I/O component - AXL F DO16/1 1H
2688349

Axioline F, Digital output module, Digital outputs: 16, 24 V DC, connection method: 1-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors


Product Details


The module is designed for use within an Axioline F station.It is used to output digital signals.The outputs are protected against short circuit and overload.



Dimensional drawing
Width 35 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Color traffic grey A RAL 7042

Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps

Module
ID code (hex) none

Digital
Output name Digital outputs
Connection method Push-in connection
Connection technology 1-conductor
Number of outputs 16
Protective circuit Short-circuit protection, overload protection of the outputs; electronic
Output voltage 24 V
Maximum output current per module 8 A (provide external protection)
Nominal output voltage 24 V DC
Output voltage when switched off max. 1 V
Output current when switched off max. 300 µA
Nominal load, inductive max. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, lamp max. 12 W (at nominal voltage)
Nominal load, ohmic max. 12 W (48 Ω, with nominal voltage)
Switching frequency max. 10000 per second (with at least 50 mA load current)
max. 1 per second (with inductive load)
max. 16 per second (with nominal lamp load)
Reverse voltage resistance to short pulses limited protection up to 0.5 A for 1 s
Behavior with overload Shutdown with automatic restart
Behavior with inductive overload Output can be destroyed

Type modular
Axioline
Mounting position any (no temperature derating)
Scope of delivery including bus base module and Axioline F connectors
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Maximum power dissipation for nominal condition 240 W
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 120 mA (up to HW 02)
max. 60 mA (as of HW 03)
Power consumption max. 600 mW (up to HW 02)
max. 300 mW (as of HW 03)
Potentials: Supply for digital output modules (UO)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 8 A (provide external protection)
Power consumption max. 240 W (of which 560 mW with internal losses)
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning)

Connection technology
Connection name Axioline F connector
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Applications with UL approval: only use copper conductors.
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Applications with UL approval: only use copper conductors.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail
Mounting position any (no temperature derating)


Order Key 2688349
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CNI
Catalog Page Page 76 (C-6-2019)
GTIN 4046356606530
Weight per Piece (including packing) 183,1 GRM
Weight per Piece (excluding packing) 134,0 GRM
Customs tariff number 85389091
Country of origin DE



NK

ABS

RINA

KR

LR

KR

NK

ABS

BSH

RINA

PRS

BV

EAC

EAC

DNV GL

UL Listed

cUL Listed

UL Listed

cUL Listed

DNV GL


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”


Your advantages

16 digital outputs
24 V DC, 500 mA
Connection of actuators in 1-conductor technology
Minimum update time of < 100 μs
Device rating plate stored