PTCB E1 24DC/4A NO
   - 
  Electronic circuit breaker
    
      2909906
      
      
    
  
      1-channel, electronic circuit breaker for protecting loads at 24 V DC against overload and short circuit. Easy potential distribution with components from the CLIPLINE complete terminal block system. With fixed nominal current. For installation on DIN rails.
Product details
| General | |
| Note | EN 50121-3-2: Railway applications - Electromagnetic compatibility - Part 3-2: Rolling stock – Apparatus | 
| Connection for signal line tested in accordance with EN 61000-4-4 with 1 kV; if necessary, customer must provide appropriate protective measures | |
| Repeated hard short circuits can reduce the melting integral of the integrated backup fuse. | |
| Product type | Device circuit breakers | 
| Product family | PTCB | 
| Type | DIN rail module, one-piece | 
| Number of positions | 1 | 
| No. of channels | 1 | 
| Insulation characteristics | |
| Protection class | III | 
| Pollution degree | 2 | 
| General | |
| Operating voltage | 18 V DC ... 30 V DC | 
| Rated voltage | 24 V DC | 
| Rated current IN | 24 A DC (Total current input) | 
| 4 A DC (Rated current output) | |
| Rated current (pre-adjusted) | 4 A | 
| Rated surge voltage | 0.5 kV | 
| Tripping method | E (electronic) | 
| Feedback resistance | max. 35 V DC | 
| Required backup fuse | Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. | 
| Short-circuit switching capacity | 300 A | 
| Dielectric strength | max. 35 V DC (Load circuit) | 
| Fuse | electronic | 
| Efficiency | > 99 % | 
| Closed circuit current I0 | typ. 12 mA | 
| Power dissipation | typ. 0.3 W (No-load operation) | 
| < 1.3 W (Nominal operation) | |
| Module initialization time | < 0.55 s | 
| Waiting time after switch off of a channel | 5 s (at overload / short circuit) | 
| Measuring tolerance I | ± 15 % | 
| Temperature derating | 21 A (Total current at 60°C) | 
| 24 A (Total current at 50°C) | |
| 4 A (Channel current at 60°C) | |
| 4 A (Channel current at 50°C) | |
| MTBF (IEC 61709, SN 29500) | 28571428 h (at 25 °C with 21 % load) | 
| 14084507 h (at 40°C with 34.25% load) | |
| 2053388 h (at 60°C with 100% load) | |
| Voltage drop | 0.12 V (at 4 A) | 
| Fail-safe element | 4 A DC | 
| Contact switching type | without electrical isolation | 
| Load circuit | |
| Shutdown time | ≤ 10 ms (for short circuit > 2.0 x IN) | 
| 1 s (1.2 ... 2.0 x IN) | |
| Undervoltage switch-off | ≤ 17.8 V DC (active) | 
| ≥ 18.8 V DC (inactive) | |
| Overvoltage switch-off | ≥ 30.5 V DC (active) | 
| ≤ 29.5 V DC (inactive) | |
| Max. capacitive load | 15000 µF (Depending on the available short-circuit current) | 
| Indicator/remote signaling | |
| Connection name | Remote indication circuit | 
| Switching function | N/O contact | 
| Operating voltage | 0 V DC ... 30 V DC | 
| Operating current | 100 mA DC | 
| Main circuit IN+ | |
| Connection method | Push-in connection | 
| Stripping length | 8 mm | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section rigid | 0.2 mm² ... 4 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Main circuit IN- | |
| Connection method | Push-in connection | 
| Stripping length | 8 mm | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section rigid | 0.2 mm² ... 4 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Main circuit OUT | |
| Connection method | Push-in connection | 
| Stripping length | 8 mm | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section rigid | 0.2 mm² ... 4 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Remote indication circuit | |
| Connection method | Push-in connection | 
| Stripping length | 8 mm | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section rigid | 0.2 mm² ... 4 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² | 
| Channel LED off | off (Channel switched off) | 
| Channel LED yellow | lit (Channel switched on, channel load > 80% ) | 
| flashing (Programming mode active) | |
| Channel LED green | lit (Channel switched on) | 
| Channel LED red | lit (Channel switched off, over- or undervoltage active) | 
| ON temporarily (Channel switched off, 5 s cool-down phase, overload or short-circuit release) | |
| flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) | |
| flashing quickly (Channel switched off, external voltage at the output, possible installation error) | 
| Dimensional drawing | 
                 | 
            
