IO components, safety related - AXL F LPSDO8/3 1F 2702171

Safety-related digital output module, IP20 protection, for the SafetyBridge system. The module has four safe digital outputs with two-channel occupancy or 8 safe digital outputs with single-channel occupancy


Product Details


The safety module is an output module from the Axioline F product range with integrated safety logic designed for use in a SafetyBridge Technology V3 system. The safety module can be used as part of an Axioline F station at any point within an EtherCAT®, EtherNet/IP™, Sercos, Modbus, PROFINET or PROFIBUS system. The module has four safe digital outputs for two-channel assignment or eight safe digital outputs for single-channel assignment.



Transmission medium Copper
Potentials
Protective circuit Protection against polarity reversal, EMC protective circuit, undervoltage detection
Potentials: Supply for digital output modules (UO)
Current draw typ. 25 mA (all outputs set; power supply by UO with 30.2 V DC; without power supply to the actuator)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30.2 V DC (including all tolerances, including ripple)
Potentials: Axioline F local bus supply (UBus)
Current draw max. 280 mA
typ. 260 mA (all outputs set; power supply by UO of 19.2 V DC to 30.2 V DC)
Supply voltage 5 V DC (via bus base module)

Dimensional drawing
Note on dimensions Housing dimensions
Height 126.1 mm
Width 53.6 mm
Depth 54 mm

Digital
Maximum output current per channel 2 A
Behavior with overload Affected output is disabled and a diagnostic message is generated.
Maximum output current per module / terminal block 8 A
Output name Digital outputs
Output voltage 24 V DC
Number of outputs 4 (with two-channel assignment)
8 (for single-channel assignment)
8
Protective circuit Overload protection, freewheeling circuit for inductive loads,Discharge circuit for accelerated discharge of capacitive loads
Output current max. 2 A (per channel)
max. 1.5 A (per channel according to CULUS)
max. 4 A (per group)
max. 3 A (per group according to CULUS)
max. 8 A (Total current of all outputs; Please observe the notes in the user manual.)
max. 6 A (Total current of all outputs according to CULUS)

Housing color yellow

Mounting type DIN rail

Axioline F local bus
Connection method Bus base module

Safety data: EN 62061
Safety Integrity Level Claim Limit (SIL CL) max. 3 (two channel; dependent in parameterization and wiring)
Safety data: EN ISO 13849
Category max. 4 (two channel; dependent in parameterization and wiring)
Performance level (PL) max. e (two channel; dependent in parameterization and wiring)
Safety data: IEC 61508 - High demand
SIL_GRP max. 3 (two channel; dependent in parameterization and wiring)
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL) max. 3 (two channel; dependent in parameterization and wiring)

SafetyBridge properties
Logic memory 30 kByte
Connection to I/O modules max. 16 (safe digital I/O modules)

Air pressure (operation) 70 kPa ... 108 kPa (up to 3000 m above sea level)
Ambient temperature (operation) -35 °C ... 60 °C (Mounting position: any)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above sea level)
Permissible humidity (storage/transport) 10 % ... 75 % (non-condensing)
Permissible humidity (operation) 10 % ... 75 % (on average, 85% infrequently, non-condensing)

Connection technology
Connection name Axioline F connector
Axioline F connector
Conductor cross section AWG 24 ... 16
Conductor cross section, flexible 0.2 mm2 ... 1.5 mm2
Connection method Spring-cage connection
Conductor cross section, rigid 0.2 mm2 ... 1.5 mm2
Conductor connection
Conductor cross section AWG 24 ... 16
Conductor cross section solid 0.2 mm2 ... 1.5 mm2
Connection method Spring-cage connection
Conductor cross section flexible 0.2 mm2 ... 1.5 mm2

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Type modular
Axioline
Application SafetyBridge technology


Order Key 2702171
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CNA
Catalog Page Page 269 (C-6-2019)
GTIN 4055626004983
Weight per Piece (including packing) 352,9 GRM
Weight per Piece (excluding packing) 222,0 GRM
Customs tariff number 85389091
Country of origin DE



Functional Safety

UL Listed

cUL Listed

Functional Safety

BSH

DNV GL

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
China RoHS For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”


Your advantages

Cost-effective system configuration, as no safety PLC or safe fieldbus system is required
Flexible use, thanks to compatibility with all bus couplers from the Axioline F range
Reduced installation time, thanks to fast wiring and easy handling
Up to SIL 3 according to EN 61508
Up to SILCL 3 according to EN 62061
Up to cat. 4/PL e according to EN ISO 13849-1
Easy configuration using the free SAFECONF software