MACX MCR-EX-RTD-I-C
-
Temperature measuring transducer
1052463
Ex i temperature transducer: converts signals from resistance temperature detectors installed in the Ex area and transmits a 0/4 - 20 mA signal to a load in the safe area. Freely programmable. 3-way isolation, SIL, screw connection, order configuration.
Free download available.
Downloads
Product details
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product type | Temperature transmitter |
Product family | MACX Analog |
Application | Temperature |
No. of channels | 1 |
Type | Ex i signal conditioners with SIL functional safety |
Configuration | Software |
Insulation characteristics: GB Standard | |
Overvoltage category | II |
Pollution degree | 2 |
Alignment span | ± 5 % |
Alignment zero | ± 5 % |
No. of channels | 1 |
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Step response (0–99%) | 1 s |
≤ 1.7 s | |
Temperature coefficient, typical | 0.01 %/K |
Transmission error, typical | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) |
Electrical isolation Input/output/power supply | |
Rated insulation voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Input/output | |
Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Electrical isolation Input/power supply | |
Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
Power dissipation | ≤ 0.76 W |
Power consumption | ≤ 1 W |
Signal | |
Number of inputs | 1 |
Measurement | |
Description of the input | Intrinsically safe |
Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
Temperature measuring range | -200 °C ... 850 °C (Range depending on the sensor type) |
Linear resistance measuring range | 0 Ω ... 50 kΩ |
Potentiometer resistance range | 0 Ω ... 50 kΩ |
Max. permissible overall conductor resistance | 50 Ω (Per cable) |
Sensor input current | 10 µA ... 210 µA (Up to 2x 210 µA with 3-conductor technology) |
Temperature measuring range | ≥ 50 K |
Signal: Current | |
Number of outputs | 1 |
Configurable/programmable | Yes |
Current output signal | 0 mA ... 20 mA |
4 mA ... 20 mA (SIL) | |
Max. current output signal | ≥ 21 mA |
Load/output load current output | ≤ 600 Ω |
Output ripple (current) | < 15 µAPP |
< 10 µArms | |
Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Connection method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Ex installation (EPL) | Gc |
Div. 2 | |
Ex i circuits (EPL) | Ga |
Da | |
Ma | |
Div. 1 | |
Safety data: Terminals: 4.1, 4.2, 5.1, 5.2 | |
Max. internal capacitance Ci | 44 nF |
Max. output voltage Uo | 6 V |
Max. output current Io | 16.6 mA (RTD in 4-conductor technology) |
13 mA (RTD in 3-conductor technology) | |
7.1 mA (RTD in 2-conductor technology) | |
16.6 mA (2x RTD in 2-conductor technology) | |
13 mA (Potentiometer) | |
Max. output power Po | 25.2 mW (Linear) |
Safety-related maximum voltage Um | 253 V AC |
125 V DC | |
30 V DC (Zone 2: 3.1, 3.2) | |
IIA/I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 850 mH / 1000 µF |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 460 mH / 1000 µF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 40 µF |
IIB/IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 950 nF, 50 mH / 950 nF, 5 mH / 950 nF, 1 mH / 950 nF |
IIIC/I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 950 nF, 50 mH / 950 nF, 5 mH / 950 nF, 1 mH / 950 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 555 nF, 50 mH / 555 nF, 5 mH / 555 nF, 1 mH / 555 nF, 10 µH / 555 nF |
Safety data: μUSB interface | |
Input voltage Ui | 7 V |
Input current Ii | 100 mA |
Input power Pi | 550 mW |
Max. internal capacitance Ci | 47 µF |
Max. output voltage Uo | 3.5 V |
Max. output current Io | 400 mA |
Max. output power Po | 350 mW |
IIC: Max. external inductivity Lo / Max. external capacitance Co | 20 µH / 2 µF |
Status display | Green LED (supply voltage) |
Red LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR) | |
Red LED, flashing 1.2 Hz (service operation, ERR) | |
Red LED, permanently on (module error, ERR) |
Dimensional drawing |
|
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing material | PA 6.6-FR |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 70 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m) | |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient temperature (operation) | -40 °C ... 70 °C |
Test voltage | 2.5 kV |
Rated insulation voltage | 300 Vrms (IEC/EN 60079-11) |
375 VPP (IEC/EN 60079-11) | |
Altitude range (≤ 3000 m) | |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -40 °C ... 60 °C |
Test voltage | 2.25 kV |