| Width | 6.2 mm | 
| Height | 105.8 mm | 
| Depth | 55.6 mm (incl. DIN rail 7.5 mm) | 
| Color | gray (RAL 7042) | 
| Material | PBT | 
| PBT | |
| Flammability rating according to UL 94 | V-0 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -30 °C ... 60 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 70 °C | 
| Altitude | ≤ 3000 m up to 52 °C (amsl) | 
| ≤ 4000 m up to 46 °C (amsl) | |
| Humidity test | 96 h, 95 % RH, 40 °C | 
| Shock (operation) | 30g (IEC 60068-2-27, Test Ea) | 
| Vibration (operation) | 10 Hz ... 59.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) | 
| 59.6 Hz ... 150 Hz (Acceleration 5g; in accordance with IEC 60068-2-6, Test Fc) | |
| 5 Hz ... 100 Hz (Resonance search 4g; resonance frequency 4g; 90 min in accordance with DNV GL Class B) | |
| UL approval | |
| Identification | UL/C-UL Listed UL 508 | 
| UL Recognized UL 2367 | |
| UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D; T4 (Hazardous Location) | |
| Shipbuilding approval | |
| Identification | DNV GL | 
| Corrosive gas test | |
| Identification | ISA S71.04.2013 G3 Harsh Group A | 
| Shipbuilding data | |
| Temperature | D | 
| Humidity | B | 
| Vibration | B | 
| EMC | B | 
| Enclosure | A | 
| Standards/specifications | EN 61000-6-2 | 
| Note | EMC – Immunity for industrial areas | 
| Standards/specifications | EN 61000-6-3 | 
| Note | EMC – Emission for residential, business and commercial properties and small operations | 
| Standards/specifications | EN 60068-2-78 | 
| Note | Environmental influences – Moisture and heat, constant | 
| Standards/specifications | EN 50178 | 
| Note | Equipping power installations with electronic equipment | 
| Standards/specifications | EN 60068-2-6 | 
| Note | Environmental influences – Vibrations (sinusoidal) | 
| Standards/specifications | EN 60068-2-27 | 
| Note | Environmental influences – Shocks | 
| Standards/specifications | EN 60068-2-30 | 
| Note | Environmental influences – Part 2–30: Tests – Test Db: Damp heat, cyclical | 
| Standards/specifications | EN 61373 | 
| Note | Railway applications - Rolling stock equipment - Shock and vibration tests | 
| Standards/specifications | EN 45545-2 | 
| Note | Railway applications - Fire protection on railway vehicles - Part 2: Requirements for fire behavior of materials and components | 
| Mounting type | DIN rail: 35 mm | 
| Item number | 2909906 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | CLA | 
| Product key | CLA135 | 
| GTIN | 4055626408736 | 
| Weight per piece (including packing) | 34,7 g | 
| Weight per piece (excluding packing) | 27,58 g | 
| Customs tariff number | 85363010 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27140401 | 
| ECLASS-15.0 | 27140401 | 
ETIM
| ETIM 9.0 | EC003538 | 
UNSPSC
| UNSPSC 21.0 | 39121400 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | 
              EFUP-50
               An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. 
             | 
          
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | 639a383c-d359-4216-a326-e11fde3e4bbf | 
| EF3.0 Climate Change | |
| CO2e kg | 1,06 kg CO2e | 
Compatible products
            Note: Applying some accessories below might limit this product.
          
