Inline XC, Digital output terminal, Digital outputs: 4, 24 V DC, 500 mA, connection method: 3-conductor, Extreme conditions version, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field


Product Details


The terminal is designed for use within an Inline station.It is used to output digital signals.Thanks to special engineering measures and tests, the terminal can be used under extreme ambient conditions.



Dimensional drawing
Width 12.2 mm
Height 140.5 mm
Depth 71.5 mm
Note on dimensions Housing dimensions

Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Color green

Inline local bus
No. of channels 2
Connection method Inline data jumper
Transmission speed 500 kbps

Module
ID code (dec.) 189
ID code (hex) BD

Digital
Output name Digital outputs
Connection method Spring-cage connection
Connection technology 3-conductor
Number of outputs 4
Protective circuit Overload protection, short-circuit protection of outputs; Zener diode in output chip
Output voltage 24 V DC (US - 1 V)
Maximum inrush current max. 1.5 A (for 20 ms)
Maximum output current per channel 500 mA
Maximum output current per module 2 A
Nominal output voltage 24 V DC (voltage difference at Inom ≤ 1 V)
Output voltage when switched off max. 2 V
Output current when switched off max. 300 µA
Nominal load, inductive 12 VA (1.2 H, 50 Ω)
Nominal load, lamp 12 W
Nominal load, ohmic 12 W (48 Ω)
Maximum operating frequency with ohmic nominal load max. 300 Hz (this switching frequency is limited by the data rate selected, the number of bus devices, the structure of the bus, the software used and the control or computer system used)
Reverse voltage resistance to short pulses Reverse voltage proof
Behavior with overload Auto restart
Behavior with inductive overload Output can be destroyed
Behavior at voltage switch-off The output follows the power supply without delay

Type modular
Inline
Scope of delivery including Inline connector and labeling field
No. of channels 4
Operating mode Process data operation with 4 bits
Diagnostics messages Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module

No. of channels 4
Potentials: Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current draw max. 44 mA
Potentials: Segment circuit supply (US)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 2 A

Connection technology
Connection name Inline connector
Conductor connection
Connection method Spring-cage connection
Conductor cross section solid 0.08 mm² ... 1.5 mm²
Conductor cross section flexible 0.08 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Stripping length 8 mm
Inline connector
Connection method Spring-cage connection
Conductor cross section, rigid 0.08 mm² ... 1.5 mm²
Conductor cross section, flexible 0.08 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 55 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail


Order Key 2701155
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CNI
Catalog Page Page 128 (C-6-2019)
GTIN 4046356713818
Weight per Piece (including packing) 93,4 GRM
Weight per Piece (excluding packing) 66,0 GRM
Customs tariff number 85389091
Country of origin DE



UL Recognized

cUL Recognized

cULus Recognized


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”


Your advantages

4 digital outputs
Connection of actuators in 2- and 3-conductor technology
Nominal current per output: 500 mA
Total current of the terminal: 2 A
Short-circuit and overload-protected outputs
Diagnostic and status indicators
Can be used under extreme ambient conditions
Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
Coated PCBs