MACX MCR-EX-TC-I-C - Temperature measuring transducer
1052458

Is being prepared to meet the requirements of the CRA

Ex i-Temperature measuring transducer converts signals from thermocouples installed in the Ex area and mV sources and transmits a 0 mA/4 mA ... 20 mA signal to a load in the safe area. number of channels: 1, Order configuration, freely programmable, 3-way isolation, Safety Integrity Level (SIL, IEC 61508): 2, Systematic Capability: 2, Screw connection

Free download available. Downloads

Product details









Compatible products



Your advantages

Input for thermocouples and mV sources
Power supply possible via DIN rail connector
Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
Installation in zone 2, protection type "ec" (EN 60079-7) permitted
3-way electrical isolation
Status indicator for supply voltage, cable, sensor, and module errors
Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
Output: 0 mA ... 20 mA or 4 mA ... 20 mA