Safety-related maximum voltage Um | 190 V AC |
110 V DC | |
Rated insulation voltage | 190 Vrms (IEC/EN 60079-11) |
Altitude range (≤ 4000 m) | |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -40 °C ... 55 °C |
Test voltage | 2 kV |
Safety-related maximum voltage Um | 60 V AC/DC |
Rated insulation voltage | 60 Vrms (IEC/EN 60079-11) |
Altitude range (≤ 5000 m) | |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -40 °C ... 49 °C |
Test voltage | 1.75 kV |
Safety-related maximum voltage Um | 60 V AC/DC |
Rated insulation voltage | 60 Vrms (IEC/EN 60079-11) |
CE | |
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX | |
Identification | I (M1) [Ex ia Ma] I |
II (1) G [Ex ia Ga] IIC | |
II (1) D [Ex ia Da] IIIC | |
II 3(1) G Ex ec ic [ia Ga] IIC T4 Gc | |
Certificate | IBExU19ATEX1006 X |
UKCA Ex (UKEX) | |
Identification | I (M1) [Ex ia Ma] I |
II (1) G [Ex ia Ga] IIC | |
II (1) D [Ex ia Da] IIIC | |
II 3 (1) G Ex ec ic [ia Ga] IIC T4 Gc | |
Certificate | CML 22UKEX3531X |
IECEx | |
Identification | [Ex ia Ma] I |
[Ex ia Ga] IIC | |
[Ex ia Da] IIIC | |
Ex ec ic [ia Ga] IIC T4 Gc | |
Certificate | IECEx IBE 19.0001 X |
CCC / China-Ex | |
Identification | [Ex ia Ga] IIC |
[Ex iaD] | |
Ex nA ic [ia Ga] IIC T4 Gc | |
Certificate | NEPSI GYJ20.1305X |
UL, USA/Canada | |
Identification | UL 61010 Listed |
Class I Div 2; IS for Class I, II, III Div 1 | |
Certificate | , C.D.-No 83104549 |
Shipbuilding approval | |
Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | 2 |
INMETRO | |
Identification | [Ex ia Ma] I |
[Ex ia Ga] IIC | |
[Ex ia Da] IIIC | |
Ex ec ic [ia Ga] IIC T4 Gc | |
Certificate | DNV 21.0064 X |
EAC Ex | |
Identification | [Ex ia Ga] IIC |
[Ex ia Da] IIIC | |
Certificate | RU C-DE.AB72.B.00093/19 |
DNV GL data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 1 % |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 1 % |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 1 % |
Electrical isolation | 3-way isolation |
GB Standard | |
Standards/regulations | GB 3626.20 |
GB 3836.1 | |
GB 3836.4 | |
GB 3836.8 | |
GB 12476.1 | |
GB 12476.4 |
Mounting type | DIN rail mounting |
Item number | 1052463 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Note | Made to order (non-returnable) |
Sales key | NULL |
Product key | CK3121 |
Catalog page | Page 146 (C-5-2019) |
Weight per piece (including packing) | 182 g |
Weight per piece (excluding packing) | 150 g |
Customs tariff number | 85437090 |
Country of origin | DE |
ECLASS
ECLASS-11.0 | 27210129 |
ECLASS-12.0 | 27210129 |
ECLASS-13.0 | 27210129 |
ETIM
ETIM 8.0 | EC002919 |
UNSPSC
UNSPSC 21.0 | 41112100 |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads” |
Compatible products
-
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - DIN rail bus connectors 2695439
-
EA-MSTB 2,5/ 5 - Accessories 1831016
-
TC-D37SUB-AIO16-EX-PS-UNI - Module carrier 2902932
-
TC-D37SUB-ADIO16-EX-P-UNI - Module carrier 2924854
-
IFS-USB-PROG-ADAPTER - Programming adapter 2811271
-
IFS-BT-PROG-ADAPTER - Adapter 2905872
-
MPS-IH WH - Insulating sleeve 0201663
-
MPS-IH RD - Insulating sleeve 0201676
-
MPS-IH BU - Insulating sleeve 0201689
-
MPS-IH YE - Insulating sleeve 0201692
-
MPS-IH GN - Insulating sleeve 0201702
-
MPS-IH GY - Insulating sleeve 0201728
-
MPS-IH BK - Insulating sleeve 0201731
-
MPS-MT - Test plugs 0201744
-
UC-EMLP (11X9) - Plastic label 0819291
-
UC-EMLP (11X9) YE - Plastic label 0822602
-
UC-EMLP (11X9) CUS - Plastic label 0824547
-
UC-EMLP (11X9) YE CUS - Plastic label 0824548
-
UC-EMLP (11X9) SR - Plastic label 0828094
-
UC-EMLP (11X9) SR CUS - Plastic label 0828098
-
US-EMLP (11X9) - Plastic label 0828789
-
US-EMLP (11X9) YE - Plastic label 0828871
-
US-EMLP (11X9) SR - Plastic label 0828872
-
LS-EMLP (11X9) WH - Device marker 0831678
-
LS-EMLP (11X9) SR - Device marker 0831705
-
LS-EMLP (11X9) YE - Device marker 0831732
-
MACX MCR-PTB - Power and error message module 2865625
-
MACX MCR-PTB-SP - Power and error message module 2924184
-
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply unit 2904614
-
SZS 0,6X3,5 - Screwdriver 1205053
Your advantages
Power supply possible via DIN rail connector
Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
Input for resistance thermometers and resistance-type sensors, [Ex ia] IIC
Installation in zone 2, protection type "ec" (EN 60079-7) permitted
3-way electrical isolation
Status indicator for supply voltage, cable, sensor, and module errors
Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
Output: 0 mA ... 20 mA or 4 mA ... 20 mA