The QUINT HP UPS for panel mounting, with IQ Technology and matching external battery module, ensures superior system availability. The online topology with a pure sine wave reliably supplies your AC loads with a perfect voltage at powers ranging from 1.5 kVA to 2.5 kVA.
QUINT-HP-UPS/230AC/2.5KVA/PT
-
Uninterruptible power supply
1136815
QUINT AC UPS, IQ Technology, Panel mounting, input: 230 V AC, output: 230 V AC / 2500 VA. At least 2x 1133819 are required for operation.. The product is being prepared for compliance with the Cyber Resilience Act (CRA).
This product needs further products for operation.
Mandatory accessories
Free download available.
Downloads
Product details
| Note on application | |
| Note on application | As things stand now, we are preparing the product so that, as of December 11, 2027, it will comply with the requirements of the EU Cyber Resilience Act (CRA) based on the information currently available regarding the CRA. |
| General | |
| Note on the battery | For proper operation of the UPS, at least 2 QUINT-HP-BAT/PB/48DC/7.0AH/PT (1133819) battery modules are required. For longer buffer times, multiples of 2 battery modules must always be connected to the UPS (2, 4, 6, 8, or 10). A maximum of 10 batteries can be connected to a single UPS. |
| Input voltage | 200 V AC -10 % / +20 % |
| 210 V AC -15 % / +20 % | |
| 220 V AC -15 % / +20 % | |
| 230 V AC -20 % / +15 % | |
| 240 V AC -20 % / +10 % | |
| Voltage type of supply voltage | AC |
| Frequency range (fN) | 47.5 Hz ... 52.5 Hz |
| 57 Hz ... 63 Hz | |
| Bypass fuse | 25 A T 250 V |
| Permissible backup fuse | B25 C25 |
| Current consumption | nom. 15.2 A (200 V AC) |
| nom. 14.5 A (210 V AC) | |
| nom. 13.8 A (220 V AC) | |
| nom. 13.2 A (230 V AC) | |
| nom. 12.7 A (240 V AC) | |
| max. 21.3 A (200 V AC) | |
| max. 21.4 A (210 V AC) | |
| max. 20.5 A (220 V AC) | |
| max. 20.8 A (230 V AC) | |
| max. 19.9 A (240 V AC) | |
| Rated short-time current carrying capacity Icw | 6 kA |
| Classification according to IEC 62040-3 | VFI-SS-111 |
| Efficiency | > 95 % (100% load, battery charged) |
| > 89 % (100% load, battery charged) | |
| Apparent power | 2500 VA |
| Real power | 2250 W |
| Power factor | 0.9 |
| Crest factor | 2.8 |
| Switch-over time | 0 ms |
| Connection in parallel | yes |
| max. 3 | |
| Connection in series | no |
| Overload capability Mains operation | 120 % ... 150 % (20 s / 5 s, then switch to bypass operation) |
| Overload capability Battery operation | 120 % ... 150 % (20 s / 5 s, then shutdown) |
| Overload capability Bypass mode | 120 % ... 150 % (for a sustained period / 20 s, then shutdown) |
| Rated short-time current carrying capacity Icw | 6 kA |
| Mains operation | |
| Output voltage | 200 V AC ±2 % |
| 210 V AC ±2 % | |
| 220 V AC ±2 % | |
| 230 V AC ±2 % | |
| 240 V AC ±2 % | |
| Form of output voltage | Pure sine |
| Output current | nom. 12.5 A (200 V AC) |
| nom. 11.9 A (210 V AC) | |
| nom. 11.4 A (220 V AC) | |
| nom. 10.9 A (230 V AC) | |
| Static Boost (IStat.Boost) | nom. 10.4 A (240 V AC) |
| Maximum no-load power dissipation | 10 W |
| Power loss nominal load max. | < 100 W (100% load, battery charged) |
| Nominal output frequency | 50 Hz |
| 60 Hz | |
| ±0.5 % (Output frequency tolerance) | |
| Electronic current limitation | > 2,5 x Output: Current nom. (> 200 ms) |
| Battery operation | |
| Maximum no-load power dissipation | 10 W |
