CAPAROC E4 12-24DC/1-10A
-
Electronic circuit breaker
1115658
Four-channel electronic circuit breaker module for protecting 12 and 24 V DC loads against overload and short circuit. Nominal current adjustable from 1 A to 10 A via LED button. For DIN rail installation via the CAPAROC current rails.
This product needs further products for operation.
Mandatory accessories
Product details
General | |
Note | LABS release – in accordance with test specification VW PV 3.10.7:2005-0 |
When using CAPAROC E1... modules, for continuous shock in accordance with IEC 60068-2-27 the 6 ms / 15g degree of severity applies |
Product type | Device circuit breakers |
Product family | CAPAROC |
Number of positions | 1 |
No. of channels | 4 |
Number of slots | 2 |
Insulation characteristics | |
Protection class | III |
Pollution degree | 2 |
General | |
Operating voltage | 10 V DC ... 30 V DC |
Rated voltage | 12 V DC |
24 V DC | |
Rated current IN | 10 A DC (per channel) |
Rated current IN | 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 A DC (adjustable per output channel) |
Rated current (pre-adjusted) | 4 A |
Rated surge voltage | 0.5 kV |
Tripping method | E (electronic) |
Feedback resistance | max. 35 V DC |
Switch-on delay | 50 ms (each channel preset by default) |
can be adapted with CAPAROC PM IOL and CAPAROC PM PN power modules | |
Required backup fuse | Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. |
Short-circuit switching capacity | 300 A |
Dielectric strength | 35 V DC (Load circuit) |
Fuse | electronic |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 20 mA (no load at 24 V) |
Power dissipation | typ. 0.48 W (no load at 24 V) |
< 6 W (in nominal operation at 24 V and 10 A) | |
Waiting time after switch off of a channel | 5 s (at overload / short circuit) |
Measuring tolerance I | ± 10 % (typ.) |
Temperature derating | 16 A (Total current at 65 °C) |
40 A (Total current at 25°C) | |
MTBF (IEC 61709, SN 29500) | 6325945.91 h (at 25 °C with 21 % load) |
1812525.02 h (at 40°C with 34.25% load) | |
365459.81 h (at 25°C with 100% load) | |
Voltage drop | 0.14 V (at 10 A) |
Fail-safe element | 15 A DC (per output channel) |
Contact switching type | without electrical isolation |
Load circuit | |
Shutdown time | 4 s (with overload 1.1…1.5 x IN) |
1 s (with overload 1.5…2.0 x IN) | |
0.1 s (with overload 2.0…3.0 x IN) | |
≤ 10 ms (For short circuit > 3.0 x IN) | |
Undervoltage switch-off | ≤ 8.5 V DC (active) |
≥ 9.2 V DC (inactive) | |
Overvoltage switch-off | ≥ 32.5 V DC (active) |
≤ 30.5 V DC (inactive) | |
Max. capacitive load | ≤ 25000 µF (Depending on the current setting and the short-circuit current available) |
Fuse-protected output | |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section flexible | 0.2 mm² ... 4 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 4 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 4 mm² |
Channel LED off | off (Channel switched off) |
Channel LED yellow | lit (Channel switched on, channel load > 80% ) |
flashing (Programming mode active) | |
two flashes (Check the installation, no communication to power module) | |
Channel LED green | lit (Channel switched on) |
Channel LED red | lit (Channel switched off, over- or undervoltage active) |
ON temporarily (Channel switched off, 5 s cool-down phase, overload or short-circuit release) | |
flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) | |
two flashes (Channel switched off, system total current limit exceeded) | |
Channel LED red-yellow | flashing (Channel switched on, overload mode, capacity approximately 110 ... 150%, shutdown after 5 s) |
Channel LED red-green | flashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release) |
Dimensional drawing | |
Width | 12.4 mm |
Height | 132.4 mm |
Depth | 111.3 mm (incl. DIN rail 7.5 mm) |
Color | light gray (RAL 7035) |
Material | PA 6 |
PA 6 | |
PA 6 | |
PC | |
Flammability rating according to UL 94 | V-0 |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -30 °C ... 65 °C (The temperature range of the power module must be taken into consideration) |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Altitude | ≤ 4000 m (amsl) |
Humidity test | 96 h, 95 % RH, 40 °C |
Shock (operation) | 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) |
25g (6 ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock) | |
Vibration (operation) | 5g (10 ... 150 Hz / 10 cycles / axis / X, Y, Z) |
UL approval | |
Identification | UL/C-UL Listed UL 508 |
UL Recognized UL 2367 | |
Corrosive gas test | |
Identification | ISA S71.04.2013 G3 Harsh Group A |
Standards/specifications | EN 61000-6-2 |
Note | EMC – Immunity for industrial areas |
Standards/specifications | EN 61000-6-3 |
Note | EMC – Emission for residential, business and commercial properties and small operations |
Standards/specifications | EN 60068-2-78 |
Note | Environmental influences – Moisture and heat, constant |
Standards/specifications | EN 50178 |
Note | Equipping power installations with electronic equipment |
Standards/specifications | EN 60068-2-6 |
Note | Environmental influences – Vibrations (sinusoidal) |
Standards/specifications | EN 60068-2-27 |
Note | Environmental influences – Shocks |
Mounting type | pluggable onto CAPAROC CR… current rail |
Item number | 1115658 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product key | CLA234 |
GTIN | 4063151040192 |
Weight per piece (including packing) | 94.2 g |
Weight per piece (excluding packing) | 86.4 g |
Customs tariff number | 85363010 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27140401 |
ECLASS-12.0 | 27140401 |
ECLASS-13.0 | 27140401 |
ETIM
ETIM 9.0 | EC003538 |
UNSPSC
UNSPSC 21.0 | 39121400 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 93998b27-cb53-4fbc-98ab-c831cf83cb3d |
Compatible products
-
CAPAROC PD 0V - Potential distributors 1110987
-
UC-TMF 6 - Marker for terminal blocks 0818140
-
UCT-TMF 6 - Marker for terminal blocks 0828746
-
UC-TM 12 - Marker for terminal blocks 0819194
-
UCT-TM 12 - Marker for terminal blocks 0829144
-
CAPAROC CR EXT20 - Busbar 1115674
-
CAPAROC CR EXT8 - Busbar 1110990
-
CAPAROC CR EXT4 - Busbar 1110991
-
CAPAROC CR CON - Metal part 1270955
Your advantages
The benchmark that you can tailor with the individual combination of multi-channel protective modules
Easy operation for everyone through tool-free assembly, uninterrupted installation, and transparent operating state
Exceptionally easy design-in with four separately fused channels with the narrowest of space requirements of just 3 mm per channel
PHOENIX CONTACT Israel Ltd.
P.O.B. 1799 Industrial Park Hasharon
Kadima 60920