UL Recognized
Approval ID: E118976| Nominal voltage UN | Nominal current IN | Cross section AWG | Cross section mm2 | |
|---|---|---|---|---|
| keine | ||||
| 600 V | 80 A | - 6 | ||
Contact insert, number of positions: 4+PE, size: B16, power contacts: 4, control contacts: 0, Pin, Screw connection, 830 V, 80 A, 1.5 mm2 ... 16 mm2, application: Power
| General | For HEAVYCON-ADVANCE housings of B16 type and HEAVYCON housings of B16 and B32 types |
| General | Connectors may be operated only when there is no load/voltage. |
| Assembly note | To ensure correct use, installation in housing with IP54 protection or better is required |
| Use wire end protection (screw connections do not have wire protection) |
| Product type | Contact insert with a fixed no. of positions |
| Series | HC-K |
| Application | Power |
| Type | B16 |
| B32 | |
| Number of positions | 4 |
| Connection profile | 4+PE |
| Contact numbering | 1 - 4 |
| No. of power contacts | 4 |
| No. of control contacts | 0 |
| Contact material type | turned |
| Screwdriver blade | 0.8 x 4.5 mm (power contacts) |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
| Dimensional drawing |
|
| Width | 34 mm |
| Height | 42 mm |
| Length | 84.5 mm |
| Drill hole distance, horizontal | 77.5 mm |
| Mechanical characteristics | |
| Contact diameter | 6 mm |
| Connection technology | |
| Connection technology | Screw connection (power contacts) |
| Conductor connection | |
| Conductor cross-section | 1.5 mm² ... 16 mm² |
| Connection cross section AWG | 16 ... 6 |
| Tightening torque | 0.8 Nm ... 1.2 Nm (PE connection cross-section with cable lug expandable to 16 mm²) |
| 0.5 Nm ... 0.8 Nm (Mounting screws for mounting in the HEAVYCON housing) | |
| 3 Nm (4.0 mm² ... 16 mm²) | |
| 2 Nm (2.5 mm²) | |
| 1.2 Nm (1.5 mm²) | |
| Stripping length of the individual wire | 14 mm |
| Rated voltage (III/3) | 830 V (power contacts) |
| Rated surge voltage | 8 kV (power contacts) |
| Rated current | 80 A (power contacts) |
| Mechanical data | |
| Insertion/withdrawal cycles | ≥ 500 |
| Flammability rating according to UL 94 | V0 |
| Contact material | Cu alloy |
| Contact surface material | Ag |
| Contact carrier material | PC |
| Material of contact surface, power contact | Ag |
| Ambient conditions | |
| Ambient temperature (operation) | -40 °C ... 125 °C |
| Specification | IEC 60512-9-1:2010-03 |
| Requirements, visual check | There may be no malfunctions that could disturb the normal function. |
| No. of cycles | 500 |
| Vibration, broadband noise | |
| Specification | IEC 61373:2010-05 |
| Contact disturbance requirement | Duration of the disturbance: max. 1 μs |
| Requirements, visual check | No damage that can affect the intended use. |
| Lowest frequency | 5 Hz |
| Highest frequency | 150 Hz |
| Test directions | X-, Y- and Z-axis |
| Category | 1 |
| Class | B |
| Shock | |
| Specification | IEC 61373:2010-05 |
| Contact disturbance requirement | Duration of the disturbance: max. 1 μs |
| Requirements, visual check | No defects that impair normal functionality. |
| Acceleration | 50 m/s² |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Number of shocks per direction | 3 |
| Shock duration | 30 ms |
| Temperature rise | |
| Specification | IEC 60512-5-1:2002-02 |
| Requirements | The specified upper limiting temperature must not be exceeded. |
| Upper limiting temperature | 125 °C |
| Climatic test group | |
| Specification | IEC 61984:2008-10 |
| IEC 60512-11-10:2002-02 | |
| IEC 60512-11-9:2002-02 | |
| IEC 60512-11-7:2003-05 | |
| Requirements, visual check | No defects that impair normal functionality. |
| Cold stress | -40 °C/16 h |
| Thermal stress | 125 °C/168 h |
| Corrosive stress | 0,2 dm3 SO2 / 40 °C 3 °C / 24 h / 2 cycles |
| Specification | IEC 60512-2-2:2003-05 |
| Requirements | Initial value: 5 mΩ, max. |
| Requirements, Contact resistance | The contact resistance must not increase by more than 50% of the reference value or ≤ 5 mΩ. The higher value applies. |
| Test current | 1 A |
| Additional text | The values specified apply to all repetitions of the same test within the normative test sequence. |
| Specification | IEC 60512-4-1:2003-05 |
| Requirements, dielectric strength | No disruptive charge or sparkover |
| Test voltage | 690 V |
| Rated surge voltage | 8 kV |
| Specification | IEC 60512-3-1:2002-02 |
| Requirements, insulation resistance | RI ≥ 400 MΩ |
| Test voltage | 1000 V DC |
| Test duration | 60 s |
| Specification | IEC 60512-1-1:2002-02 |
| Requirements, visual check | No defects that impair normal functionality. |
| Additional text | The values specified apply to all repetitions of the same test within the normative test sequence. |
| Dimensional examination | |
| Specification | IEC 60512-1-2:2002-02 |
| Requirements | All individual parts have been approved for the current revision status. |
| Durability of marking | |
| Specification | IEC 60068-2-70:1995-12 |
| Requirements | Inscriptions must be legible after the test. |
| Polarization and coding | |
| Specification | IEC 61984:2008-10 |
| Requirements | No damage that can impair normal functionality. Connectors must only be able to be plugged in when they are in the correct position and combination. The design must prevent mismatching. Polarization prevents incorrect electrical contact. |
| Test force | 80 N |
| Contact retention in insert | |
| Specification | IEC 60512-15-1:2008-05 |
| Requirements | No axial offset should occur that can affect functions. |
| Mechanical strength impact | |
| Specification | IEC 60512-7-2:2011-11 |
| Requirements, visual check | Loose parts or damage that would impair functionality are not permitted. |
| Protection against electric shock | |
| Specification | IEC 61984:2008-10 |
| Requirements | Unencapsulated connectors: It must not be possible to touch live parts. Encapsulated connectors: The required air clearances and creepage distances must be maintained between the live parts and the test finger. |
| Test force | 20 N |
| Item number | 1679414 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales key | BF61 |
| Product key | AF7ABA |
| GTIN | 4017918168858 |
| Weight per piece (including packing) | 118.6 g |
| Weight per piece (excluding packing) | 115.8 g |
| Customs tariff number | 85366990 |
| Country of origin | CN |
| ECLASS-13.0 | 27440205 |
| ECLASS-15.0 | 27440205 |
| ETIM 10.0 | EC000438 |
| UNSPSC 21.0 | 39121500 |
| Nominal voltage UN | Nominal current IN | Cross section AWG | Cross section mm2 | |
|---|---|---|---|---|
| keine | ||||
| 600 V | 80 A | - 6 | ||
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 6(c) |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
| SCIP | ef036728-252d-401f-bf52-90336a2a46b2 |
| EF3.1 Climate Change | |
| CO2e kg | 9.669 kg CO2e |