Temperature measuring transducer - MACX MCR-T-UIREL-UP
2811378

Freely programmable temperature transducer with analog output and 3 limit value relays, standard configuration, resistance thermometer in 2-, 3-, or 4-conductor technology, thermocouples, electrical isolation, wide-range power supply, screw connection, SIL, PL.

Downloads

Product Details




Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Temperature transmitter
Type Signal conditioners with SIL and PL Functional Safety
Configuration DIP switches
Software
Insulation characteristics
Overvoltage category II
Pollution degree 2

Electrical isolation 4-way isolation
Step response (0–99%) ≤ 1.75 s (SIL on)
1.3 s (SIL off)
Maximum temperature coefficient 0.01 %/K
Maximum transmission error 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA)
Electrical isolation Input/output/power supply
Rated insulation voltage 300 Vrms
Test voltage 2.5 kV AC (50 Hz, 60 s)
Insulation Safe isolation in accordance with IEC/EN 61010-1
Electrical isolation Input/output
Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
Electrical isolation Input/power supply
Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
Electrical isolation Input/switching output
Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
Supply
Supply voltage range 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Power consumption < 2.4 W

Signal
Number of inputs 1
Input signal Temperature
Resistor
Voltage
Measurement
Sensor types (RTD) that can be used Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range -250 °C ... 2500 °C (Range depending on the sensor type)
Linear resistance measuring range 0 Ω ... 50 kΩ
Potentiometer resistance range 0 Ω ... 50 kΩ
Linear mV signal range -1000 mV ... 1000 mV

Switching: Relay
Configurable/programmable Yes
Contact type 3 changeover contacts
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 250 V AC (250 V DC)
Max. switching current 2 A (250 V AC)
2 A (28 V DC)
Signal: Current
Number of outputs 1
Configurable/programmable Yes
Max. voltage output signal ± 11 V
Current output signal 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL)
Max. current output signal 22 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output ≤ 600 Ω (20 mA)
Behavior in the event of a sensor error according to NE 43 or freely configurable

Connection method Screw connection
Stripping length 7 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14

Width 35 mm
Height 112.5 mm
Depth 113.7 mm
114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Flammability rating according to UL 94 V0 (Housing)
Housing material PA 6.6-FR

Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m
Permissible humidity (operation) typ. 5 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
CE
Identification  II 3 G Ex nA nC ic IIC T4 Gc X
Certificate IBExU 10 ATEX B001 X
CE
Identification  II 3 G Ex nA nC ic IIC T4 Gc X
Certificate PxCIF21UKEX2811394X
CE
Identification Ex nA nC ic IIC T4 Gc X
Certificate IECEx IBE 10.0011 X
CE
Identification UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
CE
Certificate DNV GL TAA000020C
CE
Identification 2
CE
Identification d
CE
Identification  2Ex ec ic IIC T4 Gc
Certificate BY/112 02.01 TP012 103.01 00078
DNV GL data
Temperature B
Humidity B
Vibration A
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.

Electrical isolation 4-way isolation

Mounting type DIN rail mounting

Item number 2811378
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C01
Product Key CK1121
Catalog Page Page 126 (C-5-2019)
GTIN 4046356288903
Weight per Piece (including packing) 351.6 g
Weight per Piece (excluding packing) 351.6 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210129
ECLASS-10.0.1 27210129
ECLASS-11.0 27210129

ETIM

ETIM 8.0 EC002919

UNSPSC

UNSPSC 21.0 41112100

DNV GL

Approval ID: TAA000020C

UL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 238705

Functional Safety

Approval ID: SEBS-A.150520/17 V1

Functional Safety

Approval ID: 09/11-04 R013 V1R0

Functional Safety

Approval ID: 100134C P0019 C001

IECEx

Approval ID: IECEx IBE 10.0011X

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

ATEX

Approval ID: IBExU 10 ATEX B001 X

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Cold junction compensation with separate plug
Configuration via software (FDT/DTM) or IFS-OP-UNIT operator interface and display unit
Up to SIL 2 according to EN 61508
Installation in zone 2, protection type "n" (EN 60079-15) permitted
Programming during operation and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
Plug-in screw or spring-cage connection technology (Push-in technology)
Freely programmable input and output
Input for resistance thermometers, thermocouples, resistance-type sensors, potentiometers, and mV sources
Measure differential temperatures
Three limit value relays, can be used in combination as a safe limit value relay
Inverse output signal ranges as an option