A field multiplexer system is a simple system for transmitting signals between two remote stations. It has a modular structure and is designed to reduce conventional parallel cabling. A field multiplexer system consists of two identical field multiplexer stations. The field multiplexer exchanges data with the remote station via a remote bus cable. The field multiplexer is the central unit of a field multiplexer station. All the necessary Inline I/O terminals of a station are connected to the field multiplexer.
    
  
  IB IL 24 MUX MA-PAC
   - 
  Field multiplexer
    
      2861205
      
      
    
  
      Inline field multiplexer, complete with accessories (connector and labeling field), transmission of very remote signals without configuration
Product details
| Dimensional drawing |  | 
| Width | 48.8 mm | 
| Height | 135 mm | 
| Depth | 71.5 mm | 
| Note on application | |
| Note on application | Only for industrial use | 
| Remote bus | |
| Connection method | Inline shield connector | 
| Transmission physics | RS-485 | 
| Inline local bus | |
| Connection method | Inline data jumper | 
| Transmission speed | 500 kbps | 
| System limits | |
| Number of local bus devices that can be connected | 32 (without additional power terminal block, observe allowable total current consumption) | 
| Number of devices with parameter channel | 0 | 
| Number of supported branch terminals with remote bus branch | 0 | 
| Module | |
| ID code (hex) | none | 
| Relay | |
| Contact switching type | N/C contact | 
| Contact connection type | floating contacts | 
| Switching voltage | typ. 24 V DC | 
| max. 150 V | |
| max. 125 V AC | |
| Switching current | max. 1 A | 
| Switching power | max. 30 W | 
| max. 60 VA | |
| Product type | I/O component | 
| Product family | Inline | 
| Type | modular | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 (in accordance with EN 50178) | 
| Maximum power dissipation for nominal condition | 3 W | 
| Protective circuit | Surge protection (segment supply, main supply, field multiplexer supply); Input protective diodes (can be destroyed by permanent overload)Pulse loads up to 1500 W are short circuited by the input protective diode. | 
| Protection against polarity reversal (segment supply/main supply); Parallel diodes for protection against polarity reversal; in the event of an error the high current flowing through the diodes causes the fuse connected upstream to blow. | |
| Protection against polarity reversal (field multiplexer supply); Serial diode in the lead path of the power supply unit; in the event of an error only a low current flows. In the event of an error, no fuse trips within the external power supply unit. | |
| Potentials: Field multiplexer supply UMUX; the communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from supply UMUX. | |
| Supply voltage | 24 V DC (via Inline connector) | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Current draw | max. 1.25 A (with max. number of connected I/O terminal blocks) | 
| typ. 60 mA (without connected Inline I/O terminals) | |
| Potentials: Communications power (UL) | |
| Supply voltage | 7.5 V DC ±5 % | 
| Potentials: Supply of analog modules (UANA) | |
| Supply voltage | 24 V DC (via Inline connector) | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Potentials: Main circuit supply (UM) | |
| Supply voltage | 24 V DC (via voltage jumper) | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Potentials: Segment circuit supply (US) | |
| Supply voltage | 24 V DC (via voltage jumper) | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: RS-485 interface / supply voltage | 500 V AC | 
| Test voltage: RS-485 interface / local bus | 500 V AC | 
| Connection technology | |
| Connection name | Inline connector | 
| Conductor connection | |
| Connection method | Spring-cage connection | 
| Conductor cross-section rigid | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section flexible | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 28 ... 16 | 
| Stripping length | 8 mm | 
| Inline connector | |
| Connection method | Spring-cage connection | 
| Conductor cross-section, rigid | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible | 0.08 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 28 ... 16 | 
| Stripping length | 8 mm | 
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 55 °C | 
| Degree of protection | IP20 | 
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Ambient temperature (storage/transport) | -25 °C ... 85 °C | 
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | 
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) | 
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | 
| Mounting type | DIN rail mounting | 
| Item number | 2861205 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | 110 | 
| Product key | DRI11M | 
| GTIN | 4017918902506 | 
| Weight per piece (including packing) | 258,5 g | 
| Weight per piece (excluding packing) | 212 g | 
| Customs tariff number | 85389091 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27242608 | 
| ECLASS-15.0 | 27242608 | 
ETIM
| ETIM 9.0 | EC001604 | 
UNSPSC
| UNSPSC 21.0 | 32151600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | d3fdeb6a-6ef6-4be6-8499-fe25d611eb53 | 
Compatible products
- 
    
      CLIPFIX 35 - End bracket 3022218
- 
    
      CLIPFIX 35-5 - End bracket 3022276
- 
    
      E/UK - End bracket 1201442
- 
    
      E/AL-NS 35 - End bracket 1201662
- 
    
      IB IL SCN-PWR IN-CP - Inline connector 2727637
- 
    
      IB IL FIELD 8 - Marking field 2727515
- 
    
      EMT (62X46)R - Insert label 0800059
- 
    
      IB IL FIELD 2 - Marking field 2727501
- 
    
      EMT (62X10)R - Insert label 0800057
- 
    
      IB IL MUX-CAB PSI - Adapter cable 2878476
Your advantages
Remote bus connections in copper technology (can be operated via fiber optics using an interface converter as an option)
        A field multiplexer station can be supplied with all of the required 24 V voltages
        Floating alarm output (“N/C” relay contact) for connecting alarm signals
        Up to 63 I/O terminals can be connected
        Up to 512 digital or 32 analog I/Os (or a mixture) can be connected
        Connection establishment and comparison of the I/O configuration of both stations
        Frequently searched
PHOENIX CONTACT (Pty) Ltd.
        
        36 Lyn Road P.O. Box 916 ZA-Ferndale 2160