UPS modules with integrated energy storage are particularly space saving: UPS module and energy storage are combined in one housing. It's just a case of connecting a power supply upstream.
UNO-UPS/24DC/24DC/60W
-
Uninterruptible power supply
2905907
Uninterruptible energy supply with integrated energy storage, lead AGM, VRLA technology, 24 V DC, 0.8 Ah.
Product details
DC operation | |
Input voltage | 24 V DC |
Input voltage range | 22.5 V DC ... 29.5 V DC |
Voltage type of supply voltage | DC |
Buffer period | 45 min. (0.5 A) |
20 min. (1 A) | |
8 min. (2 A) | |
5 min. (2.5 A) | |
Current consumption | 2.8 A (max.) |
< 60 mA | |
< 300 mA | |
Input fuse | 5 A (electronic) |
Efficiency | > 95 % (Mains operation, with charged energy storage) |
> 92 % (Battery operation) | |
Nominal output voltage | 24 V DC |
Nominal output current (IN) | 2.5 A |
Bridging time | 300 s |
Output power | 60 W |
Power dissipation | 3 W (Mains operation) |
6 W (Battery operation) | |
Battery operation | |
Connection in series | No |
Mains operation | |
Nominal output voltage | 24 V DC |
Output voltage range | UOut = UIn - 0.5 V DC |
Nominal output current (IN) | 2.5 A |
Battery operation | |
Nominal output voltage | 24 V DC |
Output voltage range | 20 V DC ... 27.3 V DC |
Nominal output current (IN) | 2.5 A |
Signal: Alarm | |
Output description | Transistor (24 V DC/15 mA) |
Signal: Battery mode | |
Output description | Transistor (24 V DC/15 mA) |
Charging current | 200 mA |
Nominal capacity | 2x 0.8 Ah |
Charging time | approx. 5 h |
Battery module service life | 3 Years ... 5 Years (20 °C) |
Latest startup date (battery only) | 3 Months (0 °C ... 20 °C) |
1 Months (30 °C ... 40 °C) | |
Latest startup (battery only) - range | 3 Months ... 1 Months (20 °C ... 30 °C) |
Battery technology | VRLA-AGM |
Memory medium | Lead rechargeable battery module |
Accumulator type | YUASA NP0.8-12 |
YUCEL Y0.8-12 | |
YUVOLT 0.8-12 | |
Battery presence check (cyclic) | 60 s |
Battery fuse | T 5 A 32 V |
IQ technology | no |
Input | |
Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output | |
Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal | |
Connection method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Types of signaling | LED |
Signal output | |
Signalization designation | Power In OK |
Status display | LED |
Note on status display | Static to |
Signal output: Switching output | |
Signalization designation | Alarm |
Status display | LED |
Note on status display | Static to |
Signal output | |
Status display | LED |
Note on status display | flashing |
Signal output: Switching output | |
Signalization designation | Battery mode |
Status display | LED |
Note on status display | flashing |
Signal output | |
Signalization designation | Service |
Status display | LED |
Note on status display | flashing |
Product type | DC UPS with integrated energy storage |
Product family | UNO UPS ‒ UPS with integrated energy storage |
IQ technology | no |
MTBF (IEC 61709, SN 29500) | > 1900000 h (40 °C) |
Insulation characteristics | |
Protection class | III |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors) | |
Time | 170312 h |
Width | 110 mm |
Height | 90 mm |
Depth | 84 mm |
Installation dimensions | |
Installation distance right/left | 0 mm / 0 mm (≤ 70 °C) |
Installation distance top/bottom | 30 mm / 30 mm (≤ 70 °C) |
Mounting type | DIN rail: 35 mm |
Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Housing material | Plastic |
Type of housing | Plastic |
Foot latch material | POM (Polyoxymethylene) |
Housing material | PC+ABS |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -15 °C ... 50 °C |
Ambient temperature (storage/transport) | -20 °C ... 60 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 13.2 Hz, amplitude ±1.0 mm (according to IEC 60068-2-6) |
13.2 Hz ... 100 Hz, 0.7g |
Standard - Electrical safety | IEC 62368-1 (SELV) |
UL approvals | UL Listed UL 508 |
UL/C-UL Recognized UL 60950-1 |
EMC requirements for noise emission | EN 61000-6-3 |
EN 61000-6-4 | |
EMC requirements for noise immunity | EN 61000-6-1 |
EN 61000-6-2 | |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 8 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 3 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Output | 1 kV (Test Level 3 - symmetrical) |
2 kV (Test Level 3 - asymmetrical) | |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion A |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Emitted interference | |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria | |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Item number | 2905907 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | CM27 |
Product key | CMUUV3 |
Catalog page | Page 349 (C-4-2019) |
GTIN | 4055626007380 |
Weight per piece (including packing) | 1,182 g |
Weight per piece (excluding packing) | 1,182 g |
Customs tariff number | 85371091 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27040705 |
ECLASS-13.0 | 27040705 |
ECLASS-12.0 | 27040705 |
ETIM
ETIM 9.0 | EC000382 |
UNSPSC
UNSPSC 21.0 | 39121000 |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 25; |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
Your advantages
Compact and narrow