The bus coupler is intended for use within a PROFINET network. The bus coupler creates the link to the Axioline P PROFIBUS PA segments and the PROFIBUS PA signals connected to them. Up to eight redundant Axioline P PROFIBUS PA segments can be connected to the bus coupler.
AXL P BK PN AF
-
Bus coupler
2316390
Axioline P, Bus coupler, PROFINET, RJ45 socket, auto negotiation and auto crossing, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and connectors
This product needs further products for operation.
Mandatory accessories
Free download available.
Downloads
Product details
| Dimensional drawing |
|
| Width | 45 mm |
| Height | 126.93 mm |
| Depth | 75 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Mounting type | DIN rail mounting |
| Mounting position | any |
| Color (Housing) | gray (RAL 7042) |
| Supported protocols | PROFINET |
| LLDP | |
| SNMP | |
| MRP | |
| DCP | |
| Axioline P local bus | |
| Number of interfaces | 1 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| PROFINET | |
| Number of interfaces | 2 |
| No. of channels | 2 |
| Connection method | RJ45 socket, auto negotiation and auto crossing |
| Transmission speed | 100 Mbps (Full duplex) |
| Transmission physics | Ethernet in RJ45 twisted pair |
| Fieldbus: Local bus gateway | |
| Max. number of local bus devices | 63 (Redundant PROFIBUS PA segments and AXL P I/O modules. Consider the logic current consumed by the devices.) |
| System limits | |
| Number of supported devices | max. 8 (per redundant PROFIBUS PA segments) |
| max. 63 (per station) | |
| PROFINET | |
| Device function | PROFINET device |
| Specification | Version 2.3 |
| Conformance Class | Conformance Class C |
| Device ID | 0148hex |
| Vendor ID | 00B0hex |
| Product type | I/O component |
| Product family | Axioline P |
| Type | block modular |
| Mounting position | any |
| Scope of supply | including bus base module and connectors |
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Maximum power dissipation for nominal condition | 5 W |
| Potentials: Supply of the bus coupler (UL) | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 4.15 A (19.2 V DC) |
| max. 3 A (via bus base module) | |
| 125 mA (24 V DC) | |
| Protective circuit | Surge protection; electronic |
| Reverse polarity protection; electronic | |
| Potentials: Axioline P local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Power supply unit | 2 A |
| Current draw | 3 A (via bus base module) |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: PROFINET interface 1 / PROFINET interface 2 | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 1 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 1 / functional ground | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 2 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 2 / functional ground | 1500 V AC, 50 Hz, 1 min |
| Test voltage: 24 V communications voltage (UL) feed-in / functional ground | 500 V AC, 50 Hz, 1 min |
| Connection technology | |
| Connection name | Power supply |
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline P: System and installation” user manual. |
| Power supply | |
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline P: System and installation” user manual. |
| Conductor cross-section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -40 °C ... 70 °C (Mounting position: panel mounting on horizontal DIN rail) |
| -40 °C ... 50 °C (Mounting position: any) | |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 2000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 2000 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Mechanical test | |
| Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6 | 2g |
| Shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 15g |
| Continuous shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 10g |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| ATEX | |
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | IBExU 18ATEXB018 X |
| IECEx | |
| Identification | Ex ec IIC T4 Gc |
| Certificate | IECEx IBE 18.0023X |
| UKCA Ex (UKEX) | |
| Identification | II 3G Ex ec IIC T4 Gc X |
| Certificate | PxCAI22UKEx2316390X |
| Ex data | |
| UL, USA / Canada | Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, IIC T4 |
| Item number | 2316390 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales key | DR06 |
| Product key | DRIP1A |
| GTIN | 4055626368382 |
| Weight per piece (including packing) | 321 g |
| Weight per piece (excluding packing) | 259 g |
| Customs tariff number | 85176200 |
| Country of origin | US |
ECLASS
| ECLASS-13.0 | 27242608 |
| ECLASS-15.0 | 27242608 |
ETIM
| ETIM 10.0 | EC001604 |
UNSPSC
| UNSPSC 21.0 | 32151600 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 7(a), 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-25
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
| 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol (CAS: 119-47-1) | |
| SCIP | 0ed5392b-61dc-4898-8cab-de1bf8266d85 |
Compatible products
Your advantages
2 Ethernet ports (with integrated switch)
PROFINET RT
Supports S2 system redundancy
Supports eight redundant PROFIBUS PA segments with up to 256 PROFIBUS PA instruments
Hot-swappable
Firmware can be updated
High temperature operating range