Thermal device circuit breakers - TCP 2A 0712217

Thermal miniature circuit breaker, pluggable in screw-type fuse terminal block UK 6-FSI/C and spring-cage fuse terminal block ST 4-FSI/C


Product Details




Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C
Humidity test 240 h, 95 % RH, 40 °C
Degree of protection IP40 (Actuation area)
Altitude 4000 m

General When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly.

Fuse Slow-blow
Dielectric strength 3000 V AC (Actuation area)
1500 V AC (Installation area)
Rated current IN 2 A
Rated surge voltage 2.5 kV
No. of channels 1
Fuse type Automatic device
Maximum power dissipation for nominal condition ≤ 1 VA
Switching cycles, max. 6000 (At 1 x In, low-induction)
3000 (At 1 x In, inductive)
500 (At 2 x In, inductive)
Short-circuit switching capacity 2000 A (250 V AC / UL 1077)
2000 A (72 V DC / UL 1077)
Device resistance 0 Ω
Rated voltage 250 V AC
65 V DC
250 V (AC according to UL 1077)
72 V (DC according to UL 1077)
Rated short-circuit switching capacity Icn 12 A (250 V AC / 65 V DC)
20 A (30 V DC)
Insulation resistance Riso > 100 MΩ (500 V DC)
Tripping method T (thermal)

Mechanical data
Open side panel No

Dimensional drawing
Height 24.4 mm
Width 8.2 mm
Depth 44.5 mm
Height NS 35/7,5 55 mm

Insulating material group IIIb
Color black
Insulating material PPS
Flammability rating according to UL 94 V0

Mounting type on base element

Nominal current 2 A
Nominal voltage 250 V AC
65 V DC

Standards/specifications EN 60934

Number of positions 1
Type Male
No. of channels 1
Insulation characteristics
Overvoltage category II
Degree of pollution 2


Order Key 0712217
Packing unit 20 pc
Minimum order quantity 1 pc
Sales Key 010
Catalog Page Page 401 (C-4-2019)
GTIN 4017918848361
Weight per Piece (including packing) 11,5 GRM
Weight per Piece (excluding packing) 10,5 GRM
Customs tariff number 85362010
Country of origin ID



CSA

Approval Specification Data
Nominal voltage UN 250 V
Nominal current IN 2 A

UL Recognized

cUL Recognized

EAC

CCC

EAC

VDE Zeichengenehmigung

cULus Recognized


China RoHS Environmentally Friendly Use Period = 25;
China RoHS For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”