Product type Safety relays
Application Extension module
Mechanical service life approx. 107 cycles
Relay type Safety relay for contact extension
Insulation characteristics
Overvoltage category III
Times
Typ. starting time with Us < 20 ms (at Us / when controlled via A11/A12)
Typical release time < 20 ms (at Us / when controlled via A11/A12)
Recovery time < 1 s

Maximum power dissipation for nominal condition 15.8 W (US = 26.4 V, IL² = 72 A², PTotal max = 1.4 W + 14.4 W)
Nominal operating mode 100% operating factor
Rated insulation voltage 250 V
Rated surge voltage/insulation See section “Insulation coordination”

Rated control circuit supply voltage US 24 V -20 % ... +10 %
Power consumption at US 1 W (with DC)
1.2 W (with AC)
Rated control supply current IS typ. 39 mA (per channel, DC)
typ. 50 mA (per channel, AC)
Inrush current typ. 200 mA (Δt = 2 ms at Us, per channel)
Protective circuit Surge protection; Varistor (40 V breakdown voltage)

Contact type 5 enabling current paths
1 signaling current path
1 confirmation current path
Contact material AgSnO2
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V AC/DC
Limiting continuous current 6 A (N/O contact)
3 A (N/C contact 11/12)
6 A (N/C contact 71/72)
Maximum inrush current 6 A
Inrush current, minimum 10 mA
Sq. Total current 72 A2 (ITH2 = I12 + I22 + ... + I52)
Switching capacity min. 50 mW
Switching capacity according to IEC 60947-5-1 3 A (AC15)
5 A (DC13)
Output fuse 10 A gL/gG (N/O contact)
6 A gL/gG (N/C contact)
Relay
Interrupting rating (ohmic load) max. see load limit curve

Connection technology
pluggable yes
Conductor connection
Connection method Push-in connection
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG 24 ... 16

Operating voltage display 2 x green LED

Width 35 mm
Height 112 mm
Depth 114.5 mm

Housing material Polyamide
Housing color yellow

Safety data
Stop category 0
Safety data: EN ISO 13849
Category 4 (In conjunction with suitable evaluating device)
Performance level (PL) e (In conjunction with suitable evaluating device)
Safety data: IEC 61508 - High demand
Equipment type Type A
Safety Integrity Level (SIL) 3 (In conjunction with suitable evaluating device)
Probability of a hazardous failure per hour (PFHD) 9.04 x 10-11 (3 A DC13; 3 A AC15; 8760 switching cycles/year)
Proof test interval 240 Months
Duration of use 240 Months
Safety data: IEC 61508 - Low demand
Equipment type Type A
Safety Integrity Level (SIL) 3 (In conjunction with suitable evaluating device)
Probability of a hazardous failure on demand (PFDAVG) 1.46 x 10-4
Proof test interval 110 Months
Duration of use 240 Months

Ambient conditions
Degree of protection IP20
Min. degree of protection of inst. location IP54
Ambient temperature (operation) -20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Maximum altitude ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Shock 15g
Vibration (operation) 10 Hz ... 150 Hz, 2g

Air clearances and creepage distances between the power circuits
Standards/regulations EN 60947-5-1

Mounting type DIN rail mounting
Assembly instructions Observe derating
Mounting position vertical or horizontal

Item number 2964005
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key C18
Product Key DNA152
Catalog Page Page 232 (C-6-2019)
GTIN 4017918904739
Weight per Piece (including packing) 302.38 g
Weight per Piece (excluding packing) 270.18 g
Customs tariff number 85371098
Country of origin DE


ECLASS

ECLASS-9.0 27371819
ECLASS-10.0.1 27371819
ECLASS-11.0 27371819

ETIM

ETIM 8.0 EC001449

UNSPSC

UNSPSC 21.0 39122200

EAC

Approval ID: RU C-DE.A*30.B.01082

UL Listed

Approval ID: FILE E 140324

cUL Listed

Approval ID: FILE E 140324

cULus Listed


China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Five enabling, one signaling, and one confirmation current path
1- and 2-channel control
Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with IEC 62061, SIL 3 in accordance with IEC 61508