Surge protection device - DT-TELE-RJ45
2882925

Attachment plug with surge protection for analog and digital telecommunications interfaces (VDSL up to 50 Mbps). Connection: RJ45 (RJ12/RJ11) and screw terminal block (COMBICON). Alternatively, can be snapped onto a DIN rail.


Product Details




IEC test classification B2
C1
C2
C3
D1
Type Attachment plug for DIN rail mounting
Product type Surge protection for information technology
Number of positions 4
Wire pairs per module 2
Insulation characteristics
Overvoltage category II
Pollution degree 2

Connection method RJ45/COMBICON
Screw thread M2
Tightening torque 0.22 Nm
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
Conductor cross section solid 0.14 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16

Dimensional drawing
Width 25 mm
Height 102 mm
Depth 63.5 mm

Color silver/black
Housing material Zinc die-cast

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Ground/Shield
Maximum continuous voltage UC 185 V DC
130 V AC
Rated current ≤ 380 mA (25 °C)
Operating effective current IC at UC ≤ 6 µA
Residual current IPE ≤ 4 µA
Nominal discharge current In (8/20) µs (line-line) ≤ 5 kA
Nominal discharge surge current In (8/20) µs (Core-Earth) ≤ 5 kA
Total discharge current Itotal (8/20) µs 10 kA
Nominal pulse current Ian (10/1000) µs (line-line) 100 A
Nominal pulse current Ian (10/1000) µs (line-earth) 100 A
Nominal pulse current Ian (10/700) µs (line-line) 150 A
Nominal pulse current Ian (10/700) µs (line-earth) 150 A
Output voltage limitation at 1 kV/µs (line-line) static ≤ 250 V
Output voltage limitation at 1 kV/µs (line-earth) static ≤ 250 V
Residual voltage at In (conductor-conductor) ≤ 120 V
Residual voltage at In (conductor-ground) ≤ 120 V
Voltage protection level Up (line-line) ≤ 250 V (B2 - 4 kV / 100 A)
≤ 250 V (C1 - 1 kV / 500 A)
≤ 250 V (C2 - 10 kV / 5 kA)
Voltage protection level Up (line-earth) ≤ 250 V (B2 - 4 kV / 100 A)
≤ 250 V (C1 - 1 kV / 500 A)
≤ 250 V (C2 - 10 kV / 5 kA)
Response time tA (line-line) ≤ 100 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.5 dB (≤ 5 MHz / 100 Ω)
typ. 0.3 dB (≤ 8 MHz / 150 Ω)
typ. 0.3 dB (≤ 2.5 MHz / 600 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ω system typ. 50 MHz
Capacity (Core-Core) typ. 20 pF (f= 1 MHz / VR= 0 V)
Capacity (Core-Earth) typ. 20 pF (f= 1 MHz / VR= 0 V)
Resistance per path 3.3 Ω 10 %
Surge protection fault message none
Impulse durability (line-line) B2 - 4 kV / 100 A
C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
Impulse durability (line-earth) B2 - 4 kV / 100 A
C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
D1 - 1 kA

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C

Standards/specifications IEC 61643-21
Standards/specifications EN 61643-21

Mounting type Connection-specific attachment plug and DIN rail, 35 mm

Item number 2882925
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C08
Product Key CL3221
Catalog Page Page 162 (C-4-2017)
GTIN 4046356155137
Weight per Piece (including packing) 330.5 g
Weight per Piece (excluding packing) 314.324 g
Customs tariff number 85369010
Country of origin DE


ECLASS

ECLASS-9.0 27130807
ECLASS-10.0.1 27130807
ECLASS-11.0 27130807

ETIM

ETIM 8.0 EC000943

UNSPSC

UNSPSC 21.0 39121600

EAC

Approval ID: EAC-Zulassung

EAC

Approval ID: RU C-DE.*09.B.00169

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Compatible Products



Your advantages

Easy network integration via RJ45/COMBICON connection
No signal interference with adapted protective circuit
Can be installed in a control cabinet by removing the ground connection adapter