| Power loss nominal load max. | 275 W (100% load, battery charged) |
| Nominal output frequency | 50 Hz |
| 60 Hz | |
| ±0.5 % (Output frequency tolerance) | |
| Total harmonic distortion factor (THD) | < 3 % (linear load) |
| < 8 % (non-linear load) | |
| Electronic current limitation | > 2,5 x Output: Current nom. (> 200 ms) |
| Input | |
| Input voltage | 48 V DC |
| max. 60 V DC | |
| Input current | max. 40 A |
| Nominal capacity range | 7 Ah ... 200 Ah |
| Charging current | max. 10 A |
| Output | |
| Short-circuit current | 650 A (< 1,5 ms) |
| General | |
| Connection in parallel | yes |
| max. 5 (per battery string) | |
| Connection in series | no |
| IQ-Technology | yes |
| Permissible backup fuse | 40 A |
| Temperature sensor | yes |
| Input | |
| Position | 1.x |
| Identification | 1.1 (L), 1.2 (N), 1.3 () |
| Connection technology | |
| Position marking | 1.1 (L), 1.2 (N), 1.3 () |
| Conductor connection | |
| Connection method | Push-in connection |
| rigid (Terminal block) | 2.5 mm² ... 6 mm² |
| flexible (Klemme) | 2.5 mm² ... 6 mm² |
| flexible with ferrule without plastic sleeve (Terminal block) | 2.5 mm² ... 4 mm² |
| flexible with ferrule with plastic sleeve (Terminal block) | 2.5 mm² ... 4 mm² |
| AWG (Terminal block) | 14 ... 10 (Cu) |
| Stripping length (starr/flexibel) | 10 mm (Rigid/flexible/ferrule) |
| Output | |
| Position | 2.x |
| Identification | 2.1 (L), 2.2 (N), 2.3 () |
| Connection technology | |
| Position marking | 2.1 (L), 2.2 (N), 2.3 () |
| Conductor connection | |
| Connection method | Push-in connection |
| rigid (Terminal block) | 2.5 mm² ... 6 mm² |
| flexible (Klemme) | 2.5 mm² ... 6 mm² |
| flexible with ferrule without plastic sleeve (Terminal block) | 2.5 mm² ... 4 mm² |
| flexible with ferrule with plastic sleeve (Terminal block) | 2.5 mm² ... 4 mm² |
| AWG (Terminal block) | 14 ... 10 (Cu) |
| Stripping length (starr/flexibel) | 10 mm (Rigid/flexible/ferrule) |
| Output | |
| Position | 2.x |
| Identification | 2.4 (L'), 2.5 (N), 2.6 () |
| Connection technology | |
| Position marking | 2.4 (L'), 2.5 (N), 2.6 () |
| Conductor connection | |
| Connection method | Push-in connection |
| rigid (Terminal block) | 2.5 mm² ... 6 mm² |
| flexible (Klemme) | 2.5 mm² ... 6 mm² |
| flexible with ferrule without plastic sleeve (Terminal block) | 2.5 mm² ... 4 mm² |
| flexible with ferrule with plastic sleeve (Terminal block) | 2.5 mm² ... 4 mm² |
| AWG (Terminal block) | 14 ... 10 (Cu) |
| Stripping length (starr/flexibel) | 15 mm (Rigid/flexible/ferrule) |
| Battery | |
| Position | 4.x |
| Identification | 4.1, 4.2; 4.3, 4.4 |
| Connection technology | |
| Position marking | 4.1 (+), 4.2 (-), 4.3 (+), 4.4 (-) |
| Conductor connection | |
| Connection method | Push-in connection |
| rigid (Terminal block) | 6 mm² ... 16 mm² |
| flexible (Klemme) | 6 mm² ... 16 mm² |
| flexible with ferrule without plastic sleeve (Terminal block) | 6 mm² ... 16 mm² |
| flexible with ferrule with plastic sleeve (Terminal block) | 6 mm² ... 16 mm² |
| AWG (Terminal block) | 8 ... 6 (Cu) |
| Stripping length (starr/flexibel) | 18 mm (Rigid/flexible/ferrule) |
| Signal | |
| Position | 3.x |
| Identification | 3.1 ... 3.9 |
| Connection technology | |
| Position marking | 3.1 (Alarm), 3.2 (Bat.-Mode), 3.3 (Power Good), 3.4 (Ready), 3.5 (P>Pn), 3.6 (Service Required), 3.7 (Bat.-Start), 3.8 (Remote), 3.9 (SGnd) |
