The module is designed for use within an Axioline F station. It has four floating relay N/O contacts which are independent of one another. Low-voltage and extra-low-voltage modules can be used side by side within an Axioline F station.
AXL F DOR4/2 AC/220DC 1F
-
Relay module
2700608
Axioline F, Relay module, Relay outputs: 4 (floating), N/O contact, 220 V DC, 230 V AC, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors; The product is being prepared for compliance with the Cyber Resilience Act (CRA).
Free download available.
Downloads
Product details
| Dimensional drawing |
|
| Width | 53.6 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Note on application | Only for industrial use |
| Note on application | As things stand now, we are preparing the product so that, as of December 11, 2027, it will comply with the requirements of the EU Cyber Resilience Act (CRA) based on the information currently available regarding the CRA. |
| Mounting type | DIN rail mounting |
| Mounting position | any (observe temperature and current derating) |
| Color (Housing) | gray (RAL 7042) |
| Axioline F local bus | |
| Number of interfaces | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Programming data | |
| Input address area | 0 Byte |
| Output address area | 1 Byte |
| Fieldbus data telegram (PROFIBUS) | |
| Required parameter data | 1 Byte |
| Required configuration data | 6 Byte |
| Relay | |
| Number of outputs | 4 (floating) |
| Connection method | Push-in connection |
| Connection technology | 2-conductor |
| Contact switching type | N/O contact |
| Contact material | AgSnO2 |
| Nominal output voltage (DC) | 220 V DC |
| Nominal output voltage (AC) | 230 V AC |
| Output voltage range (DC) | 24 V DC ... 220 V DC -20 % / +15 % |
| Output voltage range (AC) | 24 V AC ... 230 V AC -20 % / +15 % (50/60 Hz) |
| Output current (max. per channel) | max. 8 A (per channel, provide an external fuse) |
| Output current (max. per module) | max. 32 A (per module) |
| Inrush current | max. 15 A (for 4 s) |
| max. 65 A (for 0.02 s) | |
| Switching current | max. 8 A AC (cos phi = 1) |
| For DC see load limit curve, e.g., the following values: | |
| max. 8 A DC (≤ 30 V, ohmic load) | |
| max. 500 mA DC (110 V, ohmic load) | |
| max. 250 mA DC (220 V DC, ohmic load) | |
| max. 220 mA DC (125 V DC, L/R ≤ 50 ms, applications with UL approval) | |
| max. 110 mA DC (250 V DC, L/R ≤ 50 ms, applications with UL approval) | |
| Switching power | max. 2000 VA |
| For DC see load limit curve, e.g., the following values: | |
| max. 240 W (30 V DC) | |
| max. 55 W (≥ 60 V DC) | |
| max. 25 W (125 V DC, 250 V DC, applications with UL approval) | |
| Switching frequency | 0.1 Hz (with load) |
| 20 Hz (without load) | |
| Switching capacity in accordance with IEC 60947-5-1 | 6 A (120 V (AC15)) |
| 3 A (240 V (AC15)) | |
| 0.22 A (125 V (DC13)) | |
| 0.1 A (250 V (DC-13)) | |
| Switching frequency | max. 6 (per minute) |
| Typical response time | 10 ms |
| Bouncing time | 3 ms |
| Typical release time | < 5 ms |
| Service life electrical | 100000 switching cycles |
| Mechanical service life | 10x 106 cycles |
| Common potentials | all contacts floating |
| Product type | I/O component |
| Product family | Axioline F |
| Type | block modular |
| Mounting position | any (observe temperature and current derating) |
| Scope of supply | including bus base module and Axioline F connectors |
| Special properties | The product is being prepared for compliance with the Cyber Resilience Act (CRA) |
| Insulation characteristics | |
| Overvoltage category | III (EN 61010-2-201/UL 61010-2-201), up to 2000 m above sea level II (EN 61010-2-201/UL 61010-2-201), up to 3000 m above sea level |
| Pollution degree | 2 |
| Maximum power dissipation for nominal condition | 1.4 W |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Current draw | max. 280 mA (all relays pick up) |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Relay contact / logic | 4 kV |
| 5 kV | |
| Test voltage: Relay contact / functional ground | 4 kV |
| 5 kV | |
| Test voltage: Relay contact/relay contact (open contact) | 1 kV, 50 Hz, 1 min |
| Test voltage: Relay contact/relay contact (adjacent male connectors) | 2.5 kV |
| Connection technology | |
| Connection name | Axioline F connector |
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual. When selecting the cables, please note that in the case of a small conductor cross-section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| Axioline F connector | |
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual. When selecting the cables, please note that in the case of a small conductor cross-section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| Conductor cross-section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C (max. 6 A/channel for panel mounting on horizontal DIN rail; max. 4 A/channel for any mounting position) |
| -25 °C ... 50 °C (max. 8 A/channel for panel mounting on horizontal DIN rail; max. 6 A/channel for any mounting position) | |
| -25 °C ... 40 °C (max. 8 A/channel for any mounting position) | |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Mechanical test | |
| Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6 | 5g |
| Shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 20g (contact interruption) / 5g (contact closure) |
| Continuous shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 10g |
| Developed according to standard | Immunity to ESD |
| Immunity to EF | |
| Immunity to burst | |
| Immunity to surge | |
| Immunity to conducted interference | |
| Standard designation | Ambient conditions |
| Standards/specifications | IEC 61850-3 |
| Item number | 2700608 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales key | DR02 |
| Product key | DRI232 |
| GTIN | 4046356916486 |
| Weight per piece (including packing) | 255.7 g |
| Weight per piece (excluding packing) | 222 g |
| Customs tariff number | 85389091 |
| Country of origin | DE |
ECLASS
| ECLASS-13.0 | 27242604 |
| ECLASS-15.0 | 27242604 |
ETIM
| ETIM 10.0 | EC001599 |
UNSPSC
| UNSPSC 21.0 | 32151600 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
-
AXL F BS F - Bus connector 2688129
-
AXL F BS CAP - Protective cap 2702275
-
ZB 20,3:UNPRINTED - Zack marker strip 0820248
-
ZBF 10/5,8 AXL UNPRINTED - Zack Marker strip, flat 0829580
-
ZB 10:UNBEDRUCKT - Zack marker strip 1053001
-
ZBF 5:UNBEDRUCKT - Zack Marker strip, flat 0808642
-
EMT (35X46)R - Insert label 0801604
Your advantages
Meets the requirements of IEC 61850-3 and IEEE 1613
4 monostable relays
Floating connections for 4 actuators
Nominal current of each output: 8 A
Total current of the module: 32 A (4 x 8 A)
Device rating plate stored