1) Mount screw connection flange in the housing using the correct torque 2) Insert cable 3) Tighten union nut using the correct torque
Method 1 Cut the outer sheath, but do not remove it. Feed the cable through the screw connection and then remove the outer sheath. Now pull the cable back until the connection is established between the cable shield and the contact spring.
Method 2 Push the braided shield back around 15 ... 20 mm over the outer sheath. Insert the cables into the screw connection until the connection is established between the cable shield and the contact spring.
Cable structure
External cable diameter
18 mm ... 25 mm
Ambient conditions
Halogen-free
no
Shielded
yes
Cable diameter without cable sheath
16 mm (Diameter of braided shield)
Dimensional drawing
Dimensional drawing
Hole diameter
37.1 mm ... 37.4 mm
Length of the connecting thread
8 mm
Wrench size, union nut
40 mm
Length
47 mm
Hexagon angular dimension
44.5 mm
Thread type connection side
Pg29
Wrench size, support
40 mm
Ambient temperature (operation)
-40 °C ... 100 °C (static)
Degree of protection
IP68
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”