Surge protection device - D-LAN-CAT.5-HC
2800763

Surge protection for data networks up to 1 Gbps. For use in Ethernet, Power over Ethernet (PoE, mode A and mode B), token ring, ISDN, and DS1. RJ45 attachment plug with separate grounding cable and snap-on foot for NS 35 DIN rails.


Product Details




IEC test classification B2
C2
D1
C1
VDE requirement class B2
C2
D1
C1
Type Attachment plug for DIN rail mounting
Product type Surge protection for information technology
Number of positions 8
Wire pairs per module 4
Insulation characteristics
Overvoltage category II
Pollution degree 2

Connection method RJ45

Dimensional drawing
Width 28 mm
Height 110 mm
Depth 60 mm (incl. NS 35 adapter)

Color gray
Flammability rating according to UL 94 V-0
Housing material PC+ABS

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Ground/Shield
Maximum continuous voltage UC ± 5 V DC
Maximum continuous voltage UC (line-line) ± 5 V DC (± 57 V DC / PoE+)
Rated current ≤ 1.5 A (25 °C)
Operating effective current IC at UC ≤ 600 µA
Nominal discharge current In (8/20) µs (line-line) 350 A
Nominal discharge surge current In (8/20) µs (Core-Earth) 2 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 1 kA
Total discharge current Itotal (8/20) µs 8 kA
Nominal pulse current Ian (10/700) µs (line-line) ≤ 25 A
Nominal pulse current Ian (10/700) µs (line-earth) ≤ 100 A
Nominal pulse current Ian (10/700) µs (line-line) ≤ 25 A
Nominal pulse current Ian (10/700) µs (line-earth) ≤ 100 A
Output voltage limitation at 1 kV/µs (line-line) spike ≤ 25 V
≤ 90 V (PoE)
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 750 V
Residual voltage at In (conductor-conductor) ≤ 35 V
≤ 110 V (PoE)
Residual voltage at In (conductor-ground) ≤ 850 V
Voltage protection level Up (line-line) ≤ 20 V (B2 - 1 kV / 25 A)
≤ 90 V (B2 - 1 kV / 25 A - PoE)
≤ 35 V (C1-700 V/350 A)
≤ 110 V (C1-700 V/350 A-PoE)
Voltage protection level Up (line-earth) ≤ 700 V (B2 - 4 kV / 100 A)
≤ 850 V (C2 - 4 kV / 2 kA)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. ≤ 0.5 dB (100 MHz/100 Ω)
≤ 1 dB (100 MHz/100 Ω/Link Class E)
Near-end crosstalk attenuation typ. 63 dB (1 MHz/100 Ω/Link Class E)
typ. 43 dB (16 MHz / 100 Ω / Link Class E)
typ. 30 dB (100 MHz/100 Ω/Link Class E)
> 40 dB (100 MHz/100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ω system 250 MHz
Capacity (Core-Core) typ. 15 pF (f= 1 MHz / VR= 0 V)
Capacity (Core-Earth) typ. 5 pF (f= 1 MHz / VR= 0 V)
Impulse durability (line-line) B2 - 1 kV / 25 A
C1 - 700 V / 350 A
Impulse durability (line-earth) B2 - 4 kV / 100 A
C2 - 4 kV / 2 kA
D1 - 1kA
Additional technical data
Max. total discharge current I total max (8/20) µs 10 kA (1x)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %

VDE requirement class B2
C2
D1
C1
Air clearances and creepage distances
Standards/regulations VDE 0110-1 / IEC 60664
Standards/specifications IEC 61643-21/A1
Standards/specifications GB/T 18802.21
Standards/specifications EN 61643-21/A1
Standards/specifications IEC 61643-21

Mounting type Connection-specific attachment plug and DIN rail, 35 mm

Item number 2800763
Packing unit 1 pc
Minimum order quantity 1 pc
Note Made to Order (non-returnable)
Sales Key C08
Product Key CL3112
GTIN 4046356730280
Weight per Piece (including packing) 178 g
Weight per Piece (excluding packing) 25 g
Customs tariff number 85363030
Country of origin CN


ECLASS

ECLASS-9.0 27130807
ECLASS-10.0.1 27130807
ECLASS-11.0 27130807

ETIM

ETIM 8.0 EC000943

UNSPSC

UNSPSC 21.0 39121600

UL Listed

Approval ID: FILE E 138168

REACh SVHC Lead 7439-92-1