AXL F SSDOR4/2 1F
   - 
  Safety module
    
      2702859
      
      
    
  
      Axioline F, Functional safety, Signal inputs: 2, Outputs OUT24V_0 and OUT24V_1: 2, Safe relay outputs: 4 (floating), N/O contact, degree of protection: IP20
      Free download available.
      Downloads
    
  Product details
| Dimensional drawing |  | 
| Width | 53.6 mm | 
| Height | 126.1 mm | 
| Depth | 54 mm | 
| Note on dimensions | Housing dimensions | 
| Note on application | |
| Note on application | Only for industrial use | 
| Axioline F local bus | |
| Connection method | Bus base module | 
| Module | |
| Input address area | 8 Byte | 
| Output address area | 8 Byte | 
| Required parameter data | 1 Byte | 
| Required configuration data | 7 Byte | 
| Digital: | |
| Input name | Signal inputs | 
| Number of inputs | 2 | 
| Input voltage | Power supply from clock outputs UT1 and UT2 | 
| Nominal input current at UIN | typ. 3.2 mA | 
| Digital: | |
| Output name | Outputs OUT24V_0 and OUT24V_1 | 
| Number of outputs | 2 | 
| Nominal output voltage | Power supply from U0 or U1 | 
| Relay | |
| Number of outputs | 4 (floating) | 
| Contact switching type | N/O contact | 
| Switching voltage | min. 12 V AC/DC | 
| max. 30 V AC/DC | |
| Switching current | min. 3 mA | 
| max. 6 A (30 V DC) | |
| Switching power | min. 60 mW | 
| Limiting continuous current | 6 A | 
| Mechanical service life | 10x 106 cycles | 
| Output fuse | 6 A gL/gG (See “Application examples” section) | 
| Product type | I/O component | 
| Product family | Axioline F | 
| Application | Functional safety | 
| Type | modular | 
| Mounting position | any | 
| Operating mode | SafetyBridge | 
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1) | 
| Pollution degree | 2 (IEC 60664-1) | 
| Transmission medium | Copper | 
| Potentials | |
| Protection | max. 500 mA slow-blow (for UI) | 
| max. 6 A gL/gG (For U0 and U1 respectively) | |
| Protective circuit | Polarity reversal protection of the supply voltage; parallel protection against polarity reversal for a limited period of time | 
| Surge voltage detection; at 31 V | |
| Undervoltage detection; at 17 V | |
| Surge protection of the supply voltage; electronic (35 V, 0.5 s) | |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) | 
| Current draw | max. 163 mA (at UBus 5 V DC) | 
| typ. 93 mA (at UBus 5 V DC) | |
| Potentials: Supply voltage UI for EDM | |
| Supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30.2 V DC (including all tolerances, including ripple) | 
| Current draw | max. 30 mA | 
| typ. 10 mA (Power supply from UI with 30 V DC, all inputs set) | |
| Potentials: Feed-in U0 and U1 for safe I/O supply | |
| Supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Current draw | max. 6 A | 
| typ. 1.6 mA (Power supply from U0 with 30 V DC, all inputs set without load) | |
| Connection technology | |
| Connection name | I/O | 
| Note on the connection method | Note the specification in the section Conductor cross-sections, and stripping and insertion lengths. | 
| Conductor connection | |
| Connection method | Push-in connection | 
| Conductor cross-section rigid | 0.5 mm² ... 1.5 mm² | 
| Conductor cross-section flexible | 0.5 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 20 ... 16 | 
| Stripping length | 8 mm | 
| I/O | |
| Connection method | Push-in connection | 
| Note on the connection method | Note the specification in the section Conductor cross-sections, and stripping and insertion lengths. | 
| Conductor cross-section, rigid | 0.5 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible | 0.5 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 20 ... 16 | 
| Stripping length | 8 mm | 
| Ambient conditions | |
| Ambient temperature (operation) | -35 °C ... 60 °C | 
| Degree of protection | IP20 | 
| Degree of protection at installation location | min. IP54 | 
| Air pressure (operation) | 70 kPa ... 108 kPa | 
| Air pressure (storage/transport) | 66 kPa ... 108 kPa | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Protection class | III (IEC 61140-1) | 
| Air clearances and creepage distances | |
| Air clearances and creepage distances | IEC 60664-1 | 
| Mounting type | DIN rail mounting | 
| Mounting position | any | 
| Item number | 2702859 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DNA532 | 
| GTIN | 4055626363295 | 
| Weight per piece (including packing) | 270 g | 
| Weight per piece (excluding packing) | 218 g | 
| Customs tariff number | 85371098 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27242604 | 
| ECLASS-15.0 | 27242604 | 
| ECLASS-15.0 ASSET | 27250101 | 
ETIM
| ETIM 9.0 | EC001599 | 
UNSPSC
| UNSPSC 21.0 | 32151600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | 8db25eb2-3768-4936-8194-eb49c94e7f73 | 
Compatible products
Frequently searched
PHOENIX CONTACT Israel Ltd.
        P.O.B. 1799 Industrial Park Hasharon
        Kadima 60920