| Conductor connection | |
| Connection method | Push-in connection |
| rigid (Terminal block) | 0.2 mm² ... 4 mm² |
| flexible (Klemme) | 0.2 mm² ... 4 mm² |
| flexible with ferrule without plastic sleeve (Terminal block) | 0.2 mm² ... 2.5 mm² |
| flexible with ferrule with plastic sleeve (Terminal block) | 0.2 mm² ... 2.5 mm² |
| AWG (Terminal block) | 24 ... 12 (Cu) |
| Stripping length (starr/flexibel) | 10 mm (Rigid/flexible/ferrule) |
| Communication | |
| Position | 5.x |
| Identification | 5.1 ... 5.3 |
| Connection technology | |
| Position marking | 5.1 (LIN), 5.2 (Parallel Port), 5.3 (Parallel Port) |
| Conductor connection | |
| Connection method | RJ45 |
| Communication interface | |
| Interface | Battery module communication interface |
| Number of interfaces | 1 |
| Connection method | RJ45 |
| Position | 5.x |
| Locking | Locking clip |
| Transmission physics | Twisted-Pair 4x2 |
| Communication interface | |
| Interface | Parallel operation communication interface |
| Number of interfaces | 2 |
| Connection method | RJ45 |
| Position | 5.x |
| Locking | Locking clip |
| Transmission physics | Twisted-Pair 4x2 |
| Signal input Bat.-Start | |
| Signalization designation | Bat.-Start |
| Position | 3.x |
| Position marking | 3.7 (Bat.-Start) |
| Low signal | Connection to SGnd with < 2.7 kΩ |
| High signal | Open (> 200 kΩ between Bat.-Start and SGnd) |
| Signal input Remote | |
| Signalization designation | Remote |
| Position | 3.x |
| Position marking | 3.8 (Remote) |
| Low signal | Connection to SGnd with < 2.7 kΩ |
| High signal | Open (> 35 kΩ between Remote and SGnd) |
| Signal output Alarm | |
| Position | 3.x |
| Signalization designation | Alarm |
| Position marking | 3.1 (Alarm) |
| Switching output | Transistor output, active |
| Output voltage | 24 V |
| Continuous load current | ≤ 20 mA |
| Signal output Battery Mode | |
| Position | 3.x |
| Signalization designation | Bat.-Mode |
| Position marking | 3.2 (Bat.-Mode) |
| Switching output | Transistor output, active |
| Output voltage | 24 V |
| Continuous load current | ≤ 20 mA |
| Signal output Power Good | |
| Position | 3.x |
| Signalization designation | Power Good |
| Position marking | 3.3 (Power Good) |
| Switching output | Transistor output, active |
| Output voltage | 24 V |
| Continuous load current | ≤ 20 mA |
| Signal output Ready | |
| Position | 3.x |
| Signalization designation | Ready |
| Position marking | 3.4 (Ready) |
| Switching output | Transistor output, active |
| Output voltage | 24 V |
| Continuous load current | ≤ 20 mA |
| Signal output P > PN | |
| Position | 3.x |
| Signalization designation | P>Pn |
| Position marking | 3.5 (P>Pn) |
| Switching output | Transistor output, active |
| Output voltage | 24 V |
| Continuous load current | ≤ 20 mA |
| Signal output Service Required | |
| Position | 3.x |
| Signalization designation | Service Required |
| Position marking | 3.6 (Service Required) |
| Switching output | Transistor output, active |
| Output voltage | 24 V |
| Continuous load current | ≤ 20 mA |
| Signal ground SGnd | |
| Function | Signal ground |
| Reference potential | For signal inputs and signal outputs |
| Product type | AC UPS |
| Product family | QUINT AC UPS |
| Special properties | The product is being prepared for compliance with the Cyber Resilience Act (CRA) |
| Insulation characteristics | |
| Protection class | I |
