC Ex
Identification
2Ex nA nC IIC T4 Gc X
Certificate
RU C-DE.HB49.B.00033/20
CE
Designation
UL, USA / Canada
Identification
508 Listed
Class I, Div. 2, Groups A, B, C, D T4A
Class I, Zone 2, IIC T4
CE
Designation
KC approval for South Korea
Certificate
R-R-PCK-2901533
CE
Designation
Corrosive gas test
Identification
ISA-S71.04-1985 G3 Harsh Group A
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Standards/specifications
EN 61000-6-2
Standards/specifications
EN 61000-6-4
Standards/specifications
EN 60079-0
Standards/specifications
EN-60079-15
Assembly instructions
on standard DIN rail NS 35 in accordance with EN 60715
Mounting position
any
Item number
2901533
Packing unit
1 pc
Minimum order quantity
1 pc
Sales Key
DNC61D
Product Key
DNC61D
Catalog Page
Page 380 (C-6-2019)
GTIN
4046356610216
Weight per Piece (including packing)
239.1 g
Weight per Piece (excluding packing)
230 g
Customs tariff number
85389090
Country of origin
DE
ECLASS
ECLASS-9.0
27242602
ECLASS-10.0.1
27242602
ECLASS-11.0
27242602
ETIM
ETIM 8.0
EC001597
UNSPSC
UNSPSC 21.0
32151600
UL Listed
Approval ID: FILE E 238705
cUL Listed
Approval ID: FILE E 238705
KC
Approval ID: R-R-PCK-2901533
EAC Ex
Approval ID: RU*HB49.B00033/20
IECEx
Approval ID: IECEx IBE 13.0019X
cUL Listed
Approval ID: FILE E 196811
UL Listed
Approval ID: FILE E 196811
ATEX
Approval ID: IBExU 15 ATEX B008 X
cULus Listed
cULus Listed
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”