Surge protection device - TTC-6-1X2-TELE-UT
1077107

Surge protection for analog and digital telecommunications interfaces (VDSL up to 300 Mbps, G.fast up to 1.5 Gbps). Integrated overload protection (power-cross).


Product Details




IEC test classification B2
C1
C2
C3
D1
Type DIN rail module, one-piece 
Product type Surge protection for MCR technology
Wire pairs per module 1
Insulation characteristics
Overvoltage category III
Pollution degree 2

Connection method Screw connection
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12

Dimensional drawing
Width 6.2 mm +0.1 mm
Height 105.8 mm
Depth 69.5 mm (incl. DIN rail 7.5 mm)

Color traffic grey A RAL 7042
Flammability rating according to UL 94 V-0
Insulating material PBT
Housing material PBT

Mechanical data
Open side panel No

Maximum continuous voltage UC 60 V DC
Rated current 200 mA
Operating effective current IC at UC ≤ 1 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line) 5 kA
Nominal discharge surge current In (8/20) µs (Core-Earth) 5 kA
Pulse discharge current Iimp (10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-line) ≤ 650 V (B2 - 1 kV)
≤ 800 V (B2 - 4 kV)
≤ 1 kV (C1 - 1 kV / 500 A)
≤ 1.4 kV (C2 - 10 kV / 5 kA)
≤ 850 V (C3 - 15 A)
≤ 1.1 kV (C3 - 25 A)
≤ 1.4 kV (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 600 V (B2 - 1 kV)
≤ 750 V (B2 - 4 kV)
≤ 750 V (C1 - 1 kV / 500 A)
≤ 800 V (C2 - 10 kV / 5 kA)
≤ 650 V (C3 - 15 A)
≤ 750 V (C3 - 25 A)
≤ 1.2 kV (C3 - 100 A)
Response time tA (line-line) ≤ 100 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 1 dB (≤ 40 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 100 MHz
Capacity (Core-Core) typ. 10 pF
Resistance per path 6 Ω
Surge protection fault message none
Impulse durability (line-line) B2 - 4 kV / 100 A
C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth) B2 - 4 kV / 100 A
C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line) ≤ 30 ms
Pulse reset time (line-earth) ≤ 200 ms

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 4000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %

Standards/specifications IEC 61643-21
EN 61643-21
Standards/specifications EN 61643-21

Mounting type DIN rail: TH 35 - 7.5 mm

Item number 1077107
Packing unit 1 pc
Minimum order quantity 1 pc
Product Key CL2261
GTIN 4055626789040
Weight per Piece (including packing) 36.3 g
Weight per Piece (excluding packing) 36.3 g
Country of origin DE


ECLASS

ECLASS-9.0 27130807
ECLASS-10.0.1 27130807
ECLASS-11.0 27130807

ETIM

ETIM 8.0 EC000943

UNSPSC

UNSPSC 21.0 39121600

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Your advantages

For analog and digital (DSL) telecommunications interfaces up to 300 Mbps or 1.5 Gbps with G.fast
Space-saving and inexpensive with a narrow overall width of just 6.2 mm
Safe behavior in the event of overload (power-cross) with integrated short-circuit mechanism and electronic current limiter
Tests by Deutsche Telekom confirm compatibility with VDSL, vectoring VDSL, super-vectoring VDSL (SVVDSL), and G.fast