| Overvoltage category | II |
| Pollution degree | 2 |
| Item dimensions | |
| Width | 188 mm |
| Height | 240 mm |
| Depth | 143 mm |
| Drill hole | |
| Diameter | 5.5 mm |
| Installation dimensions | |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
| Mounting type | Panel mounting |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 60 °C (> 50 °C: 2,5 % / K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 4000 m (> 1000 m: 3 % / 1000 m) |
| Max. permissible relative humidity (operation) | ≤ 95 % |
| Shock | 30g in each direction, according to IEC 60068-2-27 |
| Vibration (operation) | 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
| Uninterruptible power supply systems | |
| Standard designation | Uninterruptible power supply systems |
| Standards/specifications | EN 62040-1 |
| EN 62040-2 | |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 |
| Electrostatic discharge | |
| Contact discharge | ± 6 kV |
| Discharge in air | ± 8 kV |
| Comments | Criterion A |
| Electromagnetic HF field | |
| Standards/regulations | EN 61000-4-3 |
| Electromagnetic HF field | |
| Frequency range | 80 MHz ... 6 GHz |
| Test field strength | 10 V/m |
| Comments | Criterion A |
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 |
| Fast transients (burst) | |
| Input | ± 2 kV |
| ± 2 kV | |
| Output | ± 2 kV |
| Signal | ± 2 kV |
| ± 2 kV (Communication parallel operation, battery module) | |
| Comments | Criterion A |
| Surge voltage load (surge) | |
| Standards/regulations | EN 61000-4-5 |
| Surge voltage load (surge) | |
| Input/Output | ± 1 kV (symmetrical) |
| ± 2 kV (asymmetrical) | |
| Signal | 1 kV (asymmetrical) |
| Comments | Criterion A |
| Input/Output | ± 1 kV (symmetrical) |
| ± 2 kV (asymmetrical) | |
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 |
| Conducted interference | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Signal | 10 V (asymmetrical) |
| Comments | Criterion A |
| Power frequency magnetic field | |
| Standards/regulations | EN 61000-4-8 |
| Frequency | 50 Hz |
| Signal | 30 A/m |
| Comments | Criterion A |
| Harmonic and interharmonic components | |
| Standards/regulations | EN 61000-4-13 |
| Harmonic and interharmonic components | |
| Frequency range | 140 Hz ... 360 Hz |
| Signal | 10 V |
| Comments | Criterion A |
| Criteria | |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Item number | 1136815 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales key | CM30 |
| Product key | CMUW15 |
| GTIN | 4063151073121 |
| Weight per piece (including packing) | 5,936 g |
| Weight per piece (excluding packing) | 5,400 g |
| Customs tariff number | 85371091 |
| Country of origin | DE |
ECLASS
| ECLASS-13.0 | 27040705 |
| ECLASS-15.0 | 27040705 |
ETIM
| ETIM 10.0 | EC000382 |
UNSPSC
| UNSPSC 21.0 | 39121000 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes (No exemptions) |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
| EF3.1 Climate Change | |
| CO2e kg | 167.543 kg CO2e |
Compatible products
Your advantages
Pure sine wave in normal and battery operation
Can be switched in parallel for increased performance, redundancy, or for a 3 AC system
Startup from the energy storage system possible, even without mains input
Communication platform: Com.board with USB or serial interface
Compact design with active cooling
PHOENIX CONTACT
586 Fulling Mill Road, Middletown, PA 17057