CTM 1X2- 60DC
   - 
  Surge protection plug
    
      2838568
      
      
    
  
      LSA-PLUS plug (COMTRAB CTM) with protection for conductor pairs in floating signal circuits. Nominal voltage: 60 V DC
      This product needs further products for operation.
      Mandatory accessories
    
  Product details
| Product type | Surge protection for MCR technology | 
| Product family | COMTRAB | 
| IEC test classification | B2 | 
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Type | LSA-PLUS module | 
| Surge protection fault message | none | 
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 | 
| Wire pairs per module | 1 | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Nominal voltage UN | 60 V DC | 
| Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips | 
| Dimensional drawing |  | 
| Width | 9.4 mm | 
| Height | 21 mm | 
| Depth | 52.4 mm | 
| Color | black (RAL 9005) | 
| copper color | |
| Flammability rating according to UL 94 | V-0 | 
| Housing material | PA 6.6 | 
| Mechanical data | |
| Open side panel | No | 
| Direction of action | Line-Line & Line-Earth Ground | 
| Maximum continuous operating voltage UC | 60 V DC | 
| 50 V AC | |
| Rated current | 380 mA AC (25 °C) | 
| 150 mA DC (25 °C) | |
| Operating effective current IC at UC | ≤ 70 µA | 
| Protective conductor current IPE | ≤ 2 µA | 
| Nominal discharge current In (8/20) µs (line-line) | 5 kA | 
| Nominal discharge current In (8/20) µs (line-ground) | 5 kA | 
| Pulse discharge current Iimp (10/350) µs (line-earth) | 1 kA | 
| Total discharge current ITotal (8/20) µs | 10 kA | 
| Total discharge current ITotal (10/350) µs | 2.5 kA | 
| Nominal pulse current Ian (10/1000) µs (line-line) | 100 A | 
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A | 
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 160 V | 
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V | 
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V | 
| Residual voltage at In (conductor-conductor) | ≤ 95 V | 
| Residual voltage at In (conductor-ground) | ≤ 60 V | 
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 35 V | 
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 12 V | 
| Voltage protection level Up (line-line) | ≤ 200 V (C2 - 10 kV / 5 kA) | 
| ≤ 160 V (C3 - 100 A) | |
| Voltage protection level Up (line-earth) | ≤ 700 V (C2 - 10 kV / 5 kA) | 
| ≤ 700 V (C3 - 100 A) | |
| Voltage protection level Up static (line-line) | ≤ 95 V (C2 - 10 kV / 5 kA) | 
| ≤ 35 V (C3 - 100 A) | |
| Voltage protection level Up static (line-earth) | ≤ 90 V (C2 - 10 kV / 5 kA) | 
| ≤ 12 V (C3 - 100 A) | |
| Response time tA (line-line) | ≤ 1 ns | 
| Response time tA (line-earth) | ≤ 100 ns | 
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 500 kHz / 100 Ω) | 
| Cut-off frequency fg (3 dB), sym. in 100 Ω system | typ. 2 MHz | 
| Capacity (Core-Core) | typ. 1.2 nF | 
| Resistance per path | 3.3 Ω 20 % | 
| Surge protection fault message | none | 
| Impulse durability (line-line) | B2 - 4 kV / 100 A | 
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| Impulse durability (line-earth) | B2 - 4 kV / 100 A | 
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -25 °C ... 75 °C | 
| Altitude | ≤ 2000 m (amsl) | 
| Standards/specifications | IEC 61643-21 | 
| Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 | 
| Standards/specifications | EN 61643-21 | 
| Note | 2001 + A1:2009 + A2:2013 | 
| Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip | 
| Item number | 2838568 | 
| Packing unit | 10 pc | 
| Minimum order quantity | 1 pc | 
| Product key | CL3211 | 
| GTIN | 4017918819736 | 
| Weight per piece (including packing) | 8.9 g | 
| Weight per piece (excluding packing) | 8.9 g | 
| Customs tariff number | 85363010 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27171501 | 
| ECLASS-15.0 | 27171501 | 
ETIM
| ETIM 9.0 | EC000943 | 
UNSPSC
| UNSPSC 21.0 | 39121600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
| EF3.0 Climate Change | |
| CO2e kg | 1.725 kg CO2e | 
Compatible products
Your advantages
Space-saving due to compact design
        Flexible fields of application with modular protective plug
        Can be used in LSA-PLUS disconnect and control strips or CT-TERMIBLOCK via adapted connection technology
        PHOENIX CONTACT Israel Ltd.
        P.O.B. 1799 Industrial Park Hasharon
        Kadima 60920