          
        - 
    
      
FBS 2-6 - Plug-in bridge 3030336
 - 
    
      
FBS 3-6 - Plug-in bridge 3030242
 - 
    
      
FBS 4-6 - Plug-in bridge 3030255
 - 
    
      
FBS 5-6 - Plug-in bridge 3030349
 - 
    
      
FBS 10-6 - Plug-in bridge 3030271
 - 
    
      
FBS 20-6 - Plug-in bridge 3030365
 - 
    
      
FBS 50-6 - Plug-in bridge 3032224
 - 
    
      
FBS 2-6 BU - Plug-in bridge 3036932
 - 
    
      
FBS 3-6 BU - Plug-in bridge 3036945
 - 
    
      
FBS 4-6 BU - Plug-in bridge 3036958
 - 
    
      
FBS 5-6 BU - Plug-in bridge 3036961
 - 
    
      
FBS 10-6 BU - Plug-in bridge 3032198
 - 
    
      
FBS 20-6 BU - Plug-in bridge 3032208
 - 
    
      
FBS 50-6 BU - Plug-in bridge 3032211
 - 
    
      
FBS 2-6 GY - Plug-in bridge 3032237
 - 
    
      
FBS 3-6 GY - Plug-in bridge 3032240
 - 
    
      
FBS 4-6 GY - Plug-in bridge 3032279
 - 
    
      
FBS 5-6 GY - Plug-in bridge 3032266
 - 
    
      
FBS 2-5 - Plug-in bridge 3030161
 - 
    
      
FBS 3-5 - Plug-in bridge 3030174
 - 
    
      
FBS 4-5 - Plug-in bridge 3030187
 - 
    
      
FBS 5-5 - Plug-in bridge 3030190
 - 
    
      
FBS 10-5 - Plug-in bridge 3030213
 - 
    
      
FBS 20-5 - Plug-in bridge 3030226
 - 
    
      
FBS 50-5 - Plug-in bridge 3038930
 - 
    
      
FBS 2-5 BU - Plug-in bridge 3036877
 - 
    
      
FBS 3-5 BU - Plug-in bridge 3036880
 - 
    
      
FBS 4-5 BU - Plug-in bridge 3036893
 - 
    
      
FBS 5-5 BU - Plug-in bridge 3036903
 - 
    
      
FBS 10-5 BU - Plug-in bridge 3036916
 - 
    
      
FBS 20-5 BU - Plug-in bridge 3036929
 - 
    
      
FBS 50-5 BU - Plug-in bridge 3032114
 - 
    
      
FBS 2-5 GY - Plug-in bridge 3038969
 - 
    
      
FBS 3-5 GY - Plug-in bridge 3038972
 - 
    
      
FBS 4-5 GY - Plug-in bridge 3038985
 - 
    
      
FBS 5-5 GY - Plug-in bridge 3038998
 - 
    
      
RB ST 10-(2,5/4) - Reducing bridge 3030873
 - 
    
      
PT 4 - Feed-through terminal block 3211757
 - 
    
      
PT 4-TWIN - Feed-through terminal block 3211771
 - 
    
      
PT 4-QUATTRO - Feed-through terminal block 3211797
 - 
    
      
ST 4 - Feed-through terminal block 3031364
 - 
    
      
ST 4-TWIN - Feed-through terminal block 3031393
 - 
    
      
ST 4-QUATTRO - Feed-through terminal block 3031445
 - 
    
      
QTC 2,5 - Feed-through terminal block 3206416
 - 
    
      
QTC 2,5-TWIN - Feed-through terminal block 3206445
 - 
    
      
QTC 2,5-QUATTRO - Feed-through terminal block 3206446
 - 
    
      
PT 2,5 - Feed-through terminal block 3209510
 - 
    
      
PT 2,5-TWIN - Feed-through terminal block 3209549
 - 
    
      
PT 2,5-QUATTRO - Feed-through terminal block 3209578
 - 
    
      
ST 2,5 - Feed-through terminal block 3031212
 - 
    
      
ST 2,5-TWIN - Feed-through terminal block 3031241
 - 
    
      
ST 2,5-QUATTRO - Feed-through terminal block 3031306
 - 
    
      
QTC 1,5 - Feed-through terminal block 3205019
 - 
    
      
QTC 1,5-TWIN - Feed-through terminal block 3205048
 - 
    
      
QTC 1,5-QUATTRO - Feed-through terminal block 3205077
 - 
    
      
PT 10 - Feed-through terminal block 3212120
 - 
    
      
ST 10 - Feed-through terminal block 3036110
 - 
    
      
ZB 6:UNBEDRUCKT - Zack marker strip 1051003
 - 
    
      
ZBF 6:UNBEDRUCKT - Zack Marker strip, flat 0808710
 - 
    
      
UCT-TM 6 - Marker for terminal blocks 0828736
 - 
    
      
UCT-TM 6 CUS - Marker for terminal blocks 0829602
 - 
    
      
US-TML (104X3,8) - Marker for terminal blocks 0830768
 - 
    
      
TTC-6P-T3-24DC-PT-I - Type 3 surge protection device 1027586
 - 
    
      
DB 50- 90 BK - Wire bridge 2820916
 - 
    
      
DB 50- 90 BU - Wire bridge 2821180
 - 
    
      
DB 50- 90 GY - Wire bridge 2820929
 - 
    
      
DB 50- 90 RD - Wire bridge 2864639
 
Your advantages
Simple application setup due to bridging option to CLIPLINE complete terminal block system
        More space in the control cabinet: narrowest protection on just 6 mm width
        Individual setup for suitable protection, exactly according to your requirements
        PHOENIX CONTACT (Pty) Ltd.
        
        36 Lyn Road P.O. Box 916 ZA-Ferndale 2160