I/O component - AXL F DI32/1 1F
2688035

Axioline F, Digital input module, Digital inputs: 32, 24 V DC, connection method: 1-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors


Product Details


The module is designed for use within an Axioline F station.It is used to acquire digital signals.You can adjust the filter times of the inputs to increase noise immunity.Filter times of 100 μs enable you to implement a counter function with a maximum input frequency of 5 kHz in the application.



Dimensional drawing
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Color traffic grey A RAL 7042

Axioline F local bus
No. of channels 2
Connection method Bus base module
Transmission speed 100 Mbps

Digital
Input name Digital inputs
Description of the input EN 61131-2 types 1 and 3
Number of inputs 32
Connection method Push-in connection
Connection technology 1-conductor
Input voltage range "0" signal -3 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Nominal input voltage UIN 24 V DC
Nominal input current at UIN 2.4 mA
Input filter time 3000 µs (Default)
1000 µs
< 100 µs
Protective circuit Polarity reversal protection of the inputs; parallel diode (30 V, 5 s)

Type modular
Axioline
Mounting position any (no temperature derating)
Scope of delivery including bus base module and Axioline F connectors
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Maximum power dissipation for nominal condition 0.6 W
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 120 mA (up to HW 04)
max. 60 mA (as of HW 05)
Power consumption max. 600 mW (up to HW 04)
max. 300 mW (as of HW 05)
Potentials: Supply for digital input modules (UI)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 50 mA
Power consumption max. 1.2 W
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning)

Connection technology
Connection name Axioline F connector
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Applications with UL approval: only use copper conductors.
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Applications with UL approval: only use copper conductors.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail
Mounting position any (no temperature derating)


Order Key 2688035
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key 114
Catalog Page Page 75 (C-6-2019)
GTIN 4046356501590
Weight per Piece (including packing) 232,1 GRM
Weight per Piece (excluding packing) 232,1 GRM
Customs tariff number 85389091
Country of origin DE



PRS

BV

LR

KR

ABS

BSH

RINA

LR

ABS

PRS

BV

RINA

BSH

KR

EAC

EAC

DNV GL

UL Listed

cUL Listed

UL Listed

cUL Listed

DNV GL


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”


Your advantages

32 digital inputs according to EN 61131-2 type 1 and type 3
24 V DC, 2.4 mA
Connection of sensors in 1-conductor technology
Minimum update time of < 100 μs
Filter times can be adjusted in three increments: < 100 µs, 1000 µs or 3000 µs
Maximum input frequency: 5 kHz
Device rating plate stored