CB TM1 5A M1 P - Thermomagnetic device circuit breaker
2800851

Thermomagnetic device circuit breaker, 1-pos., tripping characteristic M1 (medium-blow), 1 changeover contact, plug for base element.

This product needs further products for operation. Mandatory Accessories

Product Details




General When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly.

Type Male
Product type Thermomagnetic device circuit breakers
Product family CB TM
Number of positions 1
No. of channels 1
Insulation characteristics
Degree of pollution 2

No. of channels 1
Fuse type Automatic device
General
Rated voltage 50 V DC (IEC 60934)
50 V DC (UL 1077)
50 V DC (UL 508 - with plug-in base)
240 V AC (Ue according to IEC 60934)
277 V AC (UL 1077)
277 V AC (UL 508 - with plug-in base)
Rated insulation voltage Ui 277 V AC (UL 1077)
250 V AC (IEC 60934)
Rated current IN 5 A (IEC 60934)
5 A AC (inductive load according to UL 1077)
5 A DC (low-induction load according to UL 1077)
5 A AC (inductive load according to UL 508 - with plug-in base)
5 A DC (low-induction load according to UL 508 - with plug-in base)
Rated surge voltage 2.5 kV (Increased insulation in actuation area)
Insulation resistance Riso > 100 MΩ (500 V DC)
Auxiliary circuit 277 V AC / 0.5 A (Low-induction)
277 V AC / 1 A (Low-induction, maximum of 2000 cycles)
50 V DC / 1 A (Low-induction)
Type of actuation S type
Tripping method TM (thermomagnetic)
Tripping level Trip-free mechanism (positive)
Device resistance 60 mΩ
Required backup fuse 20 A (I > Icn)
Rated short-circuit switching capacity Icn 300 A (240 V AC)
600 A (50 V DC)
Short-circuit switching capacity 1000 A AC (277 V AC)
1000 A DC (50 V DC)
Dielectric strength 3000 V AC (Actuation area)
1500 V AC (Main to auxiliary circuit)
1500 V AC (Open main circuit)
1000 V AC (Open auxiliary circuit)
Switching cycles, max. 6000 (at 1 x In)
Fuse M1 (normal blow)
Power dissipation 1.5 W (in nominal operation per channel)
Voltage drop 0.31 V (at 1 x In)
Auxiliary contact
Minimum operating voltage Umin DC 10 V
Maximum operating voltage Umax DC 240 V
Maximum operating voltage Umax. AC 240 V
Minimum operating current Imin 10 mA
Max. operating current Imax 1 A

Connection method pluggable

Dimensional drawing
Width 12.3 mm
Height 45 mm
Depth 52 mm
Complete module width 12.3 mm
Complete module height 90 mm
Complete module depth 77.3 mm

Color gray
Flammability rating according to UL 94 V-0
Insulating material group II

Mechanical data
Open side panel No

Ambient conditions
Degree of protection IP30 (Actuation area)
Ambient temperature (operation) -30 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Humidity test 240 h, 95 % RH, 40 °C
Shock (operation) 30g (According to IEC 60068-2-27, Test Ea)
Vibration (operation) 8g (in accordance with IEC 60068-2-6, Test Fc)

UL approval
Identification UL Listed UL 508
UL/C-UL Recognized UL 1077
CSA
Identification CSA CAN/CSA-C22.2 No. 235-04
Shipbuilding approval
Identification DNV GL

Standards/specifications EN 60934

Mounting type on base element

Item number 2800851
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C09
Product Key CLA124
Catalog Page Page 392 (C-4-2019)
GTIN 4046356690027
Weight per Piece (including packing) 44.8 g
Weight per Piece (excluding packing) 44.8 g
Customs tariff number 85362010
Country of origin ID


ECLASS

ECLASS-9.0 27141116
ECLASS-10.0.1 27140401
ECLASS-11.0 27140401
ECLASS-12.0 27140401

ETIM

ETIM 8.0 EC003538

UNSPSC

UNSPSC 21.0 39121400

cUL Recognized

Approval ID: FILE E 140459

UL Recognized

Approval ID: FILE E 140459

EAC

Approval ID: RU C-DE.*09.B.00169

DNV GL

Approval ID: TAE00003C7

VDE Zeichengenehmigung

Approval ID: 40034683

UL Listed

Approval ID: FILE E 172140

CCC

Approval ID: 2019010307158887

CSA

Approval ID: 2786957

cUL Listed

Approval ID: FILE E 172140

KC

Approval ID: SW05012-15001A

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products




Your advantages

Individually adjustable with protective plugs
Switch higher starting currents with the aid of the M1 characteristic curve
Protective plug with fixed nominal current value as protection against unintentional changes
Increased safety with electrical isolation in the event of errors