PROFIBUS or other RS-485 networks can be actively terminated at the end of the bus using the PSI-TERMINATOR-PB. This ensures safe communication even if the bus device is connected/disconnected during operation. In addition, the connectable termination enables the device to be operated as a service interface at any point in the bus system. For the operation of active programming and diagnostic devices, the required power supply is provided at the alternative D-SUB connection.
    
  
  PSI-TERMINATOR-PB
   - 
  Termination resistor
    
      2313944
      
      
    
  
      Active termination resistor for PROFIBUS and RS-485 bus systems. Compact design, electrical isolation between supply and data interface, bus termination can be activated, integrated programming interface.
Product details
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area | 
| Utilization restriction | |
| CCCex note | Use in potentially explosive areas is not permitted in China. | 
| Product type | Terminal resistor | 
| MTTF | 3550 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) | 
| 1818 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
| 849 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) | |
| MTBF | 2383 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) | 
| 559 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | 
| Electrical isolation | RS-485 // VCC | 
| Maximum power dissipation for nominal condition | 1.08 W | 
| Test voltage data interface/power supply | 1.5 kVrms (50 Hz, 1 min.) | 
| Supply | |
| Supply voltage range | 19.2 V DC ... 28.8 V DC (via pluggable COMBICON screw terminal block) | 
| Nominal supply voltage | 24 V DC (via pluggable COMBICON screw terminal block) | 
| Typical current consumption | 45 mA (24 V DC) | 
| Function | |
| Status and diagnostic indicators | LEDs: UL (communications power), data activity (not marked) | 
| Supply | |
| Tightening torque | 0.56 Nm ... 0.79 Nm | 
| Signal | Modbus | 
| PROFIBUS | |
| Data: PROFIBUS acc. to IEC 61158, RS-485 2-conductor | |
| Serial transmission speed | ≤ 12 Mbps | 
| Connection method | D-SUB-9, COMBICON | 
| Transmission length | ≤ 1200 m (Depends on transmission speed and cable type) | 
| Termination resistor | 390 Ω | 
| 220 Ω | |
| 390 Ω (Can be connected) | |
| Conductor cross-section flexible max. | 1.5 mm² | 
| Conductor cross-section flexible min. | 0.2 mm² | 
| Conductor cross-section, rigid max. | 1.5 mm² | 
| Conductor cross-section, rigid min. | 0.2 mm² | 
| Conductor cross-section AWG max. | 16 | 
| Conductor cross-section AWG min. | 24 | 
| Output nominal voltage | 5 V DC | 
| Dimensional drawing |  | 
| Width | 22.5 mm | 
| Height | 99 mm | 
| Depth | 56 mm | 
| Color (Housing) | green (RAL 6021) | 
| Material (Housing) | PA 6.6-FR | 
| Free fall in accordance with IEC 60068-2-32 | Free fall: 1 m | 
| Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6 | Vibration (operation): 5g, 10...150 Hz, 2.5 h, in XYZ direction | 
| Shock in accordance with EN 60068-2-27/IEC 60068-2-27 | Shock (operation): 25g, 11 ms period, half-sine shock pulse | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -20 °C ... 65 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) | 
| Permissible humidity (operation) | 30 % ... 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| UL, USA/Canada | |
| Identification | 508 Listed | 
| Class I, Div. 2, Groups A, B, C, D | |
| UL, USA | |
| Identification | Class I, Zone 2, AEx nA IIC T5 | 
| UL, Canada | |
| Identification | Class I, Zone 2, Ex nA IIC T5 Gc X | 
| Corrosive gas test | |
| Identification | ISA-S71.04-1985 G3 Harsh Group A | 
| ATEX | |
| Identification |  II 3 G Ex nA IIC T4 Gc X | 
| Note | Please follow the special installation instructions in the documentation! | 
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU | 
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 | 
| Electrostatic discharge | |
| Contact discharge | ± 6 kV (Test Level 3) | 
| Discharge in air | ± 8 kV (Test Level 3) | 
| Comments | Criterion B | 
| Electromagnetic HF field | |
| Standards/regulations | EN 61000-4-3 | 
| Electromagnetic HF field | |
| Frequency range | 80 MHz ... 3 GHz (Test Level 3) | 
| Field intensity | 10 V/m | 
| Comments | Criterion A | 
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 | 
| Fast transients (burst) | |
| Input | ± 2.2 kV (Test Level 3) | 
| Signal | ± 2.2 kV (Test Level 3) | 
| Comments | Criterion B | 
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 | 
| Surge current load (surge) | |
| Input | ± 0.5 kV (DC supply) | 
| Signal | ± 1 kV (Data line, asymmetrical) | 
| Comments | Criterion B | 
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 | 
| Conducted interference | |
| Frequency range | 0.15 MHz ... 80 MHz | 
| Comments | Criterion A | 
| Voltage | 10 V | 
| Emitted interference | |
| Standards/regulations | EN 61000-6-4 | 
| Radio interference voltage in acc. with EN 55011 | EN 55011 class A industrial area of application | 
| Emitted radio interference in acc. with EN 55011 | EN 55011 class A industrial area of application | 
| Criteria | |
| Criterion A | Normal operating behavior within the specified limits. | 
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. | 
| Free from substances that could impair the application of coating | in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 | 
| Mounting type | DIN rail mounting | 
| Item number | 2313944 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Note | Made to order (non-returnable) | 
| Sales key | 096 | 
| Product key | DNC141 | 
| GTIN | 4046356579445 | 
| Weight per piece (including packing) | 136 g | 
| Weight per piece (excluding packing) | 124,2 g | 
| Customs tariff number | 85389091 | 
| Country of origin | DE | 
UNSPSC
| UNSPSC 21.0 | 32121617 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 6(c), 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      
- 
    
