PLT-EE-T3-60AC-P
   - 
  Type 3 surge protection plug
    
      1249055
      
      
    
  
      Replacement plug for type 3 surge protection from the PLT-EE product range. 60 V nominal voltage
Product details
| Product type | Replacement plug | 
| IEC power supply system | TN-S | 
| Type | Male | 
| Number of positions | 2 | 
| Surge protection fault message | optical | 
| Insulation characteristics | |
| Overvoltage category | III | 
| Pollution degree | 2 | 
| IEC test classification | III | 
| T3 | |
| EN type | T3 | 
| Number of ports | One | 
| Connection method | pluggable | 
| Dimensional drawing | 
                 | 
            
| Width | 17.7 mm | 
| Height | 46.8 mm | 
| Depth | 62.7 mm | 
| Horizontal pitch | 1 Div. | 
| Color | traffic grey B (RAL 7043) | 
| traffic grey B (RAL 7043) | |
| Flammability rating according to UL 94 | V-0 | 
| CTI value of material | 600 | 
| Insulating material | PA 6.6-FR 20 % GF | 
| PA 6.6-FR | |
| Housing material | PA 6.6-FR 20 % GF | 
| PA 6.6-FR | 
| Mode of protection | L-N | 
| L-PE | |
| N-PE | |
| Nominal voltage UN | 60 V AC (TN-S) | 
| Nominal frequency fN | 50 Hz (60 Hz) | 
| Maximum continuous operating voltage UC | 80 V AC | 
| Protective conductor current IPE | ≤ 5 µA | 
| Standby power consumption PC | ≤ 5.3 mVA (at UREF) | 
| ≤ 8.4 mVA (at UC) | |
| Reference test voltage UREF | 66 V AC | 
| Nominal discharge current In (8/20) µs | 2 kA | 
| Combination wave UOC | 4 kV | 
| Voltage protection level Up (L-N) | ≤ 0.48 kV | 
| Voltage protection level Up (L-PE) | ≤ 0.8 kV | 
| Voltage protection level Up (N-PE) | ≤ 0.8 kV | 
| TOV behavior at UT (L-N) | 120 V AC (120 min / withstand mode) | 
| TOV behavior at UT (L-PE) | 120 V AC (120 min / withstand mode) | 
| Response time tA (L-N) | ≤ 25 ns | 
| Response time tA (L-PE) | ≤ 100 ns | 
| Response time tA (N-PE) | ≤ 100 ns | 
| Short-circuit current rating ISCCR | 6 kA AC | 
| Max. backup fuse with branch wiring | 16 A (gG / B / C) | 
| Additional technical data | |
| Residual voltage Ures (L-N) | ≤ 0.42 kV (at 1 kA) | 
| ≤ 0.48 kV (at 2 kA) | |
| ≤ 0.4 kV (at UOC = 2 kV) | |
| Residual voltage Ures (L-PE) | ≤ 0.55 kV (at 1 kA) | 
| ≤ 0.6 kV (at 2 kA) | |
| ≤ 0.6 kV (at UOC = 2 kV) | |
| Residual voltage Ures (N-PE) | ≤ 0.55 kV (at 1 kA) | 
| ≤ 0.6 kV (at 2 kA) | |
| ≤ 0.6 kV (at UOC = 2 kV) | |
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -40 °C ... 80 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Altitude | ≤ 2000 m (operating voltage remote contact ≤ 250 V) | 
| ≤ 6000 m (operating voltage remote contact ≤ 150 V) | |
| Permissible humidity (operation) | 5 % ... 95 % | 
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) | 
| Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) | 
| Standards/specifications | IEC 61643-11 | 
| Note | 2011 | 
| EN 61643-11 | |
| Standards/specifications | EN 61643-11 | 
| Note | 2012 | 
| Mounting type | on base element | 
| Item number | 1249055 | 
| Packing unit | 10 pc | 
| Minimum order quantity | 1 pc | 
| Product key | CLP312 | 
| GTIN | 4063151351199 | 
| Weight per piece (including packing) | 36 g | 
| Weight per piece (excluding packing) | 33 g | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27171292 | 
| ECLASS-15.0 | 27171292 | 
ETIM
| ETIM 9.0 | EC002496 | 
UNSPSC
| UNSPSC 21.0 | 39121600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes (No exemptions) | 
| China RoHS | |
| Environment friendly use period (EFUP) | 
              EFUP-E
               No hazardous substances above the limits 
             | 
          
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products