I/O component - AXL F AI2 AO2 1H
2702072

Axioline F, Analog I/O module, Analog inputs: 2, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection method: 2-conductor, Analog outputs: 2, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection method: 2-conductor, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors


Product Details


The module is designed for use within an Axioline F station.It is used to acquire and output analog voltage and current signals.



Dimensional drawing
Width 35 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).

Color traffic grey A RAL 7042

Axioline F local bus
No. of channels 2
Connection method Bus base module
Transmission speed 100 Mbps

Analog
Input name Analog inputs
Description of the input Differential inputs, voltage or current can be chosen separately
Number of inputs 2
A/D conversion time 2 µs
A/D converter resolution 16 bit
Connection method Push-in connection
Connection technology 2-conductor
Note regarding the connection technology shielded, twisted pair
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input 104 Ω (typical)
Voltage input signal 0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input 268 kΩ (typical)
Data formats IB IL, S7-compatible, standardized representation
Input filter 30 Hz, 12 kHz and mean-value generation (can be parameterized)
Limit frequency (3 dB) 30 Hz
12 kHz
Common mode voltage range signal - ground -50 V DC ... 50 V DC
Measured value representation 16 bits (15 bits + sign bit)
Protective circuit Transient protection of inputs; Suppressor diode
Overload protection of the current inputs; No; ±5.2 V DC, maximum, Imax = 50 mA
Overload protection of the voltage inputs; ±30 V DC, maximum

Analog
Output name Analog outputs
Connection method Push-in connection
Connection technology 2-conductor
Note regarding the connection technology shielded, twisted pair
Number of outputs 2
D/A converter resolution 16 bit
Protective circuit Short-circuit and overload protection; electronic
Transient protection; Suppressor diode
Data formats IB IL, S7-compatible, standardized representation
Representation of output values 16 bits (15 bits + sign)
Process data update 150 µs
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Load/output load current output ≤ 500 Ω
Voltage output signal 0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output ≥ 2 kΩ
Precision typ. 0.1 % (of output range final value)

Type modular
Axioline
Mounting position any (no temperature derating)
Scope of delivery including bus base module and Axioline F connectors

Potentials
Power consumption typ. 1.56 W (at UBus and UA)
max. 2.67 W (at UBus and UA)
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 150 mA
typ. 120 mA
Power consumption max. 0.75 W
typ. 0.6 W
Potentials: Supply for analog modules (UA)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 80 mA (2 current channels, 24 mA output, 500 Ω load)
typ. 40 mA
max. 60 mA (2 voltage channels, 10 V output, 2 kΩ load)
Power consumption max. 1.92 W
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode

Connection technology
Connection name Axioline F connector
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm

Ambient temperature (operation) -25 °C ... 60 °C
Degree of protection IP20
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)

Protection class III (IEC 61140, EN 61140, VDE 0140-1)

Mounting type DIN rail
Mounting position any (no temperature derating)


Order Key 2702072
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CNI
Catalog Page Page 84 (C-6-2019)
GTIN 4046356933124
Weight per Piece (including packing) 195,8 GRM
Weight per Piece (excluding packing) 195,8 GRM
Customs tariff number 85389091
Country of origin DE



KR

NK

ABS

BSH

RINA

LR

PRS

BV

DNV GL

UL Listed

cUL Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”


Your advantages

2 analog differential input channels
Connection of sensors in 2-conductor technology
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
2 analog outputs
Connection of actuators in 2-conductor technology
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
Process data update < 150 µs
Device rating plate stored