PV set - PV SET 1ST/1000DC/SPD-SC 2801529

Lightning and surge arrester in IP65 housing for protecting single-string photovoltaic systems up to 1000 V DC, connection via SUNCLIX plug/socket.


Product Details




IEC test classification PV T1
PV T2
Type Installation housing
Number of positions 2
Surge protection fault message optical
Insulation characteristics
Protection class II
Overvoltage category III
Pollution degree 2

Mounting type Surface/Wall mounting

Color light grey RAL 7035
Flammability rating according to UL 94 V2 (Gehäuse / Deckel)
V0 (Steckverbinder)
Cover material Polycarbonate, transparent
Connector material PA
Impact strength IK08
Housing material Polycarbonate, glass-fiber-reinforced

Dimensional drawing
Width 125 mm
Height 200 mm
Depth 122 mm

Direction of action (L+)-PE & (L-)-PE & (L+)-(L-)
Rated load current IL 80 A DC
Residual current IPE ≤ 25 µA
≤ 350 µA
Standby power consumption PC ≤ 25 mVA
Nominal discharge current In (8/20) µs 15 kA
Maximum discharge current Imax (8/20) µs 40 kA
Total discharge current Itotal (8/20) µs 40 kA
Total discharge current Itotal (10/350) µs 5 kA
Voltage protection level Up (L+) - (L-) ≤ 3.5 kV
Voltage protection level Up (L+/L-) - PE ≤ 3.5 kV
Response time tA ≤ 25 ns
Response time tA (L+) - (L-) ≤ 25 ns
Response time tA (L+/L-) - PE ≤ 25 ns
Max. backup fuse with branch wiring not required
Protective circuit DC voltage side (DC)
Rated surge voltage resistance Uimp 6 kV
Short-circuit current ISCSTC 25 A DC
Open circuit voltage UOCSTC 830 V DC (Solar generator)
Maximum discharge current Imax (8/20) µs 40 kA
Response time tA ≤ 25 ns
Response time tA (L+) - (L-) ≤ 25 ns
Response time tA (L+/L-) - PE ≤ 25 ns
Impulse discharge current (10/350) µs, peak value limp 5 kA
Recommended backup fuse maximum not required
Total discharge current Itotal (8/20) µs 40 kA
Total discharge current Itotal (10/350) µs 5 kA
Max. backup fuse with branch wiring not required
Nominal discharge current In (8/20) µs 15 kA
Rated load current IL 80 A DC
Residual current IPE ≤ 25 µA
≤ 350 µA
Voltage protection level Up (L+) - (L-) ≤ 3.5 kV
Voltage protection level Up (L+/L-) - PE ≤ 3.5 kV
Standby power consumption PC ≤ 25 mVA

Nominal current IN 25 A DC
Indicator/remote signaling
Switching function Changeover contact, 1-pos.
Maximum operating voltage Umax. AC 250 V AC
Maximum operating voltage Umax DC 30 V DC
Max. operating current Imax 1.5 A AC (250 V AC)
1.5 A DC (30 V DC)

Standards/specifications IEC 61439-2
EN 61439-2
EN 50539-11
Air clearances and creepage distances
Standards/regulations EN 50539-11

Ambient conditions
Degree of protection IP65
Degree of protection IP65
Impact strength IK08
Ambient conditions A, B
Ambient temperature (operation) -30 °C ... 55 °C


Order Key 2801529
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CL1
Catalog Page Page 60 (C-6-2015)
GTIN 4046356804783
Weight per Piece (including packing) 1 460,0 GRM
Weight per Piece (excluding packing) 1 285,0 GRM
Customs tariff number 85363030
Country of origin DE