      SUBCON-PLUS-PROFIB/90/PG/IDC - D-SUB bus connector 2313685
- 
    
      SUBCON-PLUS-PROFIB/90/SC - D-SUB bus connector 2313698
- 
    
      SUBCON-PLUS-PROFIB/90/PG/SC - D-SUB bus connector 2313708
- 
    
      SUBCON-PLUS-PROFIB/35/M12 - D-SUB bus connector 2902320
- 
    
      SUBCON-PLUS-PROFIB/90/M12 - D-SUB bus connector 2902318
- 
    
      SUBCON-PLUS-PROFIB/90X/M12 - D-SUB bus connector 2902729
- 
    
      PSM-CABLE-PROFIB/FC - Bus system cable 2744652
- 
    
      SZF 0-0,4X2,5 - Screwdriver 1204504
- 
    
      PSM-STRIP-FC/PROFIB - Stripping tool 2744623
- 
    
      QUICK WIREFOX 6 - Stripping pliers 1204384
- 
    
      SUBCON-PLUS-PROFIB/SC2 - D-SUB bus connector 2708232
- 
    
      SUBCON-PLUS-PROFIB/PG/SC2 - D-SUB bus connector 2708245
- 
    
      SUBCON-PLUS-PROFIB/AX/SC - D-SUB bus connector 2744380
- 
    
      PSI-REP-PROFIBUS/12MB - Repeater 2708863
- 
    
      PSI-REP-RS485W2 - Repeater 2313096
- 
    
      PSM-ME-RS485/RS485-P - Repeater 2744429
- 
    
      PSM-ME-RS232/RS485-P - Interface converter 2744416
Your advantages
Extended temperature range of -20°C ... +65°C
        DIN rail mounting
        Termination can be connected externally
        Fixed programming interface in the network
        Electrical isolation of power supply and data interface
        Interference-free bus communication thanks to active termination
        Diagnostic LEDs for voltage and data activity
        Compact housing design
        PHOENIX CONTACT (Pty) Ltd.
        
        36 Lyn Road P.O. Box 916 ZA-Ferndale 2160